18/63
G.83.0074 - Release 8.1.0 CH 2014
ista International GmbH - Grugaplatz 2 - 45131 Essen
http://www.ista.com
Parameterizing loop
The following list describes how you can switch between
the loops:
▪
User loop
↔
Service loop
▪
→
: Press button for 10 sec.
▪
←
: Press button for 3 sec. (except from field code input
and day saved in month)
▪
Service loop -> Parameterising loop
▪
→
: Press button for 3 sec. in Code Input field, then en-
ter the meter date
▪
←
: Short press on button in field to return to normal op-
eration
Installation
1.
Flush pipeline according to DIN/EN. Observe the
country specific regulations!
2.
Note the direction of flow and compare with the arrow
on the meter.
3.
Close the shut-off devices in front and behind the in-
stallation site.
4.
Dismount adapter, if neccessary.
5.
Clean sealing surfaces.
6.
Only insert a new profile sealing.
7.
Insert new seal.
8.
Note the direction of flow and compare with the arrow
on the meter.
9.
Mount meter.
10. Tighten all screw connections(in case of flange con-
nection tighten nuts crosswise).
11. Install temperature sensors, depending on version,
into tees, ball valves or immersion sleeves.
a) Wall mounted ALU (optional)
1.
Pull the calculator off the attachment.
2.
Unscrew the attachment with a screw driver.
3.
Prior to drilling, check that there are no electricity ca-
bles, gas or water pipes below the surface at the instal-
lation site.
4.
Drill hole into the wall (6 mm).
5.
Insert dowels.
6.
Attach the mounting plate to the wall.
7.
Attach the calculator to the installation base from
above.
PulSE CH
Remote readout mode
(optional)
Info
123 A
Primary address for
MBus option
Info
2345678 K
Owner number, 7 digit
Info
18.02.08 F0
Time stamp for F0
Advance warning
Info
3- 01 FW
Firmware version
Info
31.12.07 V
Reference date, previ-
ous year
Previous
year
0034321 kWh
Energy previous year
on reference date
Previous
year
00923.12 m³
Volume previous year
on reference date
Previous
year
12 Fh
Downtime hours previ-
ous year
Previous
year
- -.- -.- - C
Code input for parame-
terisation
01.06.08 M
Day saved in month 1-
15
Previous
month
Key pressed more than
3s:
0034321 kWh
Energy previous month
on reference date
Previous
month
00923.12 m³
Volume previous month
on reference date
Previous
month
12 Fh
Downtime hours previ-
ous month on reference
date
Previous
month
Display
Meaning
01.01. - - S
Annual reference date (dd,mm)
24.07.08 D
Date (DD.MM.YYYY)
15.33.06 T
Time (hh.mm.ss)
2345678 K
Owner No. or MBus secondary
address)*
123 A
MBus primary address
Ft +
Downtime reset
Nb - - - - -
Return to normal operation
Display
Meaning
▼