PFC144evo
Parameter se!ng (SETUP) from panel
To access the programming menu (setup) :
·
To enter parameter programming the unit must be in TEST mode (first programming)
·
From the normal measurement display, press and hold for 3 seconds to recall the main
menu.
SET
is displayed on the main display.
·
If you have set the password (P.21 = ON) instead of
SET
the display shows
PAS
(password entry
request). Set the numeric password using and then press to move to
next digit.
·
If the password is correct the unit will show
OK U
or
OK A
depending on the entered password is
user or the advanced level. The password can be defined with parameters P.22 and P.23.
Factory default is
001
and
002
respec!vely.
·
If the entered password is wrong the unit will show
ERR
.
·
A"er having entered the password, the access is enabled un!l the unit is re
-
ini!alized or for 2
minutes without pressing any key.
·
A"er having entered the password, repeat the procedure to access the parameter se#ng.
·
Press to select the desired submenu (
BAS
à
ADV
à
ALA
... ) that is shown on the
alphanumeric display.
Indica!on
of TEST
mode
Total
number
of steps
Firmware
revision
Model
variant
MAN
mode
icon
Connected
steps
Tot kvar
inserited in
MAN
Manual
step
selec!on
enabled
·
The following table lists the available submenus:
Cod
Descrip!on
BAS
Access to Base menu
ADV
Accesso to Advanced menu
ALA
Accesso to Alarm menu
FUN
Access to Ethernet menu
CMD
Access to Command menu
CUS
Access to Custom menu
SAVE
Exits saving modifica!ons.
EXIT
Exits without saving (cancel)
·
Press to access the submenu.
·
When you are in a submenu, the main display shows the code of the selected parameter (eg
P.01
), while the numeric/alphanumeric displays at the bo%om of the screen shows the
parameter value and / or descrip!on.
·
Press to advance in the selec!on of items (such as scroll through parameters
P.01
à
P02
à
P03
… ), or press to go back to the previous parameter.
·
While a parameter is selected, with you can increase/decrease its value.
Backward Decrement/increment Forward
·
Once you reach the last parameter of the menu, by pressing once more will return you
to the submenu selec!on.
·
Using select
SAVE
to save the changes or
EXIT
to cancel.
·
Alterna!vely, from within the programming, holding for three seconds will save the
changes and exit directly.
·
If the user does not press any key for more than 2 minutes, the system leaves the setup automatically
and goes back to normal viewing without saving the changes done on parameters (like
EXIT
).
·
N.B.: a backup copy of the setup data (se#ngs that can be modified using the keyboard) can be
saved in the eeprom memory of the
PFC144evo
regulator. This data can be restored when
necessary in the work memory. The data backup 'copy' and 'restore' commands can be found in
the
Commands menu
.
Parameter table
·
Below are listed all the programming parameters in tabular form. For each parameter are
indicated the possible se#ng range and factory default, as well as a brief explana!on of the
func!on of the parameter. The descrip!on of the parameter shown on the display can in some
cases be different from what is reported in the table because of the reduced number of charac-
ters available. The parameter code can be used however as a reference.
·
Note: the parameters shown in the table with a shaded background are
essen!al
to the opera-
!on of the system, thus they represent the minimum programming required for opera!on.
COD
DESCRIPTION
ACC
UoM
DEF
RANGE
P.01
CT primary
Usr
A
OFF
OFF / 1...10.000
P.02
CT secondary
Usr
A
5
1 / 5
P.03
CT read phase
Usr
L1
L1
-
L2– L3
P.04
CT wiring polarity
Usr
Aut
Aut
-
Dir
-
Inv
P.05
Voltage read phase
Usr
L2
-
L3
L1
-
L2 L2
-
L3 L3
-
L1 L1
-
N L2
-
N L3
-
N
P.06
Smallest step power
Usr
Kvar
1.00
0.10 ... 10000
P.07
Rated installa!on
voltage
Usr
V
400V
50 ... 50000
P.08
Nominal frequency
Usr
Hz
Aut
Aut
-
50Hz
-
60Hz
-
Var
P.09
Reconnec!on !me
Adv
sec
60
1 … 30000
P.10
Sensi!vity
Usr
sec
60
1 … 1000
P.11
Step 1 func!on
Usr
OFF
OFF
-
1…32
-
ON
-
NOA
-
NCA
-
FAN
-
MAN
-
AUT
-
A01…A12
P.12
Step 2 func!on
Usr
OFF
=
P.13
Step 3 func!on
Usr
OFF
=
P.14
Step 4 func!on
Usr
OFF
=
P.15
Step 5 func!on
Usr
OFF
=
P.16
Step 6 func!on
Usr
OFF
=
P.17
Step 7 func!on
Usr
OFF
=
P.19
Cos
-
phi setpoint
Usr
0.95
IND
0.50 Ind – 0.50 Cap
P.20
Alarm messages
language
Usr
ENG
ENG
-
ITA
-
FRA
-
SPA
-
POR
-
DEU
Base menu
P.01
-
The value of the primary current transformer. Example: with CT 800/5 set 800. If set to OFF, after the
power
-
up the device will prompt you to set the CT and allow direct access to this parameter.
P.02
-
Value of the secondary of the current transformers. Example: with CT 800/5 set 5.
P.03
–
It defines on which phase the device reads the current signal. The wiring of current inputs must
match the value set for this parameter. Supports all possible combinations of parameter P.05.
P.04
-
Reading the connec!on polarity of the CT.
AUT
= Polarity is automa!cally detected at power up. Can only be used when working with
only one CT and when the system has no generator device.
Dir
= Automa!c detec!on disabled. Direct connec!on.
Inv
= Automa!c detec!on disabled. Reverse wiring.
P.05
-
Defines on which and on how many phases the device reads the voltage signal. The wiring of
voltage inputs must match the se#ng for this parameter. Supports all possible combina-
!ons of parameter P.03.
P.06
-
Value in kvar of the smallest step installed (equivalent to the step weight 1). Rated power of the
capacitor bank provided at the rated voltage specified in P.07 (exemple: step 10kvar
-
460V
supplied 400V → 10 x (400)
2
/(460)
2
→ set 7,5kvar).
P.07
-
Installa!on rated voltage, which is delivered in specified power P.06.
P.08
-
Working frequency of the system:
Aut
= automa!c selec!on between 50 and 60 Hz at power on.
50Hz
= fixed to 50 Hz.
60Hz
= fixed to 60 Hz.
Var
= variable, measured con!nuously and adjusted.
P.09
-
Minimum !me that must elapse between the disconnec!on of one step and the subsequent
reconnec!on both in
MAN
or
AUT
mode. During this !me the number of the step on the
main page is blinking.
E
N