CAPTURE OR STORE SNAPSHOTS - Continued

View stored snapshots:  Select the capture snapshots option in the main menu and press 

the ENTER button. Highlight “View Snapshots” and press the ENTER button to display stored 

snapshots. Use the UP / DOWN ARROW buttons to scroll through the stored snapshots. To 

stop reviewing snapshots, press CANCEL.

Delete snapshots: Select the “Capture Snapshots” option in the main menu and press the ENTER 

button. Highlight “Delete all Snapshots” and press the ENTER button. Confirm that all snapshots 

should be deleted and press the ENTER button again.

MFM300 SPECIFICATIONS

Ambient Temperature Operating Conditions

32° to 122°F (0° to 50°C)

Ambient Humidity Operating Conditions

10% to 90% RH Non-Condensing

Power Source

4 “Double A” (AA) Alkaline Batteries

Battery Life

100 hours Minimum

Temperature Probes

Temperature Measurement Range

-58° to 302°F (-50° to 150°C)

Temperature Accuracy

±0.3F° (±0.2C°) or ±0.5% of Reading (whichever is greater)

Temperature Display Resolution

0.1 Degree

Relative Humidity (RH) Probe

Relative Humidity Measurement Range

0% to 99% RH

Relative Humidity Accuracy

±2% RH 20 to 80% RH, 3% < 20% and > 80%

Relative Humidity Display Resolution

1% RH

Dry-Bulb Temperature Measurement Range

-40° to 185°F (-40° to 85°C)

Dry-Bulb Accuracy

±0.3% Reading

Dry-Bulb Display Resolution

0.1 Degree

Pressure Transducers

0 - 500 PSI Accuracy

±1% Full-Scale

0 - 1000 PSI Accuracy

±1% Full-Scale

Anemometer

Temperature Range

32° to 150°F (0° to 65°C) 
90% RH non-condensing

Temperature Accuracy

±2F° (±1C°)

Velocity Range

100 - 6,000 FPM (0.5 - 30.48 MPS) 

Velocity Display Resolution

1 FPM (.01 MPS)

Velocity Accuracy

3% RDG + .5% Full Scale at 77°F (25°C)
Up to 256 point averaging for airflow

Data Logger

Data Logger Temperature Range

-40° to 185°F (-40° to 85°C)

Temperature Accuracy

±2F° (±1C°)

Record Capacity

2048

Sampling Intervals

1 minute to 255 minutes

Содержание Cooper MFM300

Страница 1: ...MFM300 Multi Function Instrument User Guide and Instrument Warranty...

Страница 2: ...te Superheat Sub Cooling 5 Measure Dynamic System Superheat Sub Cooling 5 6 Measure Relative Humidity and Dry Bulb Temperature 6 Display Psychometrics 6 Measure Air Flow 6 Air Balancing 6 Navigate the...

Страница 3: ...JACK U1 UNIVERSAL JACK U2 POWER TEMPERATURE JACK T2 TEMPERATURE JACK T1 DOWN ARROW PSYCHROMETRICS PSYCH TEMPERATURE JACK T3 SHIFT SUPERHEAT SUB COOLING SH UP ARROW ENTER REFRIGERANT REF MENU AVERAGE...

Страница 4: ...ssage will appear on the display DISPLAY MIN MAX AND AVG VALUES When in Normal Mode press MIN button to display the lowest readings sensed by each probe MAX button to display the highest readings sens...

Страница 5: ...memory There is room in the memory for up to five more refrigerants New refrigerant P T data can be downloaded from the Cooper Atkins website www cooper atkins com mfm asp using the MFM300 Toolbox an...

Страница 6: ...layed you must enter the shape and size of the duct opening where airflow is being measured To do this press the MENU button while viewing CFM Use the on screen directions to enter the duct shape and...

Страница 7: ...Place a temperature probe connected to T1 into an environment with a known temperature and adjust the reading to calibrate and match Zero out probe P1 Zero out probe P2 When a pressure transducer is...

Страница 8: ...ace it where temperatures are to be measured Download data Select this menu option to store the Data Logger contents in the MFM300 and view at a later time View data Select this menu option to view th...

Страница 9: ...rature Probes Temperature Measurement Range 58 to 302 F 50 to 150 C Temperature Accuracy 0 3F 0 2C or 0 5 of Reading whichever is greater Temperature Display Resolution 0 1 Degree Relative Humidity RH...

Страница 10: ...es notice that any statements or representations made by it will not create a warranty that this product is fit for any particular purpose Such statements representations or descriptions are informati...

Отзывы: