S550 GENERAL DESCRIPTION

The IRIS Model S550 is a state- of- the-art flame
monitor viewing head utilizing two types of
detectors, an IR (infrared) solid state and UV
(ultra violet) tube.

The S550’s work with the latest version of the
P520/P522 signal processors. Like other viewing
heads in the S500 family, the S550’s produce
output pulse rates propor tional to the flame signal
strength; the pulse rates are displayed at the front
panel of the signal processors. But, unlike the
other members of the S500 family, certain
parameters in the S550 viewing head can be
selected or adjusted remotely from the front panel
of the P520/P522 signal processors. The
parameters are:

a) UV gain

0-99

b) Fil ter Se lec tion

1-8

c) IR gain

0-699

Once adjusted, the new parameters are stored in
EEPROM in the signal processor. If power is
removed from the signal processor which powers
the viewing head and then reapplied, the signal
processor then automati cally re-sends the stored
parameters out to the S550 viewing head. In
addition, at the front panel of the signal processors 
the operator may also select “CAL”, a semiau to 

-

matic mode which will help to speed up the S550
setup. This is explained in detail in the section
called 

CALIBRATING THE S550

 on page 10. Also

notice the 

FLOWCHART OF S550 PROGRAMMING

Fig ure 3 on page 15. Thus the S550 is a dual-
 sensor viewing head where the gain and filter
selec tions are adjusted remotely and stored in the
P520/P522 signal processors.

S552 GENERAL DESCRIPTION

The S552 is for IR sensing only.  It is basically an
S550 without a UV capability.  The P520 or P522
will be aware of which viewing head of the S550
family is connected to it so that only those adjust -
ments which are appro priate to the S552 will be
made available to the operator.  These adjust ments 
apply to the S552:

a) Filter Selection

1-8

b) IR gain

0-699

When it comes to features like CAL, which will be 
described later, the operator is only given those
choices which are appro priate.  For example, he
does not have to choose between calibrating with
the UV sensor or the IR sensor; in CAL he is only
offered the choice of calibrating with the IR sensor 
or not. This is shown in the 

FLOWCHART OF S552

PROGRAMMING

, Fig ure 4 on page 16.

To keep the manual straightforward only the
operation of an S550 is described.  If one has an
S552 one should simply disregard references to
those features of the S550 which are UV-related.

S556 GENERAL DESCRIPTION

The S556 is for UV sensing only.  It is basically an 
S550 without an IR capability.  The P520 or P522
will be aware of which viewing head of the S550
family is connected to it so that only the
adjustment which is appro priate to the S556 will
be made available to the operator:

a) UV gain

0-99

When it comes to features like CAL, which will be 
described later, the operator is only given those
choices which are appro priate.  For example, he
does not have to choose between calibrating with
the UV sensor or the IR sensor; in CAL he is only
offered the choice of calibrating with the UV
sensor or not. This is shown in the 

FLOWCHART

OF S556 PROGRAMMING

, Fig ure 5 on page 17.

To keep the manual straightforward only the
operation of an S550 is described.  If one has an
S556 one should simply disregard references to
those features of the S550 which are IR-related.

COM PARI SON WITH OTHER MODEL 500
SE RIES VIEW ING HEADS

The S550 uses a Germanium sensor for IR
detection like an S511 and uses a high- voltage
vacuum tube sensor for UV detection like the
S506’s, but 

both

 sensors are in the same housing

in the S550. The pulses from the UV and IR
sensors are summed inter nally into a single pulse
stream out to the signal processor.

A dual-LED indicator is used to indicate the pulse
rate out of the S550. It is visible at the rear of the

PAGE 3

IRIS MODEL S550 APPLICATION MANUAL

Содержание S550

Страница 1: ...PAGE 1 IRIS MODEL S550 APPLICATION MANUAL FLAME MONITORING SYSTEM MODEL S550 S552 S556 VIEWING HEAD APPLICATION MANUAL ...

Страница 2: ... ARE STORED 8 ASSIGNING DIFF S550 SETTINGS TO A B 9 USING TWO VIEWING HEADS PER AMPLIFIER 9 BEFORE MAKING ADJUSTMENTS 10 NEW P520 P522 FRONT PANEL 10 CALIBRATING THE S550 10 EXAMINING RESULTS GAIN SETTINGS CALIB 10 CHECKING OR CHANGING UV GAIN 11 CHECKING OR CHANGING IR FILTER 11 CHECKING OR CHANGING IR GAIN 11 MANUAL SETUP OF THE S550 12 RETURN TO DEFAULT SETTINGS 12 ANGLE OF VIEW 13 GENERAL COMM...

Страница 3: ...Filter Selection 1 8 b IR gain 0 699 When it comes to features like CAL which will be described later the operator is only given those choices which are appropriate For example he does not have to choose between calibrating with the UV sensor or the IR sensor in CAL he is only offered the choice of calibrating with the IR sensor or not This is shown in the FLOWCHART OF S552 PROGRAMMING Figure 4 on...

Страница 4: ...processors Also the earlier IR sensitive family members had only 4 high pass filters to choose from the S550 has 8 S511 S512 S550 LL 36 Hz 1 16 Hz L 71 Hz 2 24 Hz M 105 Hz 3 33 Hz H 186 Hz 4 52 Hz 5 75 Hz 6 100 Hz 7 155 Hz 8 215 Hz TECHNOLOGY USED IN THE S550 The UV and IR sensors in the S550 share a common optical axis efficiently by using a unique dichroic beamsplitting mirror Over 80 of the ult...

Страница 5: ...PAGE 5 IRIS MODEL S550 APPLICATION MANUAL ...

Страница 6: ...e done as follows Remove the plug from its packaging and layout the components 1 Strip 2 inches of the cable outer cover from the cable removing any cellophane wrap or filler material and strip the insulation from the shielded wire if insulated over shield a full 2 inches to expose shield 2 Slide the shield back until a bulge develops close to where the wire exits the cable outer covering 3 Carefu...

Страница 7: ... entirely The reason for this is that there is a complete change in the flicker content for the existing viewing head sighting If this is the case then one should try and optimize the flame signal for the sour gas by zeroing in on this flame not the warm up burner After optimizing the sighting for the sour gas one may find that the signal level is too low on the natural gas One should then try the...

Страница 8: ...ition the zone of higher UV intensity does not overlap the same zones of adjacent or opposing burners so that with proper sighting discrimination is predictable As a general rule the sighting of the S550 when using the UV detector will be more likely a line of sight than the IR flicker detector which will read flame signals bouncing off the side of the sight pipe and other reflectors Sometimes the...

Страница 9: ...n the signal level so if the associated S550 and signal processor has been previously calibrated it will be necessary to calibrate the processor again so that the gain settings will be correct If the discrimi nation is still not satisfactory then try an orificing disc with a smaller diameter hole Generally speaking orificing should always be considered when the burner s are large 50K lbs of steam ...

Страница 10: ...manually changing S550 settings when the desired channel is not selected press the push button for the desired channel and then proceed During the process of examining or changing the S550 settings with the Channel A and B NO and YES push buttons the red LED for the channel which the changes apply will be blinking One should visually check which channel push button is lighted when the S550 setting...

Страница 11: ...ture one does not have the option of working with the channel that is not selected by the external input 3 Bring the firing rate of the burner to a low fire condition 4 If the flame relay has not pulled in adjust the flame on off set points so it does pull in 5 Decide whether to calibrate using the UV or IR sensor See earlier sections on I R DETECTOR and UV DETECTOR At the front panel of the P520 ...

Страница 12: ...r all of the initial setup proce dures described in this manual Further infor mation on how these filters can affect the discrimi nation ratio is found in the P520 APPLICATION MANUAL and in the P522 APPLICATION MANUAL in the section MULTIBURNER REQUIREMENTS For further information please call the factory or contact IRIS Systems Inc See page 13 for contact information CHECKING OR CHANGING IR GAIN Y...

Страница 13: ...tinue reducing the gain in steps of 100 until the displayed reading is reduced Then set the gain so the reading is in the 1000 to 1400 range If the IR sensor was not saturated one can skip paragraph 5 below 5 If the S550 was saturating one should check the aiming of the S550 again using the LED on the back of the housing to adjust the viewing angle of the head for a maximum pulse rate If the LED p...

Страница 14: ...vative product that this is the ultimate state of the art flame monitor The way it works has been described only in a general sense and obviously the algorithms implemented by the embedded controller software are proprietary and will not be made public Any existing P520 or P522 signal processor can be upgraded to an S550 compatible processor by changing the controller chip and the front panel TECH...

Страница 15: ...PAGE 15 IRIS MODEL S550 APPLICATION MANUAL Figure 1 Figure 2 ...

Страница 16: ...IRIS MODEL S550 APPLICATION MANUAL PAGE 16 Figure 3 ...

Страница 17: ...PAGE 17 IRIS MODEL S550 APPLICATION MANUAL Figure 4 ...

Страница 18: ...PAGE 18 IRIS MODEL S550 APPLICATION MANUAL Figure 5 ...

Страница 19: ...PAGE 19 IRIS MODEL S550 APPLICATION MANUAL 5 June 1997 ...

Отзывы: