2.  INSTALLATION

2.1.  PLATE DATA

 2.2.  POSITIONING

• 

• 

Check that the plate data and the characteristics of 

the electrical line correspond (V, kW, Hz, no. phases 

and power available).

The plate showing the appliance's characteristics is 

affixed on the right side of the holding cabinet (fig.2) 

and under the control panel.

The eventual preparation of machine rooms for positioning 

the condensing units must follow the Standards in force 

in the country of installation regarding fire prevention 

(contact the local fire department for the due indications).

         It must also be considered that any intervention of 

the safety valve or fuse caps, currently in the refrigerator 

circuit, leads to the immediate discharge of all coolant 

used in the environment. Consequently, realise 

appropriate means of disposal and first aid as indicated 

in the coolant safety sheet (8see par. 2.12).

Fig. 2

31010

CORBANESE (TV)

ITALY

Mod.

s/n

Compressor       HERMETIC

V

A

Refrigerant    R404A / R452A      Charge

Desing pressure (Low)

Desing pressure (High)

Rated Load

Class

Volume 

PED Code

IP

KPa

KPa

Kw

Ph

Hz

Model  
Serial no.
mm/yy/progres.

Frequency

Power

Phase

Absorption

Volt

• 

• 

• 

• 

• 

• 

• 

• 

The machine must be installed and inspected with 

complete respect of the accident-prevention legal Stan-

dards, traditional regulations and Standards in force.
The installer must check any provisions on the subject 

of fire prevention (contact the local fire department for 

the due indications).
Place the machine in the provided place.
Use the adjustment feet to level the appliance. Do not 

use the forklift truck to straighten the machine as it 

could damage the basin guides on the bottom of the 

machine (Fig.3).
If the appliances are not levelled, their functioning and 

the flow of condensate can be compromised.

To avoid (Fig.4):

Places exposed to direct sunlight

Enclosed places with high temperatures and poor air 

exchange. (

see 

Table 2

).

Do not install the machine near to any heat source.

The remote units are designed to be installed in 

places protected from the weather. The plants must 

be positioned on a level cement or steel base and 

space for maintenance must be foreseen, as indica-

ted in the technical data sheets. For installation on 

the roof or on floors, weight distribution beams should 

be arranged. The base must also be sufficiently 

strong and suitable to support the weight of the entire 

unit, as resulting from the technical data on the speci-

fic drawing. To avoid additional vibrations and noises 

we recommend use of neoprene anti-vibration mats 

placed under the corners of the unit's base.

If the operating cabinet holder is to be installed below 

the floor level or underground, the installer will apply 

the clauses required by the Standard EN378-

1:2008+A1:2010 ANNEX D to ensure that no person 

can remain locked in the cell at the end of the work 

shift.

The cabinet holder can be installed underground or on 

a mezzanine as long as there are suitable emergency 

exits as provided for by the Standard EN378-

1:2008+A1:2010 ANNEX C.

The need for forced ventilation in a room where the 

cabinet holder is installed must be verified by the 

installer, as required by the Standard EN378-

2:2008+A1:2009 in chapter 6.2.14.

Fig. 4

Fig. 3

• 

• 

• 

• 

Содержание CP One

Страница 1: ...U S E A N D M A I N T E N A N C E I N S T R U C T I O N S REV No REVISION DESCRIPTION REV DATE PROOF READER 00 26 10 2015 L B FIRST EMISSION 01 10 09 2017 D N ADDED GAS R452A...

Страница 2: ...you for having chosen IRINOX Please take the time to read this manual carefully to make the most of all the potential and benefits of your new CP ONE We would like to remind you that the perfect opera...

Страница 3: ...the connection regulations Use gloves suitable for cold trays During cleaning operations especially of the condenser always wear protective gloves glasses and masks for protection of the respiratory t...

Страница 4: ...CONNECTION 9 2 7 REFRIGERATOR CONNECTION 10 2 8 CONDENSATE DRAIN 11 2 9 WATER COOLING UNITS CONNECTION 11 2 10 NOTES FOR THE INSTALLER 12 2 11 SAFETY AND CONTROL SYSTEMS 12 2 12 R404A R452A GAS SAFETY...

Страница 5: ...with the instructions in this manual Installation must be carried out by authorised and specialised staff respecting the instructions in this manual The manufacturer declares and assigns to each indiv...

Страница 6: ...ned place see par 2 2 After the packaging has been removed check the integrity of the holding cabinet Remove the protective PVC film from all sides Fig 1 When handling the packaging and the wooden bas...

Страница 7: ...level the appliance Do not use the forklift truck to straighten the machine as it could damage the basin guides on the bottom of the machine Fig 3 If the appliances are not levelled their functioning...

Страница 8: ...8 2 3 DIMENSIONAL DATA 810 A A B B 2085 1970 56 670 1053 5 1347 871 5 SECTION B B SECTION A A Service Area 250...

Страница 9: ...l data sheets The voltage of the systems must be within the limit of 10 and the voltage distortion of the phases must not exceed 3 The electrical power connection must be performed by qualified staff...

Страница 10: ...cabinet holder s heat exchangers can be shut off from the rest of the plant via valves these exchangers must be protected by suitable safety devices as forese en by the Standard EN378 2 2008 A1 2009...

Страница 11: ...isolante del tipo a cellule chiuse di buona qualit dello spessore minimo di 19 mm Table 7 Flow line mm Intake line mm Hot gas line mm Pipes maximum length 15 m 6 12 10 19 mm 2 9 WATER COOLING UNITS C...

Страница 12: ...vation cycle reach the set temperature and one manual defro sting cycle Inform the customer regarding the exact use of the appliance with specific reference to use and the requirements of the customer...

Страница 13: ...ble that it is dangerous due to cutaneous absorption Repeated and prolonged contact can cause the removal of sebaceous matter with consequent dryness cracking and dermatitis Ecological information It...

Страница 14: ...appliance or package indicates that at the end of the product s life it must be collected separately from other waste The separate waste collection of this appliance at the end of its life is organis...

Страница 15: ...resh products or for brief periods of cooked food NEGATIVE Mode 20 C suitable for the preserva tion of frozen products also for long periods of time CHOCOLATE Mode 14 C suitable for the preserva tion...

Страница 16: ...g the minutes press P5 to confirm and save the clock setting rtc appears on the display The indicator goes off Description Phase 1 With the cabinet holder in Stand by select the operating mode See par...

Страница 17: ...Ur2 average humidity Ur3 high humidity Press P1 to confirm the data entered and exit the menu If no key is pressed after a pre set time one automatically exits the menu and the entered data is saved O...

Страница 18: ...temperature unit of measurement is F The instrument is in standby Steady Flashing Change temperature set point Compressor run requested but pending safety time end Defrosting in progress but pending c...

Страница 19: ...ing the machine on empty until the operating temperature is set In order to have good machine performance and not have deterioration of food we recommend you Make sure that a sufficient space is left...

Страница 20: ...intenance operation disconnect the machine from the electrical power supply by turning the main switch off and remo ving the plug do not pull the power supply cable to disconnect the machine from the...

Страница 21: ...visual signal system which signals the presence of an alarm press a key to silence the sound alarm Meaning Minimum temperature HACCP alarm Maximum temperature HACCP alarm Open door HACCP alarm No vol...

Страница 22: ...e connection to the electrical line No coolant gas Technician intervention No power supply Check the connection to the electrical line Faulty fan Intervention of a technician to replace the fan No ele...

Страница 23: ...aintenance operations accurately reas semble the covers and tighten the locking screws Fig 28 Fig 29 For correct and efficient functioning of the cabinet holder the air condenser must be kept clean in...

Страница 24: ...OX headquarter via Madonna di Loreto 6 B 31020 Corbanese di Tarzo TV Italy production site via Caduti nei lager 1 Z I Prealpi Trevigiane loc Scomigo 31015 Conegliano TV Italy P 39 0438 2020 F 39 0438...

Отзывы: