AW16000 - Instruction Manual
3.5 Error Codes
Error codes will be displayed on the three-digit display when certain faults occur. Most of these indicators are
associated with the daisy chain communication, but certain error codes pertain to single board operation also.
These codes are :
Display
Meaning
Action required
Err 1
This is a “watchdog” reset that is enabled
when the master controller isn’t able to cycle
through its operation.
Make sure all electrical connections are
appropriately shielded so the master controller is
not disrupted by noise.
Err 2
The pressure module has failed to respond to
the request of the master controller.
The master controller will try to recover from
the fault. If unsuccessful, replace the pressure
module.
Err 3
Communication error in the daisy chain
interface. This will only appear when the
master controller is used in conjunction with
a slave board.
Make sure the control cable used in the daisy
chain interface is properly shielded from noise.
Err 4
The master controller has detected a change
in module configuration or a fault in one of
the modules.
Reinstall all modules in accordance with the
instructions in the factory IOM.
Err 5
If the fault described in “Err 4” is not
corrected, the master controller will
reconfigure the modules that are responding
properly and operate at a degraded
condition.
Reinstall all modules.
Contact factory if the problem persists.
Err 6
a message error affecting the software of the
master controller or one of its
modules.
Check the integrity of all connecting cables used
to drive slave boards for additional solenoids.
also check the electrical grounding of the system
installation.
Err 7
Indicates that one of the triac drivers are not
functioning..
Return to factory for evaluation and repair.
Err 8
Internal Error.
Contact the factory.
Err 9
Unassigned message code.
Contact the factory.