8.5   Start-Up Faults 

     During power on and initialization, the system goes through a series of checks to 
prevent hardware failures which can occur from common wiring or installation errors. If 
Faults are discovered during the start-up sequence, 

LED1 (Charger) and LED2 (Inverter) 

will both illuminate red

 and will blink a specific quantity which correlates to the fault 

type. Listed below are the fault types and the blink quantities associated with each of 
the fault types. To clear the fault, press the system test button after problem was 
diagnosed/repaired which initiates a new system start-up. 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

8.6   Charger Faults: 

     While the batteries are being charged, the system will continuously check for faults 
as part of its diagnostic capabilities. 

LED1 (Charger LED) will illuminate red

 and will blink 

a specific quantity which correlates to the fault type. Listed below are the fault types 
and the blink quantities associated with each of the fault types. To clear the fault, press 
the system test button after problem was diagnosed/repaired which initiates a new 
system start-up. 
 
 
 
 
 
 
 
 

E3MINI SERIES   |   

15

 

INCORRECT AC (LED1/LED2 

 1 Blink) 

Indicates that the incoming AC voltage does not match the VOLTAGE SELECT JUMPER position. 
Simply remove the jumper and connect to the correct location. 

 

VOLTAGE SELECT JUMPER (LED1/LED2 

 2 Blinks) 

Indicates that the VOLTAGE SELECT JUMPER is not inserted. Insert jumper to the correct location so 
that the Incoming AC voltage matches the VOLTAGE SELECT JUMPER location. 

 

TRANSFORMER WIRING (LED1/LED2 

 3 Blinks) 

Indicates that the blue and yellow wires for the main transformer are reversed. 

 

LOW BATTERY (LED1/LED2 

 4 Blinks) 

Indicates that the battery voltage is incorrect or too low to start the system. Check the connectors 
and wiring of the batteries and measure the DC voltages to ensure they are above 12V. 

 

OVERLOAD (LED1/LED2 

 5 Blinks) 

Indicates that there is too much load connected or there is a short circuit. Check the connected 

load wiring and/or reduce the connected load to the power of the inverter’s rating.

 

 

INVERTER (LED1/LED2 

 6 Blinks) 

Indicates that there is fault with the Inverter module. 

 

BACKFEED (LED1/LED2 

 7 Blinks) 

Indicates that there is an AC voltage back-feeding the output terminals. This fault means that the 
E3MINI Series was wired incorrectly between the output terminal and the load(s). 

 

VOLTAGE SELECT JUMPER (LED1 

 2 Blinks) 

Indicates that the VOLTAGE SELECT JUMPER is not inserted. Insert jumper to the correct location so 
that the Incoming AC voltage matches the VOLTAGE SELECT JUMPER. 

 

OVER TEMPERATURE (LED1 

 1 Blink)   

Indicates that the MOS

FET’s Heatsink temperature has exceeded its limits. This fault will clear itself 

after it cools down so no reset is required. 

 

Содержание E3MINI Series

Страница 1: ...ded by the manufacturer may cause an unsafe condition F Do not use this equipment for other than intended use This unit contains lethal voltages There are no user serviceable parts inside Only authori...

Страница 2: ...dure 6 2 Shutdown Procedure 7 0 Specifications 8 0 User Interface 8 1 LED1 Charging Mode and Line Status 8 2 LED2 Inverter Mode and Battery Level Indication 8 3 Minor Alarm 8 4 Major Alarms 8 5 Startu...

Страница 3: ...g is not required 1 2 Electrical Design Features Through the use of Pulse Width Modulation PWM and the latest MOSFET technology E3MINI Series can produce a pure sine wave output which is compatible wi...

Страница 4: ...formance and life Storage at high temperatures will result in accelerated rates of self discharge and possible deterioration of battery performance and life Storage times exceeding the above may resul...

Страница 5: ...ife Every means should be made to keep the batteries in an environment that keeps the batteries around 25 C for rated battery life 3 3 Ventilation Choose a mounting location that is clean and dust fre...

Страница 6: ...ting a good connection to earth ground Use an Ohm Meter to check that continuity between conduit and protective earth ground has been established WARNING Drilling into cabinet may void warranty if met...

Страница 7: ...Knockout Locations E3MINI Series 250W Knockout Locations E3MINI Series 125W E3MINI SERIES 7...

Страница 8: ...and VOLTAGE SELECT JUMPER match and breaker size is correct 1 Connect the Utilities Feed Line voltage to the Terminal Block LINE and NEU Neutral Ensure that the wire connections to the terminal block...

Страница 9: ...hat the connected AC INPUT line voltage matches the VOLTAGE SELECT JUMPER Remove and re inserting the plug to the correct position if necessary 4 Connect the load wires to the AC OUTPUT terminals Load...

Страница 10: ...lation The E3MINI Series batteries may come pre installed and pre terminated to the main DC Battery Connector If battery connections must be made follow detail in section 5 4 for the appropriate model...

Страница 11: ...5 4 Battery Wiring Diagrams E3MINI SERIES 11 125W Inverter Single string of 24VDC Connect Jumper and wires as shown below 250W Inverter Two strings of 24VDC Connect Jumpers and wires as shown below...

Страница 12: ...ose Normally Off Switched outputs are all operational and ensure there are no overloads by measuring the currents If alarms occur during start up see section 8 5 thru 8 7 for possible explanations Als...

Страница 13: ...Power Factor 0 5 lead to 0 5 lag Output Types 1x Normally On 3x Multipurpose Normally Off Switched Battery Type Premium Long Life Valve Regulated Lead Acid VRLA Charger 3 rate with Temperature Compen...

Страница 14: ...D1 is red it is an alarm fault condition 8 2 LED2 Inverter Mode and Battery Level Indication When the LED2 is illuminated yellow the system is running on Inverter Mode If the LED2 is solid Yellow the...

Страница 15: ...the correct location VOLTAGE SELECT JUMPER LED1 LED2 2 Blinks Indicates that the VOLTAGE SELECT JUMPER is not inserted Insert jumper to the correct location so that the Incoming AC voltage matches the...

Страница 16: ...t with the Charger Inverter module VOLTAGE SELECT JUMPER LED2 2 Blinks Indicates that the VOLTAGE SELECT JUMPER is not inserted Insert jumper to the correct location so that the Incoming AC voltage ma...

Страница 17: ...s loads are being powered and the internal battery charger is maintaining a float charge The charger is regulating or floating the batteries at 2 27 Volts per Cell VPC and is temperature compensated t...

Страница 18: ...is is very beneficial with Switched or Normally Off loads The Normally On and multipurpose Normally Off Switched outputs all produce voltage during Inverter Power mode 9 4 AC Output s Types 9 4 1 Norm...

Страница 19: ...usiness hours Eastern Standard Time Zone 10 2 Return Material Authorization RMA At no time will material be accepted as returned goods without a RMA number issued from the factory If parts are deemed...

Страница 20: ...An alternate method of performing the 90 minute yearly test would be to turn off the input feed breaker for the 90 minutes and then re apply when the 90 minute duration is complete 11 1 Battery Mainte...

Страница 21: ...hearing loss Secondary effects could be falling off a ladder or other sustaining injuries To install new batteries see section 5 0 Battery and DC Connections TIP If the batteries are to be replaced di...

Страница 22: ...to the USER PRESET levels 12 2 Operation The Dimming Module provides 3 independent channels of 0 10V DALI control signals for use in Emergency Lighting A simplified block diagram of one channel is as...

Страница 23: ...ion is an Open Circuit or 100 light level and the furthest CCW rotation is about 1V or 10 dimming level The User Presets are current dependent which means that the values will change depending upon ho...

Страница 24: ...connect DALI 0 10V violet wires into the connector J1 please observe DRIVER and DIMMER positions on the terminal block since this matters when using any dimming level other than 100 DRIVER is connecte...

Страница 25: ...E3MINI SERIES 25...

Страница 26: ...Mode regardless of the state of CMD 1 TEST Pressing this TEST button in the Charge Mode will transfer DIM 1 signal to its pre set value determined by DIM ADJ TEST button does not function in Inverter...

Страница 27: ...exceed the Inverters ratings Finally press the SYSTEM TEST button to ensure all lights are illuminated and that there are no faults when running in Inverter Mode Charger Mode Operation While utility...

Страница 28: ...tinuous un interrupted source of power LINE NEU 28 INSTALLATION OPERATION MANUAL DIAGRAM 1 Note LED Fixture Neutral wire not shown Always run dedicated hot and neutral wires to emergency fixtures per...

Страница 29: ...ode Operation Normally Off outputs are energized in Inverter Mode ONLY Use this output when you need to illuminate lights only when there is a power outage OUT 1 OUT 2 OR OUT 3 LINE NEU Input Power Wi...

Страница 30: ...EU LINE Input Power 30 INSTALLATION OPERATION MANUAL Wiring Diagram Using Switched Outputs Use when turning lights on off Switch Device NO DIMMERS Operation Use Switched Command s CMD 1 CMD 2 or CMD 3...

Страница 31: ...eration Inverters Normally On output N ON provides power to the LED Fixture in Normal Mode through the dimmer During Emergency Mode OUT 1 OUT 2 or OUT 3 can wrap around the dimmer and bypass it NEU LI...

Страница 32: ...4 Lights Operation Use any of the outputs configured for your application Zone 1 Normally On night lights Zone 2 OUT 1 switched On Off with CMD 1 Zone 3 OUT 2 switched On Off with CMD 2 Zone 4 Normall...

Отзывы: