MINI and MIX Series I/O modules/Modbus
version 1.3
www.gc5.pl
Page 35 / 73
3.10
Triac Outputs MODBUS Registers
State of Triac Outputs (40018)
This 16-bit register contains the state of the Triac Outputs in digital mode. /Setting
particular bit in the register enables the corresponding Triac Output according to the
following table:
No of bit in
register
No of Triac Output
0
1
1
2
2
3
3
4
Table 27 State of TO for 4TO-H and 4TO-H-IP
Default state of triac outputs (40143)
This 16-bits register contains the default state of the Triac Output device after the start or
watchdog reset.
The register bits correspond to the Triac Outputs according to the following table:
No of bit in
register
No of Digital Output
0
1
1
2
2
3
3
4
Table 28 Default status of TO for 4TO-H and 4TO-H-IP
Value of the Triac PWM outputs 1 – 4 (40121 – 40124)
In these 16-bit registers are stored value in percent’s of duty that appears on the PWM
output. Output working mode is defined by CONFIGURATION mode of Triac Output.
Default state of the Triac PWM outputs 1 – 4 (40145 – 40148)
In these 16-bit registers are stored value in percent’s of duty that appears on the Analog
Output after power on or watchdog reset.
Configuration mode of Triac Output 1 – 4 (40168 – 40171)
These 16-bits registers contain information about the mode of the Triac Outputs according
to the following table: