DMP116it | 1
st
Issue rev. a | 03/2022
pag.
MVC503R-MB Configuration Tool
–
Product Manual
13
Figure
14. Valve configuration box
•
PICV Valve Type:
in case the actuator is installed on a LIBRA pressure
independent control valve, it is possible to select the LIBRA range from the drop-
down menu in order to improve flow control.
•
Valve Characteristic:
it allows to select the characteristic of the LIBRA valve
(linear or equipercentage).
•
Stroke Valve [mm]:
it
allows to read the calibrated stroke value or select the
stroke value in fixed stroke mode.
Once the configuration parameters described above have been selected, press the
“
Write Device
” button and
verify with
the “
Read Device
” button that the parameters
have been correctly set.
In order to make the parameters changes active, it’s necessary to reset the
actuator through the “RESET” button in the “Actuator Status”
box.
3.6
“A
ctuator Status
”
Box
In this box the actuator status and possible anomalies are shown: