11

Configuration

of the EC reading, even with highly variable flow rates.

PEC=0 PI control.

 PIQ control disabled.

PEC= 0.01 - 2% 

Dosing will be proportional to the water flow at the % rate entered and with adjustment to 

setpoint through a PI algorithm.

- PIQ (PpH):

The PIQ control mode to adjust pH is a PI algorithm conditioned on the flow rate of water to be treated. 
Initial dosing proportional to the water rate is set using the PpH parameter, and is subsequently corrected 
by means of a PI approximation curve. This system, which can only be activated with independent pumps 
(type mA outlets for acid/alkaline dosing), ensures pH stability even with highly variable flow rates and 
provides greater agility in reaching and maintaining the

setpoint.

PpH=0 PI control. PIQ control disabled.
PpH= 1 - 200 Acid dosing will be proportional to the water flow rate with setpoint adjustment by means 
of a PI algorithm. The proportion is indicated by the PpH parameter and is referenced to 100,000 units of 
water flow.

Example: For a flow rate of 200,000 l/h of water and a PpH = 1, proportional dosing of acid will be: (1 / 
100,000) x 200,000 l/h = 2 l/h

The proportion needed to achieve a specific pH will depend not only on its nature and concentration, but 
also on the nature of the water to be treated and the rest of the dosed products that can influence this 
parameter. The range PpH recommended to rapidly reach a pH and maintain it stable are detailed below.
The following tables for different acids are an approximation to the PpH value for these acids, depending 
on the pH correction required (1 or 2 points of pH).

- Kp:

Proportional constant for PI adjustment. This parameter enables adjustment of the amount of device 
response based on the difference between the reading and the setpoint (Error). The default value 
is normally correct for the majority of in-line controls. A value that is too high  will produce reading 
oscillations around the setpoint value. A value that is too low will produce a slow approach to the setpoint.

A

1 point 2 points

60%

4-10

10-20

40%

8-15

15-30

10%

30-60

60-120

5%

60-110

120-200

A

1 point 2 points

80%

3-8

8-15

50%

6-15

15-25

10%

30-60

60-120

5%

60-110 120-200

A

1 point 2 points

90%

1-13

2-5

50%

2-5

4-10

10%

10-25

20-50

5%

20-50

40-100

Table for nitric acid

Note: Column "A" corresponds to the acid concentration

Table for phosphoric acid

Table for sulphuric acid

Содержание WTRTEC Green

Страница 1: ...WTRTEC ENGLISH...

Страница 2: ...ration 9 4 4 1 Activation of the control 9 4 4 2 Advanced control configuration PI control 10 4 5 Alarms 12 4 5 1 EC and pH alarms 12 4 5 2 Zero flow alarm 13 4 5 3 Flow detector alarm 13 4 6 Configur...

Страница 3: ...oning and maintaining the equipment must follow the instructions in this manual with special attention to the detailed recommendations and warnings The specific instructions for the use of the chemica...

Страница 4: ...20 mA control is specially designed to provide in line control adapted to flow rate changes PIQ The WTRTEC enables remote monitoring and management by means of a mobile web application A communication...

Страница 5: ...0 00 mS Isolated EC temperature sensor 0 0 100 C 32 0 212 F NTC pH sensor 0 00 14 00 Isolated pH EC temperature sensor 0 0 100 C 32 0 212 F PT100 Remote input ON OFF 12 24 V AC DC Flow detector ON OFF...

Страница 6: ...g parameter alarm Flashing regulation output no device detected on the 4 20 mA output Flashing regulation outputs both remote control deactivated or no device connected to the 4 20 mA outputs Press EN...

Страница 7: ...lower right quadrant of the main screen The second control channel is for pH To enter the setpoint m3h CAL CONTROL ALARM ALARM DETECTOR REGISTER 0 20 SP mS CAL CONTROL ALARM REGISTER SP 02 00 change...

Страница 8: ...sing ESCAPE CAL m3h 0 20 SP CAL CONTROL ALARM ALARM DETECTOR REGISTER Q CAL Type Low Freq K 5 00 l p Time Q 0 015 s Select the type of flow meter Low Freq Low frequency flow meter Flow meters with pul...

Страница 9: ...dosing choose between the options Flow Rate control proportionality Dosing will be regulated depending on the value entered as the setpoint value representing the percentage of product flow rate dose...

Страница 10: ...ng tank The regulating output establishes 5 minute cycles in which the output will be ON for the proportional part of the time corresponding to PI adjustment Limit out If a 4 20 mA output is used this...

Страница 11: ...cid will be 1 100 000 x 200 000 l h 2 l h The proportion needed to achieve a specific pH will depend not only on its nature and concentration but also on the nature of the water to be treated and the...

Страница 12: ...d leave Qtest 0 Example In a 8 pipe through which water passes at 100 m3 h the water speed is approximately 1 m s If the distance between the injection point and the sensor is 10 metres the installati...

Страница 13: ...reset when the reading is back within the permissible values Stop enables shutting down of the dosing control output for the alarmed control parameter for all or none 4 5 2 Zero flow alarm An alarm c...

Страница 14: ...0 mA 2 4 mA 00 00 20 mA 14 00 ENT Reset enables automatic alarm reset when the reading is back within the permissible values Stop enables the dosing control outputs to be shut down 4 6 Configuration o...

Страница 15: ...r which includes an internal temperature sensor the reading will be the measure by this sensor LCD auto Energy saving option that allowing for switching off of the screen if no action has taken place...

Страница 16: ...adings CONFIG SET UP COMUNICATIONS CHECK MONITOR Serial No 9999 Soft Vers 1 07 Hard Vers 0 00 Model GREEN INFO UNIT mV pH 0 4 Temp 24 1 Ohms EC 0 22 Temp EC 24 1 Flow Hz 0 00 Pulse Flow ON SENSORS ENT...

Страница 17: ...lternative system for obtaining a homogeneous mixture Q 0 mS 2 5 PH m3h 10 5 7 6 1 0 01 C 21 0 Device Mixer D V m s v m s d It must be ensured that the velocity in the branch of diameter d is the same...

Страница 18: ...ut Relay 4 Control relay output Relay 5 4 20 mA output Output 1 4 20 mA output Output 2 Temperature sensor input PT100 Temperature sensor input NTC ITC EC sensor Flow detector input Input for pH senso...

Страница 19: ...connection in case of emergency must be installed The equipment must be protected to prevent abrupt starts 5 3 Remote start stop activation 2 100 240 VAC power supply External voltage free signal 12 2...

Страница 20: ...n Configure the equipment Setpoint Type of control Installation and equipment configurations 3 Check readings Start up the installation and check that the sensor reading are correct 4 Check operation...

Страница 21: ...21 Maintenance 7 MAINTENANCE 45602 45603 45604 45606 40604 44619 45606 45607 45 618 M12 45 615 M12 45 616 M12 45 618 M12...

Страница 22: ...607 Female angled terminal strip 4 pins 3 81 pitch black 2 44619 Female angled terminal strip 3 pins 5 pitch 2 40604 Female angled terminal strip 6 pins 5 pitch 1 45605 Female angled terminal strip 3...

Страница 23: ...nstruction manual Ant n Planas Manager WARRANTY I T C S L guarantees the product specified in this document for a period of 1 year from the date of purchase against all manufacturing or material defec...

Страница 24: ...ginal Manual Ed 6 3 2020 EN C Vall s 26 Pol Ind Can Bernades Subir P O Box 60 08130 Santa Perp tua de Mogoda BARCELONA SPAIN Tel 34 93 5443040 Fax 34 93 5443161 e mail itc itc es www itc dosing pumps...

Отзывы: