4.2 Installing the Output Wires
Connect the load wires to the Normally-On output leads labeled N-ON, or the
multipurpose Normally-Off/Switched outputs OUT 1, OUT 2 or OUT 3. Ensure that the
wire connections to the terminal block are secured by briefly tugging the wires. See
section 9.4 thru 9.4.2 for further load type details.
1
Ensure that the System ON/OFF switch is in the OFF position before starting.
2
Connect 120 VAC or 277 VAC to the AC INPUT terminals LINE and NEU. System
ground should be connected directly to the cabinet
’s green
grounding screw.
3
Ensure that the connected AC INPUT line voltage matches the VOLTAGE
SELECT JUMPER. Remove and re-inserting the plug to the correct position if
necessary.
4
Connect the load wires to the AC OUTPUT terminals. Load types can be either
Normally-On (N-ON) which are always energized 24/7, or multipurpose
Normally-Off/Switched. OUT 1, OUT 2 and OUT 3 are controlled by CMD 1,
CMD 2, and CMD 3 respectively when used as Switched load types. If no
connections are made to the CMD 1-3, the OUT 1-3 will act as a Normally-Off
load type and will only energize during the Inverter mode of operation (Loss of
utility power or system test). See section 9.4 thru 9.4.2 for additional details
on load types.
4.3 AC Input(s) / Output(s) Diagram
AC INPUT(S)
AC OUTPUT(S)
VOLTAGE SELECT JUMPER
E3MINI SERIES |