Power Factor Controller 

PFC144evo

 

P.10

 

-

 Connection sensitivity. This parameter sets the speed of reaction of the controller. With small values 

of P.10 the regulation is fast (more accurate  around the setpoint but with more step swithchings). 
With high values instead we’ll have slower reactions of the regulation, with fewer switchings of the 
steps. The delay time of the reaction is inversely proportional to the request of steps to reach the 
setpoint:  waiting time = (sensitivity / number of steps required).

 

Example

: setting the sensitivity to 60s, if you request the insertion of one step of weight 1 are 

expected 60s (60/1 = 60). If instead serve a total of 4 steps will be expected 15s (60/4 = 15).

 

P11 ... P18 

-

 Func!on of output relays 1 ... 8:

 

OFF

 = Not used .

 

1 .. 32

 = Weight of the step. This relay drives  a bank of cpacitors which power is n !mes (n 

= 1…32) the smallest power defined with parameter P.06.

 

ON

 = Always on.

 

NOA 

=  Alarm  normally  de

-

energized.  The  relay  is  energized  when  any  alarm  with  the 

Global alarm

 property  arises.

 

NCA

  =  Alarm  normally  energized.  The  relay  is  de

-

energized  when  any  alarm  with  the 

Global alarm

 property arises.

 

FAN

 = The relay controls the cooling fan.

 

MAN = 

Relay is energized when device is in MAN mode.

 

AUT = 

Relay is energized when device is in AUT mode.

 

A01 ... A12

= The relay is energized when the alarm specified is ac!ve.

 

P19

 

-

 Setpoint (target value) of the cosø. Used for standard applica!ons.

 

P20

 

-

 Language of scrolling alarm messages.

 

Advanced menu

 

COD

 

DESCRIPTION

 

PSW

 

UoM

 

DEF

 

RANGE

 

P.21

Password enable

 

Adv

 

  

OFF

 

OFF

 

ON

 

P.22

User password

 

Usr

 

  

001

 

0

-

999

 

P.23

Advanced password

 

Adv

 

  

002 

(*)

 

0

-

999

 

P.24

Wiring type

 

Usr

 

  

3PH

 

3PH  three

-

phase

 

1PH   single

-

phase

 

P.25

Step trimming

 

Usr

 

  

ON

 

ON  Enabled / OFF  Disabled

 

P.26

Setpoint cle

 

Usr

 

  

0.00

 

0 – 0.10

 

P.27

Setpoint clearance 

Usr

 

  

0.00

 

0 – 0.10

 

P.28

Step inser!on mode

 

Usr

 

  

STD

 

STD  Standard / LIN  Linear

 

P.29

Cogenera!on cosø setpoint

 

Usr

 

  

OFF

 

OFF / 0.50 IND – 0.50 CAP

 

P.30

Disconnec!on sensi!vity

 

Usr

 

sec

 

OFF

 

OFF / 1 – 600

 

P.31

Step disconnec!on passing in MAN

 

Usr

 

  

OFF

 

OFF  Disabled / ON  Enabled

 

P.32

Capacitor current overload alarm 
threshold

 

Adv

 

%

 

50

 

OFF / 0...150

 

P.33

Capacitor overload immediate 
disconnec!on threshold

 

Adv

 

%

 

83

 

OFF / 0.. 200

 

P.34

VT primary

 

Usr

 

V

 

OFF

 

OFF / 50

-

50000

 

P.35

VT secondary

 

Usr

 

V

 

100

 

50

-

500

 

P.36

Temperature UoM

 

Usr

 

  

°C

 

°C °Celsius ; °F °Fahrenheit

 

P.37

Fan start temperature

 

Adv

 

°

 

25

 

0 .. 212

 

P.38

Fan stop temperature

 

Adv

 

°

 

20

 

0 .. 212

 

P.39

Temperature alarm threshold

 

Adv

 

°

 

55

 

0 .. 212

 

P.41

Maximum voltage alarm threshold

 

Adv

 

%

 

110

 

OFF / 90...150

 

P.42

Minimum voltage alarm threshold

 

Adv

 

%

 

90

 

OFF / 60..110

 

P.43

THD V alarm threshold

 

Adv

 

%

 

6

 

OFF / 1..250

 

P.44

THD I alarm threshold

 

Adv

 

%

 

12

 

OFF / 1..250

 

P.45

Maintenance interval

 

Adv

 

h

 

9000

 

8760

(**)

 

-

 30000

 

P.46

Bar

-

graph func!on

 

Usr

 

  

Kvar ins/tot

 

Kvar ins/tot

 

Corr  a"/nom

 

Delta kvar  a"/tot

 

P.47

Default auxiliary measure

 

Usr

 

  

Week TPF

 

Deltakvar

 

V

 

A

 

Week TPF

 

Cap. Current

 

Temp

 

THDV

 

THDI

 

ROT

 

P.48

Backlight flashing on alarm

 

Usr

 

  

OFF

 

OFF / ON

 

P.49

Serial node address

 

Usr

 

  

01

 

01

-

255

 

P.50

Serial speed

 

Usr

 

bps

 

9.6k

 

1.2k

 

2.4k

 

4.8k

 

9.6k

 

19.2k

 

38.4k

 

P.51

Data format

 

Usr

 

  

8 bit – n

 

8 bit, no parity

 

8 bit, odd

 

8bit, even

 

7 bit, odd

 

7 bit, even

 

P.52

Stop bits

 

Usr

 

  

1

 

1

-

2

 

P.53

Protocol

 

Usr

 

  

Modbus RTU

 

Modbus RTU / Modbus 

ASCII

 

P.54

Number of insertions for maintenance

 

Adv

 

kcnt

 

OFF

 

OFF / 1...60

 

P.55

Step 9 func!on

 

Usr

 

 

OFF

 

=

 

P.56

Step 10 func!on

 

Usr

 

 

OFF

 

=

 

P.57

Step 11 func!on

 

Usr

 

 

OFF

 

=

 

P.58

Step 12 func!on

 

Usr

 

 

OFF

 

=

 

P.59

Step 13 func!on

 

Usr

 

 

OFF

 

=

 

P.60

Step 14 func!on

 

Usr

 

 

OFF

 

=

 

P.21

 – If set to OFF, password management is disabled and anyone has access to the settings and commands menu.

 

P.22

 – With P.21 enabled, this is the value to specify for activating user level access. See Password access chapter.

 

P.23

 – As for P.22, with reference to Advanced level access. 

(*) Available value only if the controller is 

not installed on the ITALFARAD cabinet

 

P.24

 – Number of phases of the power correc!on panel.

 

P.25 

-

 Enables the measurement of the actual power of the step, performed each time they are switched in. 

The measure is calculated, as the current measurement  is referred to the whole load of the plant.  
The measured power of the steps is adjusted (trimmed) after each switching  and is displayed on the 
step  life  statistic  page.  When  this  function  is  enabled,  a  15  sec  pause  is  inserted  between  the 
switching of one step and the following, necessary to measure the reactive power variation.

 

P.26  –  P.27 

-

  Tolerance  around  the  setpoint.  When  the  cosø  is  within  the  range  delimited  by  these 

parameters, in AUT mode the device does not  connect / disconnect  steps even if the 
delta

-

kvar is greater than the smallest step.

 

P.28

 

-

  Selec!ng mode of steps inser!on.

 

Standard mode 

-

 

Normal opera!on with free selec!on of the steps

 

Linear  mode 

-

 

the steps are connected in progression from le$ towards right only following 

the  step  number  and  according  to  the  LIFO  (Last  In  First  Out)  logic.  The  controller  will  not 

connect a step when the system steps are of different ra!ngs and by connec!ng the next step, 
the set

-

point value would be exceeded.

 

P.29

 

-

 Setpoint used when the system is genera!ng ac!ve power to the supplier (with nega!ve ac!ve 

power / power factor ).

 

P.30

 

-

 Disconnection sensitivity. Same as the previous parameter but related to disconnection. If set to OFF 

the disconnection has the same reaction time of connection set with the previous parameter.

 

P.31 

-

 

If set to ON, when switching from 

AUT

 mode to 

MAN

 mode, steps are disconnected in sequence.

 

P.32  – 

Trip  threshold  for  the    capacitors  overload  protec!on  (alarm  A08),  that  will  arise  a$er  a 

integral delay !me, inversely propor!onal to the value of the overload.

 

Note: 

You  can  use  this  protec!on  only  if  the  capacitors  are  not  equipped  with  filtering 

devices such as inductors or similar.

 

P.33 

-

 

Threshold  beyond  which  the  integral  delay  for  tripping  of  the  overload  alarm    is  zeroed, 

causing the immediate interven!on of the 

A08

 alarm.

 

P.34 – P.35 –  

Data of  VTs  eventually used in the wiring diagrams.

 

P.36

 – Unit of measure for temperature.

 

P.37  – P.38 

-

 

Start and stop temperature for the cooling fan of the panel, expressed in the unit set by P.36. The 

cooling fan is started when the temperature is >= to P.37 and it is stopped when it is < than P.38.

 

P.39 

-

 

Threshold for genera!on of alarm 

A08 Panel temperature too high

 .

 

P.41

 

-

 Maximum voltage alarm threshold, referred to the rated voltage set with P.07, beyond which 

the alarm 

A06 Voltage too high

 is generated.

 

P.42

 

-

  Undervoltage  alarm  threshold,  referred  to  the  rated  voltage  set  with  P.07,  below  which  the 

alarm  

A05 voltage too low

 is generated.

 

P.43

 

-

 Maximum installa!on voltage THD alarm threshold, beyond which the alarm 

A10 THDV too high

 

is generated.

 

P.44

  – Maximum installa!on current THD alarm threshold beyond which the alarm  

A05 voltage too 

low

 is generated.

 

P.45

  – Maintenance interval in hours. When it is  elapsed, the alarm 

A12 Ordinary maintenance 

 will 

be  generated.  The  hour  count  increments  as  long  as  the  device  is  powered. 

(**)  If  the 

controller is installed on the ITALFARAD cabinet

 

 P.46

 – Func!on of the semi

-

circular bar

-

graph.

 

Kvar ins/tot:

 The bar graph represents the amount of kvar actually inserted, with reference 

to the total reac!ve power installed in the panel.

 

Curr act/nom

:  Percentage of actual plant current with reference to the maximum current of the CT.

 

Delta  kvar:

 bar graph with central zero. It represts the posi!ve/nega!ve delta

-

kvar needed 

to reach the setpoint, compared to the total kvar installed.

 

 

P.47

 – Default measure shown on the secondary display. Se'ng the parameter to 

ROT

, the different 

measures will be shown with a sequen!al rota!on.

 

P.48

 – 

If set to ON, the display backlight flashes in presence of one or more ac!ve alarms.

 

P.49

 – Serial (node) address of the communica!on protocol.

 

P.50

 – Communica!on port transmission speed.

 

P.51

 – Data format. 7 bit se'ngs can only be used for ASCII protocol.

 

P.52

 – Stop bit number.

 

P.53

 – Select communica!on protocol.

 

P.54 

-

 Defines the number of the step (considering the step that has the highest count) beyond which 

the maintenance alarm A12 is generated. This parameter should  be used as an alterna!ve to 
P.45. If both P.45 and P.54 are set to a value other than OFF, then P.45 has priority.

 

P.55...P.60 

-

 Func!on of output relays 9...14. See descrip!on of parameter.

 

Alarms

 

· 

When an alarm is generated , the display will show an alarm icon, the code and the descrip!on 
of the alarm in the language selected.

 

· 

If  the  naviga!on  keys  in  the  pages  are  pressed,  the  scrolling  message  showing  the  alarm 
indica!ons will disappear momentarily, to reappear again a$er 30 seconds.

 

· 

Alarms  are  automa!cally  rese"ed  as  soon  as  the  alarm  condi!ons  that  have  generated  them 
disappear.

 

· 

In the case of one  or more alarms, the  behaviour  of the 

PFC144evo

  regulator depends  on the 

proper•es

 

se•ngs of the ac•ve alarms.

 

COD

 

ALLARME

 

DESCRIPTION

 

A01

 

Undercompensa•on

 

In  automa•c  mode,  all  the  available  steps  are  connected  but  the 
cosø is s•ll more induc•ve than the setpoint.

 

A02

 

Overcompensa•on

 

In  automa•c  mode,  all  the  steps  are  disconnected  but  the  cosø  is 
s•ll more capaci•ve than the setpoint.

 

A03

 

Current too low

 

The  current  flowing  in  the  current  inputs  is  lower  than  minimum 
measuring range.

 

This condi•on can occour normally if the plant has no load.

 

A04

 

Current too high

 

The  current  flowing  in  the  current  inputs  is  lower  than  minimum 
measuring range.

 

A05

 

Voltage too low

 

The measured voltage is lower than the threshold set with P.42.

 

A06

 

Voltage too high

 

The measured voltage is higher than the threshold set with P.41.

 

A07

 

Capacitor current  
overload

 

The  calculated  capacitor  current  overload  is  higher  than  threshold 
set with P.32 and P.33. A"er the alarm condi•ons have disappeared, 
the  alarm  message  remains  shown  for  the  following  5  min  or  un•l 
the user presses a key on the front.

 

A08

 

Temperature too high

 

The panel temperature is higher than threshold set with P.39.

 

A09

 

No

-

Voltage release

 

A no

-

voltage release has occurred on the line voltage inputs, las•ng 

more than 8ms.

 

A10

 

Voltage THD too high

 

The THD of the plant voltage is higher than the threshold set with P.43.

 

A11

 

Current THD too high

 

The THD of the plant current is higher than the threshold set with P.44.

 

A12

 

Maintenance 
requested

 

The maintenance interval set with P.45 or P.54 has elapsed. To reset 
the alarm see Command menu.

 

For further information, the complete user manual is available in our web site.

 

E

N

 

Содержание PFC144evo

Страница 1: ...8311 Fax 390516605594 E mail italfarad italfarad com Web www italfarad com APPARECCHIATURE AUTOMATICHE DI RIFASAMENTO MANUALE OPERATIVO D INSTALLAZIONE USO E MANUTENZIONE AUTOMATIC POWER FACTOR CORREC...

Страница 2: ...ItalfaradS p A ViaIVNovembren 140061MinerbioBolognaItaly Tel 390516618311 Fax 390516605594 E mail italfarad italfarad com Web www italfarad com 2...

Страница 3: ...eneral remarks 13 Connec on to the network 13 Start and use 13 Control of the automa c opera on 14 Maintenance 14 Connec on diagram 15 CT Connec on place 15 Power factor controller PFC96evo 16 Power f...

Страница 4: ...fuses on the capacitor banks provided with signal The e ciency of the coolong system checking that the fans are not defec ve or mechanically blocked and cleaning with an air jet the relevamt grilles T...

Страница 5: ...ItalfaradS p A ViaIVNovembren 140061MinerbioBolognaItaly Tel 390516618311 Fax 390516605594 E mail italfarad italfarad com Web www italfarad com 15 E N...

Страница 6: ...tor THD cap THDC Capacitors total harmonic distor on THD in current TC HI Maximum THD value measured Temperature C F Temperature of internal sensor CHI FHI Maximum temperature value measured Voltage T...

Страница 7: ...04 Reading the connec on polarity of the CT AUT Polarity is automa cally detected at power up Can only be used when working with only one CT and when the system has no generator device Dir Automa c de...

Страница 8: ...o high is generated P 42 Undervoltage alarm threshold referred to the rated voltage set with P 07 below which the alarm A05 voltage too low is generated P 43 Maximum installa on voltage THD alarm thre...

Страница 9: ...quest delta kvar higher than 50 of the smallest step and the measured cos is di erent from the setpoint Measures The PFC144evo controller provides a set of measurements displayed on the alphanumeric d...

Страница 10: ...able Below are listed all the programming parameters in tabular form For each parameter are indicated the possible se ng range and factory default as well as a brief explana on of the func on of the p...

Страница 11: ...ld be exceeded P 29 Setpoint used when the system is genera ng ac ve power to the supplier with nega ve ac ve power power factor P 30 Disconnection sensitivity Same as the previous parameter but relat...

Страница 12: ...OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO Date Signature EXTRA ORDINARY MAINTENANCE REGISTR...

Страница 13: ...ItalfaradS p A ViaIVNovembren 140061MinerbioBolognaItaly Tel 390516618311 Fax 390516605594 E mail italfarad italfarad com Web www italfarad com 23...

Страница 14: ...iabile per l ITALFARAD i condensatori utilizzati sono conformi alla EN 60831 1 2 IEC 831 1 2 i quadri hanno superato le prove di tipo previste dalle Norme CEI EN 60439 1 CEI 17 13 1 L ITALFARAD S p A...

Отзывы: