Isolite ELCD 1008 Скачать руководство пользователя страница 7

Installation  Guide
ELCD 1008

Isolite Corp  31 Waterloo Ave, Berwyn PA

7

Note:

The system supports connection of up to 10 ELCD 1008 units connected in
parallel to the fire alarm device.

The ELCD 1008 features a single pole auxiliary relay that provides switching for installations utilizing 0–10V or
Digital Addressable Lighting Interface (DALI) controls. In the event of an emergency, the relay opens the control
circuit, sending any connected loads to their full intensity output.

0-10V Auxiliary Output

Note:

All low–voltage Class 2 wiring must be separated from all Class 1 wiring. Follow local codes
and installation restrictions.

Isolite

 recommends limiting the distance run for the 0–10V control wiring from the 

controller to the last ballast (driver) to 300ft, based on 18 AWG wire.

1. Run a +10V wire, typically purple, between the 0–10V controller and the 0–10V terminal 10 in the ELCD 1008

and secure the terminal onto the wire.

2. Run a +10V wire, typically purple, between 0–10V ballast and the 0–10V terminal 9 in the ELCD 1008 and

secure the terminal onto the wire.

3. Run a common wire, typically gray, between the 0–10V controller and the 0–10V ballast.

Fire Alarm Input

The ELCD 1008 features a single dry–contact input that can 
be  used  to  force  the  transfer  from  normal  to  emergency 
state,  even  if  both  normal  and  emergency  power  are 
present. The contact may be configured for either normally 
closed  (NC)  or  normally  open  (NO)  operation  by  setting 
switch 1 and 2 on the ELCD1008 control board.

1. Run a positive control wire between the fire alarm device

and the FIRE ALARM 11 “+” terminal in the ELCD 1008
and secure the terminal onto the wire.

2. Run a negative (common) control wire between the fire

alarm device and the FIRE ALARM terminal 12 “-”and
secure the terminal onto the wire.

3. Set the fire alarm contact input configuration switches for

either normally open or normally closed operation.

+ (purple wire)

+ (purple wire)

- (grey wire)

0-10V controller

0-10V ballast

9

10

0

-1

0

V

ELCD 1008

ELCD 1008

Connect up to

10 units

Fire Alarm

11

12

F

IR

E

A

L

A

R

M

+

-

11

12

F

IR

E

A

L

A

R

M

+

-

O

N

F

IR

E

A

L

A

R

M

S

1

-1

S

1

-2

1

2

Содержание ELCD 1008

Страница 1: ...Systems Article 702 Optional Standby Systems Section 518 3 C Assembly Occupancies Section 520 7 Theatres and Similar Locations Section 540 11 C Motion Picture Projection Rooms REMOTE TEST NORMAL POWER...

Страница 2: ...ms in accordance with Article 300 of the National Electrical Code NFPA70 NEMA Type1 Enclosure suitable for installation location that conforms to the following ambient environment 0 40 C 5 95 non cond...

Страница 3: ...l power is restored Note The re alarm input functions with up to 1 000ft 300m of 18AWG wire connected between the input and the switch Fire Alarm Inputs of up to 10 ELCD 1008 units can be wired togeth...

Страница 4: ...can accommodate installations that utilize 0 10V Auxiliary Output control and for use with either normally open or normally closed operation WARNING Before you begin pulling and terminating wire to t...

Страница 5: ...wire and the jumper fork terminal c Terminate the hot wire to the NORMAL 5H hot terminal and secure the terminal screw onto the wire and the jumper fork terminal 5 Terminate emergency power wires a R...

Страница 6: ...ch terminal screw onto the wire 3 Install a jumper wire between SENSE 4N neutral and Normal 6N neutral 4 Terminate normal power wires a Run a neutral and a hot wire through conduit from the normal pow...

Страница 7: ...V wire typically purple between 0 10V ballast and the 0 10V terminal 9 in the ELCD 1008 and secure the terminal onto the wire 3 Run a common wire typically gray between the 0 10V controller and the 0...

Страница 8: ...wer to the unit 7 Test the operation of the ELCD 1008 as described in Operation and Test below Operation and Test It is important to test the ELCD 1008 regularly because it is a life safety device NFP...

Страница 9: ...l you release the PUSH TO TEST button If emergency power is not present for the test the ELCD1008 will remain in normal mode Test Button Fuse Replacement Directing a laser pointing device at the REMOT...

Страница 10: ...is locked out and tagged out before removing the cover from this enclosure 1 Disconnect both power supply sources and lock tagout appropriately 2 Loosen the four screws and remove the cover 3 Locate t...

Отзывы: