MINI and MIX Series I/O modules/Modbus
version 1.3
www.gc5.pl
Page 17 / 73
1.15
Default Settings
Out of the box device as well as after restoring default values procedure, has got the
following default registers values:
Register Name
Default Value
COUNTER
0
BAUD RATE
76800 (76800 bps)
STOP BITS
1
DATA BITS
8
PARITY BITS
0
RESPONSE DELAY
0
WATCHDOG TIME
0 ( disabled)
STATE OF THE DIGITAL OUTPUTS AFTER START
0
STATE OF THE ANALOG OUTPUTS (DIGITAL)
AFTER START
0
STATE OF THE ANALOG OUTPUTS AFTER START
0
UNIVERSAL INPUT CONFIGURATION
1
INPUT FILTER TIME CONSTANT
2
UNIVERSAL INPUT RESOLUTION
0
ANALOG OUTPUT CONFIGURATION
0
Only for modules with IP
USERNAME
platform
PASSWORD
1000
IP ADDRESS
192.168.1.123
MASK
255.255.255.0
GATEWAY
192.168.1.1
HTTP PORT
80
MODBUS TCP PORT
502
MODBUS TCP TIMEOUT
60s
RS485 TIMEOUT
1000ms
SEND MODBUS ERRORS
DISABLE
BACNET ID
826001
BACNET UDP PORT
47808 (0xBAC0)
Table 6 Default values