2. INSTALLATION
2.1. PLATE DATA
2.2. POSITIONING
•
•
Check that the plate data and the characteristics of
the electrical line correspond (V, kW, Hz, no. phases
and power available).
The plate showing the appliance's characteristics is
affixed on the right side of the holding cabinet (fig.2)
and under the control panel.
The eventual preparation of machine rooms for positioning
the condensing units must follow the Standards in force
in the country of installation regarding fire prevention
(contact the local fire department for the due indications).
It must also be considered that any intervention of
the safety valve or fuse caps, currently in the refrigerator
circuit, leads to the immediate discharge of all coolant
used in the environment. Consequently, realise
appropriate means of disposal and first aid as indicated
in the coolant safety sheet (8see par. 2.12).
Fig. 2
31010
CORBANESE (TV)
ITALY
Mod.
s/n
Compressor HERMETIC
V
A
Refrigerant R404A / R452A Charge
Desing pressure (Low)
Desing pressure (High)
Rated Load
Class
Volume
PED Code
IP
KPa
KPa
Kw
Ph
Hz
Model
Serial no.
mm/yy/progres.
Frequency
Power
Phase
Absorption
Volt
•
•
•
•
•
•
•
•
The machine must be installed and inspected with
complete respect of the accident-prevention legal Stan-
dards, traditional regulations and Standards in force.
The installer must check any provisions on the subject
of fire prevention (contact the local fire department for
the due indications).
Place the machine in the provided place.
Use the adjustment feet to level the appliance. Do not
use the forklift truck to straighten the machine as it
could damage the basin guides on the bottom of the
machine (Fig.3).
If the appliances are not levelled, their functioning and
the flow of condensate can be compromised.
To avoid (Fig.4):
Places exposed to direct sunlight
Enclosed places with high temperatures and poor air
exchange. (
see
Table 2
).
Do not install the machine near to any heat source.
The remote units are designed to be installed in
places protected from the weather. The plants must
be positioned on a level cement or steel base and
space for maintenance must be foreseen, as indica-
ted in the technical data sheets. For installation on
the roof or on floors, weight distribution beams should
be arranged. The base must also be sufficiently
strong and suitable to support the weight of the entire
unit, as resulting from the technical data on the speci-
fic drawing. To avoid additional vibrations and noises
we recommend use of neoprene anti-vibration mats
placed under the corners of the unit's base.
If the operating cabinet holder is to be installed below
the floor level or underground, the installer will apply
the clauses required by the Standard EN378-
1:2008+A1:2010 ANNEX D to ensure that no person
can remain locked in the cell at the end of the work
shift.
The cabinet holder can be installed underground or on
a mezzanine as long as there are suitable emergency
exits as provided for by the Standard EN378-
1:2008+A1:2010 ANNEX C.
The need for forced ventilation in a room where the
cabinet holder is installed must be verified by the
installer, as required by the Standard EN378-
2:2008+A1:2009 in chapter 6.2.14.