29 of 30
- The input sensor is
bypassed.
6
NEEDLE
PROBE
SENSOR 2
Needle
probe/sensor 2
error.
-
Check the parameter P0 value.
-
Check probe damages.
-
Check the probe connection.
-
Check the cabinet temperature..
Needle probe/sensor 2 error.
- The input sensor is
bypassed.
7
NEEDLE
PROBE
SENSOR 3
Needle
probe/sensor 3
error.
-
Check the parameter P0 value.
-
Check probe damages.
-
Check the probe connection.
-
Check the cabinet temperature..
Needle probe/sensor 2 error.
- The input sensor is
bypassed.
8
THERMAL
SWITCH
Thermal switch
alarm
-
Compressor overheating problem.
Check the thermal switch input
state.
-
Check parameter i11.
- A running cycle is
interrupted
-
Alarm output Activated.
9
HIGH
PRESSURE
SWITCH
High pressure
alarm.
-
Check the state of the high
pressure input.
-
Check parameter i6.
- A running cycle is interrupted
-
Alarm output Activated.
10
LOW
PRESSURE
SWITCH
Low pressure
alarm.
-
Check the state of the low
pressure input.
-
Check parameter i9.
- A running cycle is interrupted
-
Alarm output Activated.
11 DOOR
OPEN
Door open alarm.
-
Check the door status.
-
Check parameters i0 and i1.
- Cooling
configuration
i0
.
-
Alarm output activated.
12
HIGH
TEMPERATURE
High temperature
alarm
(HACCP).
-
Check the cabinet temperature.
-
Check parameters A4 and A5.
- Alarm
log.
-
Alarm output activated.
13
LOW
TEMPERATURE
Low temperature
alarm (HACCP).
- Check the cabinet temperature.
- Check parameters A1 and A2.
- Alarm
log
14
CYCLE
DURATION
Too Long cycle
duration (HACCP)
- Check parameters r5 and r6.
-
Alarm log.
15
BOARD
COMMUNICAT
IONS
Communication
Error
- Board and interface do not
communicate
- Check the user interface-control
module connection.
- A running cycle is interrupted
16
BOARD
COMPATIBILI
TY
User interface-
control module
compatibility error
- Check that the user interface and the
control module are compatible.
- A running cycle is interrupted
17
NEEDLE
PROBE
Needle probe alarm
- All the needle probe sensors enabled
are in alarm status
-
Any temperature controlled
cycle are interrupted
18
POWER
FAILURE
Power failure alarm
(HACCP alarm).
-
Check the device-power supply
connection.
- Alarm
log.
-
Last cycle status restored.
-
Alarm output activated.
19
SANITATION
PROBE
INSERTION
Sanitation alarm.
-
Check that the needle probe has
been correctly inserted and check
the value of parameters r17 and
r18.
-
The sanitation cycle will be
interrupted.
20
SANITATION
DURATION
Sanitation has not
been completed
within the
-
Check the value of parameter r23
- Alarm
Log.
- A running cycle is interrupted
- Alarm
Output
Activated.
Содержание ZERO TOUCH T12
Страница 26: ...26 EN 428000729137 USE AND MAINTENANCE MANUAL ZERO TOUCH 11 1 CONTAINERS ARRANGEMENT...
Страница 27: ...EN USE AND MAINTENANCE MANUAL 428000729137 27 ZERO TOUCH 11 2 KIT SUPPORTS ICE CREAM T5 T8...
Страница 28: ...28 EN 428000729137 USE AND MAINTENANCE MANUAL ZERO TOUCH 11 2 KIT SUPPORTS ICE CREAM T12...
Страница 29: ...EN USE AND MAINTENANCE MANUAL 428000729137 29 ZERO TOUCH 11 2 KIT SUPPORTS ICE CREAM T16...
Страница 39: ......
Страница 40: ...ISA Bastia Umbra Perugia Italy Tel 39 075 80171 Fax 39 075 8000900 www isaitaly com...
Страница 71: ......
Страница 72: ...ISA Bastia Umbra Perugia Italy Tel 39 075 80171 Fax 39 075 8000900 www isaitaly com...