2.0 RECEIVING AND STORAGE
2.1 Inspection
The E3MINI Series central inverter and batteries are shipped together. Upon
arrival, please inspect the contents to ensure that no shipping damage has
occurred. This is especially important with the batteries
–
ensure that there are no
cracks or leaks. If any damage has occurred, notify the shipping carrier immediately
and submit a damage claim.
WARNING
- Do not use system with a damaged battery as this may cause an unsafe
condition.
2.2 Storage
Storage before the installation is critical for the battery life expectancy and
warranty. Store the system indoors in a clean, dry and cool location. Storage at
higher temperatures will result in accelerated rates of self-discharge and possible
deterioration of battery performance and life.
Storage at high temperatures will result in accelerated rates of self-discharge and
possible deterioration of battery performance and life. Storage times exceeding the
above may result in plate sulfation, which may adversely affect electrical
performance and expected life.
Failure to install and charge the batteries as noted
VOIDS the battery’s warranty
DANGER
-
Batteries present a risk of electrical shock and high short circuit current.
Do not smoke, cause a flame or spark in the immediate are of the batteries. Use
proper lifting means when moving batteries and wear all appropriate safety
clothing and equipment.
4
| INSTALLATION / OPERATION MANUAL
WARNING
–
The maximum storage time from shipment to initial
charge is 6 months
for batteries stored at ambient temperatures no
warmer than 77°F (25°C). For storage temperatures greater than 77°F
(25°C) the batteries must be recharged one (1) month sooner for every
5°F (3°C) increase above 77°F (25°C).