20

 

Power Factor Controller 

PFC144evo

 

Parameter se!ng (SETUP) from panel

 

To access the programming menu (setup) :

 

· 

To enter parameter programming the unit must be in TEST mode (first programming)

 

· 

From the normal measurement display, press and hold              for 3 seconds to recall the main 

menu. 

SET

  is displayed on the main display.

 

· 

 If you have set the password (P.21 = ON) instead of 

SET

 the display shows 

PAS

 (password entry 

request). Set the numeric password using                              and then press                to move to 

next digit.

 

· 

If the password is correct the unit will show 

OK U

 or 

OK A

 depending on the entered password is 

user  or  the  advanced  level.  The  password  can  be  defined  with  parameters  P.22  and  P.23. 
Factory default is 

001

 and 

002

 respec!vely.

 

· 

If the entered password is wrong the unit will show  

ERR

.

 

· 

A"er having entered the password, the access is enabled un!l the unit is re

-

ini!alized or for 2 

minutes without pressing any key.

 

· 

A"er having entered the password, repeat the procedure to access the parameter se#ng.

 

· 

Press                               to select the desired submenu (

BAS

à 

ADV

à  

ALA 

... ) that is shown on the 

alphanumeric display.

 

Indica!on 

of TEST 

mode

 

Total 

 

number 

 

of steps

 

Firmware 

revision

 

Model 

variant

 

 

MAN 

mode 

 

icon

 

Connected 

 

steps

 

Tot kvar 

inserited in 

MAN

 

Manual 

step 

selec!on 

enabled

 

· 

The following table lists the available submenus:

 

Cod

 

Descrip!on

 

BAS

 

Access to Base menu

 

ADV

 

Accesso to Advanced menu

 

ALA

 

Accesso to Alarm menu

 

FUN

 

Access to Ethernet menu

 

CMD

 

Access to Command menu

 

CUS

 

Access to Custom menu

 

SAVE

 

Exits saving modifica!ons.

 

EXIT

 

Exits without saving (cancel)

 

· 

Press                to access the submenu.

 

· 

When  you  are  in  a  submenu,  the  main  display  shows  the  code  of  the  selected  parameter  (eg 

P.01

  ),  while  the  numeric/alphanumeric  displays  at  the  bo%om  of  the  screen  shows  the 

parameter value and / or descrip!on.

 

· 

Press               to advance in the selec!on of items (such as scroll through parameters 

P.01

 à 

P02

 

à 

P03

… ), or press                to go back to the previous parameter.

 

· 

While a parameter is selected, with                               you can increase/decrease its value.

 

Backward                     Decrement/increment                        Forward

 

· 

Once you reach the last parameter of the menu, by pressing                 once more will return you 
to the submenu selec!on.

 

· 

Using                                select 

SAVE

 to save the changes or 

EXIT

 to cancel.

 

· 

Alterna!vely,  from  within  the  programming,  holding                      for  three  seconds  will  save  the 
changes and exit directly.

 

· 

If the user does not press any key for more than 2 minutes, the system leaves the setup automatically 
and goes back to normal viewing without saving the changes done on parameters (like 

EXIT

).

 

· 

N.B.: a backup copy of the setup data (se#ngs that can be modified using the keyboard) can be 
saved  in  the  eeprom  memory  of  the 

PFC144evo

  regulator.  This  data  can  be  restored  when 

necessary in the work memory. The data backup 'copy' and 'restore' commands can be found in 
the 

Commands menu

.

 

Parameter table

 

· 

Below  are  listed  all  the  programming  parameters  in  tabular  form.  For  each  parameter  are 
indicated  the  possible  se#ng  range  and  factory  default,  as  well  as  a  brief  explana!on  of  the 
func!on of the parameter. The descrip!on of the parameter shown on the display can in some 
cases be different from what is reported in the table because of the reduced number of charac-
ters available. The parameter code can be used however as a reference.

 

· 

Note: the parameters shown in the table with a shaded background are 

essen!al

 to the opera-

!on of the system, thus they represent the minimum programming required for opera!on.

 

COD

 

DESCRIPTION

 

ACC

 

UoM

 

DEF

 

RANGE

 

P.01

 

CT primary

 

Usr

 

A

 

OFF

 

OFF / 1...10.000

 

P.02

 

CT secondary

 

Usr

 

A

 

5

 

1 / 5

 

P.03

 

CT read phase

 

Usr

 

  

L1

 

L1 

-

 L2– L3

 

P.04

 

CT wiring polarity

 

Usr

 

  

Aut

 

Aut 

-

 Dir 

-

 Inv

 

P.05

 

Voltage read phase

 

Usr

 

  

L2

-

L3

 

L1

-

L2  L2

-

L3  L3

-

L1  L1

-

N  L2

-

N  L3

-

N

 

P.06

 

Smallest step power

 

Usr

 

Kvar

 

1.00

 

0.10 ... 10000

 

P.07

 

Rated installa!on 
voltage

 

Usr

 

V

 

400V

 

50 ...  50000

 

P.08

 

Nominal frequency

 

Usr

 

Hz

 

Aut

 

Aut 

-

 50Hz 

-

 60Hz 

-

 Var

 

P.09

 

Reconnec!on !me

 

Adv

 

sec

 

60

 

1 … 30000

 

P.10

 

Sensi!vity

 

Usr

 

sec

 

60

 

1 … 1000

 

P.11

 

Step 1 func!on

 

Usr

 

  

OFF

 

OFF 

-

 1…32 

-

 ON 

-

 NOA 

-

 NCA 

-

 FAN 

-

 MAN 

-

 

AUT 

-

 A01…A12

 

P.12

 

Step 2 func!on

 

Usr

 

  

OFF

 

=

 

P.13

 

Step 3 func!on

 

Usr

 

  

OFF

 

=

 

P.14

 

Step 4 func!on

 

Usr

 

  

OFF

 

=

 

P.15

 

Step 5 func!on

 

Usr

 

  

OFF

 

=

 

P.16

 

Step 6 func!on

 

Usr

 

  

OFF

 

=

 

P.17

 

Step 7 func!on

 

Usr

 

  

OFF

 

=

 

P.19

 

Cos

-

phi setpoint

 

Usr

 

  

0.95 

IND

 

0.50 Ind – 0.50 Cap

 

P.20

 

 Alarm messages 
language

 

Usr

 

  

ENG

 

ENG 

-

 ITA 

-

 FRA 

-

 SPA 

-

 POR 

-

 DEU

 

Base menu

 

P.01

 

-

 The value of the primary current transformer. Example: with CT 800/5 set 800. If set to OFF, after the 

power

-

up the device will prompt you to set the CT and allow direct access to this parameter.

 

P.02

 

-

 Value of the secondary of the current transformers. Example: with CT 800/5 set 5.

 

P.03

  – 

It  defines  on  which  phase  the  device  reads  the  current  signal.  The  wiring  of  current  inputs  must 

match the value set for this parameter. Supports  all possible combinations of parameter P.05.

 

P.04

 

-

 

Reading the connec!on polarity of the CT.

 

AUT

 = Polarity is automa!cally detected at power up. Can only be used when working with 

only one CT and when the system has no generator device.

 

Dir

 = Automa!c detec!on disabled. Direct connec!on.

 

Inv

 = Automa!c detec!on disabled. Reverse wiring.

 

P.05

 

-

 

Defines on which and on how many phases the device reads the voltage signal. The wiring of 

voltage  inputs  must  match  the  se#ng  for  this  parameter.  Supports    all  possible  combina-

!ons of parameter P.03.

 

P.06

 

-

 Value in kvar of the smallest step installed (equivalent to the step weight 1). Rated power of the 

capacitor bank provided at  the rated voltage specified  in P.07  (exemple: step 10kvar

-

460V 

supplied 400V → 10 x (400)

2

/(460)

2

 →  set 7,5kvar).

 

P.07

 

-

  

Installa!on rated voltage, which is delivered in specified power P.06.

 

P.08

  

-

 Working frequency of the system:

 

Aut

 = automa!c selec!on between 50 and 60 Hz at power on.

 

50Hz

 = fixed to 50 Hz.

 

60Hz

 = fixed to 60 Hz.

 

Var

 = variable, measured con!nuously and adjusted.

 

P.09

 

-

  Minimum !me that must elapse between the disconnec!on of  one step and the subsequent 

reconnec!on  both  in   

MAN 

or 

AUT

  mode.  During  this  !me  the  number  of  the  step  on  the 

main page is blinking.

 

 

E

N

 

Содержание PFC144evo

Страница 1: ...8311 Fax 390516605594 E mail italfarad italfarad com Web www italfarad com APPARECCHIATURE AUTOMATICHE DI RIFASAMENTO MANUALE OPERATIVO D INSTALLAZIONE USO E MANUTENZIONE AUTOMATIC POWER FACTOR CORREC...

Страница 2: ...ItalfaradS p A ViaIVNovembren 140061MinerbioBolognaItaly Tel 390516618311 Fax 390516605594 E mail italfarad italfarad com Web www italfarad com 2...

Страница 3: ...eneral remarks 13 Connec on to the network 13 Start and use 13 Control of the automa c opera on 14 Maintenance 14 Connec on diagram 15 CT Connec on place 15 Power factor controller PFC96evo 16 Power f...

Страница 4: ...fuses on the capacitor banks provided with signal The e ciency of the coolong system checking that the fans are not defec ve or mechanically blocked and cleaning with an air jet the relevamt grilles T...

Страница 5: ...ItalfaradS p A ViaIVNovembren 140061MinerbioBolognaItaly Tel 390516618311 Fax 390516605594 E mail italfarad italfarad com Web www italfarad com 15 E N...

Страница 6: ...tor THD cap THDC Capacitors total harmonic distor on THD in current TC HI Maximum THD value measured Temperature C F Temperature of internal sensor CHI FHI Maximum temperature value measured Voltage T...

Страница 7: ...04 Reading the connec on polarity of the CT AUT Polarity is automa cally detected at power up Can only be used when working with only one CT and when the system has no generator device Dir Automa c de...

Страница 8: ...o high is generated P 42 Undervoltage alarm threshold referred to the rated voltage set with P 07 below which the alarm A05 voltage too low is generated P 43 Maximum installa on voltage THD alarm thre...

Страница 9: ...quest delta kvar higher than 50 of the smallest step and the measured cos is di erent from the setpoint Measures The PFC144evo controller provides a set of measurements displayed on the alphanumeric d...

Страница 10: ...able Below are listed all the programming parameters in tabular form For each parameter are indicated the possible se ng range and factory default as well as a brief explana on of the func on of the p...

Страница 11: ...ld be exceeded P 29 Setpoint used when the system is genera ng ac ve power to the supplier with nega ve ac ve power power factor P 30 Disconnection sensitivity Same as the previous parameter but relat...

Страница 12: ...OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO OK KO Date Signature EXTRA ORDINARY MAINTENANCE REGISTR...

Страница 13: ...ItalfaradS p A ViaIVNovembren 140061MinerbioBolognaItaly Tel 390516618311 Fax 390516605594 E mail italfarad italfarad com Web www italfarad com 23...

Страница 14: ...iabile per l ITALFARAD i condensatori utilizzati sono conformi alla EN 60831 1 2 IEC 831 1 2 i quadri hanno superato le prove di tipo previste dalle Norme CEI EN 60439 1 CEI 17 13 1 L ITALFARAD S p A...

Отзывы: