Power Factor Controller 

PFC96evo

 

Front keyboard

 

 

Key

  

-

 Used to select among available measurements. Used also to access programming menus.

 

 

 

keys

 

-

 Used to set values and to select steps. 

 

 

 

 

key

 

-

 

Used to select opera!ng mode between manual and automa!c.

 

Display indica!ons

 

Output

 

status

 

Cooling fan 

status

 

Secondary 

display

 

Ac!ve 

alarm

 

Automa!c 

mode

 

Manual 

 

mode

 

Main 

display

 

Induc!ve / 

capaci!ve

 

Bar 

 

graph

 

Alphanumeric 

 

display

 

Step 

 

status

 

Opera!ng modes

 

There are two possible opera!ng modes, listed below:

 

MAN and AUT modes

 

· 

The icons AUT and MAN indicate the opera•ng mode automa•c or manual.

 

· 

To change the mode,  press and hold the           

bu!on

 

 for 1 sec.

 

· 

The opera•ng mode remains stored even a"er removing and reapplying the power supply voltage.

 

MAN mode

 

· 

When  the  unit  is  in  manual  mode,  you  can  select  one  of  the  steps  and  manually  connected  or 
disconnect it.

 

· 

In  addi•on  to  the  specific  icon,  the  alphanumeric  display  shows 

MAN

    in  order  to  highlight  the 

manual mode condi•on. Press               to view the other measurements as usual.

 

· 

While the display shows 

MAN

, it is possible to select the step to be switched on or off. To select a 

step, use the               or                 bu!ons. The selected step will flash quickly.

 

· 

Press               to ac•vate or deac•vate the selected step.

 

· 

If the selected step has not yet exhausted the reconnec•on •me, the          icon  will  flash  to 
indicate that the transac•on has been accepted and will be conducted as soon as possible.

 

· 

Manual configura•on of the steps is maintained even when the power supply voltage is removed. 
When the power returns, the original state of the steps is restored.

 

 MAN 
mode 

 

icon

 

Connected 

steps

 

Tot kvar 

inserited in 

MAN

 

Manual step 

selec•on 

enabled

 

Select step

 

Change step status

 

AUT mode

 

· 

In automa•c mode, the controller calculates the op•mum configura•on of capacitor steps in order 
to reach the set cosø.

 

· 

The  selec•on  criteria  takes  into  account  many  variables  such  as:  the  power  of  each  step,  the 
number of opera•ons, the total •me of use, the reconnec•on •me, etc.

 

· 

The controller displays the imminent connec•on or disconnec•on of the steps with the flashing of 
their iden•fica•on number (le"). The flashing can last in cases in which the inser•on of a step is 
not possible due to the reconnec•on •me (discharge •me of the capacitor).

 

· 

The device ini•ates automa•c correc•ons when there is an average  reac•ve power request (delta

-

kvar) higher than 50% of the smallest step, and the measured cosø  is different from the setpoint.

 

Voltage

 

V

 

 RMS voltage of the plant current.

 

 

V HI

 

 Maximum voltage value measured.

 

Measure

 

Icon

 

Descrip!on

 

Delta

-

kvar

 

Δ

kvar

 

 Kvars needed to reach the cosø setpoint. If delta

-

kvar is posi•ve cpacitors     

 

 need to be inserted, if nega•ve to be disconnected.

 

 

kvar

 

 Total kvar of the plant.

 

 

Δ

STEP

 

 Number of equal steps to achieve the target power factor.

 

Current

 

A

 

 RMS current of the plant voltage.

 

 

A HI

 

 Maximum current value masured.

 

Weekly PF

 

WPF

 

 Weekly average power factor.

 

 

PF

 

 Instantaneous total power factor.

 

THD cap.

 

THDC

 

 Capacitors total harmonic distor•on  (THD) in current.

 

 

TC.HI

 

 Maximum THD value measured.

 

Temperature

 

°C  °F

 

 Temperature of internal sensor.

 

 

°CHI  

 

°FHI

 

 Maximum temperature value measured.

 

Voltage THD

 

THDV

 

 Total harmonic distor•on % (THD) of plant voltage.

 

 

VH02…

 

...VH15

 

 % voltage harmonic content from 2.nd up to 15.th order

 

Current THD

 

THDI

 

 Total harmonic distor•on % (THD) of plant current.

 

 

IH02…

 

…IH15

 

 % Current harmonic content from 2.nd up to 15.th order

 

Cosø setpoint

 

IND 

 

CAP

 

 Se'ng of desired cosø setpoint (same as P.19).

 

Step power

 

%

 

  

 Step residual power, as a percentage of the set rated power.

 

Step counter

 

OPC

 

  

❶ 

Opera•on counter of the step.

 

Step hours

 

H

 

  

❶ 

Hour meter of the step inser•on.

 

  ❶ 

These  measures  are  shown  only  if  the  S

tep  trimming

  func•on  is  enabled  (P.25=ON)    and  the 

advanced password is enabled and entered.

 

Keypad lock

 

· 

A  func•on  to  exclude  all  modifica•on  to  opera•ng  parameters  can  be  enabled;  measurement 
viewing is s•ll provided in any case.

 

· 

To lock and unlock the keypad, press and keep              key pressed. Then press the      

key 

three •mes and the               key twice and a"er that release

 

· 

The display will show 

LOC

 

when the keypad is locked and 

UNL

 

when it is unlocked.

 

· 

When the lock is enabled, it is not possible to make the following opera•ons:

 

à 

Opera•on between automa•c and manual mode

 

à 

Access to set

-

up menus

 

à 

Change of cosø set

-

point

 

· 

By a!emp•ng to conduct the above opera•ons, the display will view 

LOC

 to indicate the locked 

Measurements

 

· 

The 

PFC96evo

 controller provides a set of measurements displayed on the alphanumeric display, in 

conjunc•on with the current cosø that is always displayed on the main display.

 

· 

Press the              key to scroll through the measures in rota•on.

 

· 

A"er  30  seconds  without  pressing  any  bu!ons,  the  display  automa•cally  returns  to  the  default 
measurement defined by P.47.

 

· 

If P.47 is set on the ROT, then the measures rotate automa•cally every 5 seconds.

 

· 

At the bo!om of the list of measures it is possible to set the setpoint of the cosø, ac•ng on the 
same value set with P.19.

 

· 

Below is a table with the measurements displayed.

 

Parameter se"ng (SETUP) from panel

 

To access the programming menu (setup) :

 

· 

To enter parameter programming the unit must be in TEST mode (first programming)

 

Indica•on 

of TEST 

mode

 

Total 

number 

 

of steps

 

Firmware 

revision

 

Model 

variant

 

or in 

MAN

 mode.

 

 

MAN 

mode icon

 

Connected 

steps

 

Tot kvar 

inserited in 

MAN

 

Manual 

step 

selec•on 

enabled

 

· 

From the normal measurement display, press and hold               for  3  seconds  to  recall  the  main 
menu. 

SET

  is displayed on the main display.

 

· 

 If  you  have  set  the  password  (P.21  =  ON)  instead  of 

SET

  the  display  shows 

PAS

  (password  entry 

request). Set the numeric password using                           and then press             to move to next 
digit.

 

· 

If the password is correct the unit will show 

OK  U

 or 

OK  A

 depending on the entered password is 

user or the advanced level. The password can be defined with parameters P.22 and P.23. Factory 
default is 

001

 and 

002

 respec•vely.

 

· 

If the entered password is wrong the unit will show  

ERR

.

 

· 

A"er  having  entered  the  password,  the  access  is  enabled  un•l  the  unit  is  re

-

ini•alized  or  for  2 

minutes without pressing any key.

 

· 

A"er having entered the password, repeat the procedure to access the parameter se#ng.

 

· 

Press                                                to  select  the  desired  submenu  (

BAS

à 

ADV

à   

ALA 

...  )  that  is  shown  on  the 

alphanumeric display.

 

E

N

 

Содержание PFC144evo

Страница 1: ...8311 Fax 390516605594 E mail italfarad italfarad com Web www italfarad com APPARECCHIATURE AUTOMATICHE DI RIFASAMENTO MANUALE OPERATIVO D INSTALLAZIONE USO E MANUTENZIONE AUTOMATIC POWER FACTOR CORREC...

Страница 2: ...ItalfaradS p A ViaIVNovembren 140061MinerbioBolognaItaly Tel 390516618311 Fax 390516605594 E mail italfarad italfarad com Web www italfarad com 2...

Страница 3: ...eneral remarks 13 Connec on to the network 13 Start and use 13 Control of the automa c opera on 14 Maintenance 14 Connec on diagram 15 CT Connec on place 15 Power factor controller PFC96evo 16 Power f...

Страница 4: ...fuses on the capacitor banks provided with signal The e ciency of the coolong system checking that the fans are not defec ve or mechanically blocked and cleaning with an air jet the relevamt grilles T...

Страница 5: ...ItalfaradS p A ViaIVNovembren 140061MinerbioBolognaItaly Tel 390516618311 Fax 390516605594 E mail italfarad italfarad com Web www italfarad com 15 E N...

Страница 6: ...tor THD cap THDC Capacitors total harmonic distor on THD in current TC HI Maximum THD value measured Temperature C F Temperature of internal sensor CHI FHI Maximum temperature value measured Voltage T...

Страница 7: ...04 Reading the connec on polarity of the CT AUT Polarity is automa cally detected at power up Can only be used when working with only one CT and when the system has no generator device Dir Automa c de...

Страница 8: ...o high is generated P 42 Undervoltage alarm threshold referred to the rated voltage set with P 07 below which the alarm A05 voltage too low is generated P 43 Maximum installa on voltage THD alarm thre...

Страница 9: ...quest delta kvar higher than 50 of the smallest step and the measured cos is di erent from the setpoint Measures The PFC144evo controller provides a set of measurements displayed on the alphanumeric d...

Страница 10: ...able Below are listed all the programming parameters in tabular form For each parameter are indicated the possible se ng range and factory default as well as a brief explana on of the func on of the p...

Страница 11: ...ld be exceeded P 29 Setpoint used when the system is genera ng ac ve power to the supplier with nega ve ac ve power power factor P 30 Disconnection sensitivity Same as the previous parameter but relat...

Страница 12: ...OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO Date Signature EXTRA ORDINARY MAINTENANCE REGISTR...

Страница 13: ...ItalfaradS p A ViaIVNovembren 140061MinerbioBolognaItaly Tel 390516618311 Fax 390516605594 E mail italfarad italfarad com Web www italfarad com 23...

Страница 14: ...iabile per l ITALFARAD i condensatori utilizzati sono conformi alla EN 60831 1 2 IEC 831 1 2 i quadri hanno superato le prove di tipo previste dalle Norme CEI EN 60439 1 CEI 17 13 1 L ITALFARAD S p A...

Отзывы: