Troubleshooting

When both of the ELCD 1008 LEDs are blinking, the relays need to be manually reset to a known state.

WARNING:RISK OF ELECTRIC SHOCK! More than one live circuit is present inside the 
enclosure. Make certain the main circuit breaker cabinet or other readily accessible input 
power disconnect device for both normal and emergency power input is locked out and 
tagged out before removing the cover from this enclosure.

1. Disconnect both power supply sources and lock/tagout appropriately.
2. Loosen the four screws and remove the cover.

3. Locate the four relay switches near the

status LEDs.

4. Using a flat blade screwdriver, carefully

slide the relay switch to the left.

5. Repeat for all four relays in the ELCD 1008

enclosure.

6. Replace the cover to the enclosure.
7. Re-apply power from both sources and

retest the unit.

See Operation and Test on page 8

 for 

instructions on testing the unit.

Isolite Corp  31 Waterloo Ave, Berwyn PA

10

Содержание ELCD 1008

Страница 1: ...Systems Article 702 Optional Standby Systems Section 518 3 C Assembly Occupancies Section 520 7 Theatres and Similar Locations Section 540 11 C Motion Picture Projection Rooms REMOTE TEST NORMAL POWER...

Страница 2: ...ms in accordance with Article 300 of the National Electrical Code NFPA70 NEMA Type1 Enclosure suitable for installation location that conforms to the following ambient environment 0 40 C 5 95 non cond...

Страница 3: ...l power is restored Note The re alarm input functions with up to 1 000ft 300m of 18AWG wire connected between the input and the switch Fire Alarm Inputs of up to 10 ELCD 1008 units can be wired togeth...

Страница 4: ...can accommodate installations that utilize 0 10V Auxiliary Output control and for use with either normally open or normally closed operation WARNING Before you begin pulling and terminating wire to t...

Страница 5: ...wire and the jumper fork terminal c Terminate the hot wire to the NORMAL 5H hot terminal and secure the terminal screw onto the wire and the jumper fork terminal 5 Terminate emergency power wires a R...

Страница 6: ...ch terminal screw onto the wire 3 Install a jumper wire between SENSE 4N neutral and Normal 6N neutral 4 Terminate normal power wires a Run a neutral and a hot wire through conduit from the normal pow...

Страница 7: ...V wire typically purple between 0 10V ballast and the 0 10V terminal 9 in the ELCD 1008 and secure the terminal onto the wire 3 Run a common wire typically gray between the 0 10V controller and the 0...

Страница 8: ...wer to the unit 7 Test the operation of the ELCD 1008 as described in Operation and Test below Operation and Test It is important to test the ELCD 1008 regularly because it is a life safety device NFP...

Страница 9: ...l you release the PUSH TO TEST button If emergency power is not present for the test the ELCD1008 will remain in normal mode Test Button Fuse Replacement Directing a laser pointing device at the REMOT...

Страница 10: ...is locked out and tagged out before removing the cover from this enclosure 1 Disconnect both power supply sources and lock tagout appropriately 2 Loosen the four screws and remove the cover 3 Locate t...

Отзывы: