2.7.2.  Different level installation

If the remote unit is installed higher with respect to the 

appliance (fig.13), a siphon must be installed at every 

branch or return (a), every 1.8 metres of difference in level 

along the return pipe and at every delivery (b).

If the remote unit is installed lower compared to the appli-

ance, no siphon is required (fig.12).

Fig. 12

Fig. 13

Different level
installation

2.7.3.  Refrigerator-remote units connection

The diameters of the appliance power supply pipes are 

sized for installation distances up to 15 metres (

see 

Table 7

).

For greater distances, contact IRINOX Spa.

CP ONE has a basin for collecting the condensate. 

The basin can be extracted from the bottom part of the 

cabinet holder.

 

           L’isolamento della linea di aspirazione e del gas 

caldo dovrà essere fatto con isolante del tipo a cellule 

chiuse di buona qualità, dello spessore minimo di 19 

mm.

Table 7

Flow line

Ø mm

Intake line

Ø mm

Hot gas line

Ø mm

Pipes maximum length: 15 m

6

12

10

19 mm

2.9.  WATER COOLING UNITS CONNECTION

• 

• 

•  During testing (mains water), with the machine at a 

standstill and water network ready, check that the 

condenser drain pipe does not allow water to escape. 

If this is not the case, regulate the pressure valve until 

the leak stops (Fig.17).

It is recommended to supply a gate valve and an 

inspectionable filter in the water flow line. The 

condenser water flow and drain pipes are indicated by 

relevant plates. Both connections are 3/8”F and threa-

ded.

See 

Table 3

 for maximum water consumption

Fig. 17

FEATURES OF THE LINE FOR

WATER-COOLED CONDENSING UNITS

Maximum pressure of the inlet water
Minimum pressure of the inlet water
Maximum temperature of the inlet water in order to 

guarantee normal functioning of the appliance

1600 KPa
50 KPa
25°C 

(well water)

2.8.  CONDENSATE DRAIN

Intake pipe

Содержание CP One

Страница 1: ...U S E A N D M A I N T E N A N C E I N S T R U C T I O N S REV No REVISION DESCRIPTION REV DATE PROOF READER 00 26 10 2015 L B FIRST EMISSION 01 10 09 2017 D N ADDED GAS R452A...

Страница 2: ...you for having chosen IRINOX Please take the time to read this manual carefully to make the most of all the potential and benefits of your new CP ONE We would like to remind you that the perfect opera...

Страница 3: ...the connection regulations Use gloves suitable for cold trays During cleaning operations especially of the condenser always wear protective gloves glasses and masks for protection of the respiratory t...

Страница 4: ...CONNECTION 9 2 7 REFRIGERATOR CONNECTION 10 2 8 CONDENSATE DRAIN 11 2 9 WATER COOLING UNITS CONNECTION 11 2 10 NOTES FOR THE INSTALLER 12 2 11 SAFETY AND CONTROL SYSTEMS 12 2 12 R404A R452A GAS SAFETY...

Страница 5: ...with the instructions in this manual Installation must be carried out by authorised and specialised staff respecting the instructions in this manual The manufacturer declares and assigns to each indiv...

Страница 6: ...ned place see par 2 2 After the packaging has been removed check the integrity of the holding cabinet Remove the protective PVC film from all sides Fig 1 When handling the packaging and the wooden bas...

Страница 7: ...level the appliance Do not use the forklift truck to straighten the machine as it could damage the basin guides on the bottom of the machine Fig 3 If the appliances are not levelled their functioning...

Страница 8: ...8 2 3 DIMENSIONAL DATA 810 A A B B 2085 1970 56 670 1053 5 1347 871 5 SECTION B B SECTION A A Service Area 250...

Страница 9: ...l data sheets The voltage of the systems must be within the limit of 10 and the voltage distortion of the phases must not exceed 3 The electrical power connection must be performed by qualified staff...

Страница 10: ...cabinet holder s heat exchangers can be shut off from the rest of the plant via valves these exchangers must be protected by suitable safety devices as forese en by the Standard EN378 2 2008 A1 2009...

Страница 11: ...isolante del tipo a cellule chiuse di buona qualit dello spessore minimo di 19 mm Table 7 Flow line mm Intake line mm Hot gas line mm Pipes maximum length 15 m 6 12 10 19 mm 2 9 WATER COOLING UNITS C...

Страница 12: ...vation cycle reach the set temperature and one manual defro sting cycle Inform the customer regarding the exact use of the appliance with specific reference to use and the requirements of the customer...

Страница 13: ...ble that it is dangerous due to cutaneous absorption Repeated and prolonged contact can cause the removal of sebaceous matter with consequent dryness cracking and dermatitis Ecological information It...

Страница 14: ...appliance or package indicates that at the end of the product s life it must be collected separately from other waste The separate waste collection of this appliance at the end of its life is organis...

Страница 15: ...resh products or for brief periods of cooked food NEGATIVE Mode 20 C suitable for the preserva tion of frozen products also for long periods of time CHOCOLATE Mode 14 C suitable for the preserva tion...

Страница 16: ...g the minutes press P5 to confirm and save the clock setting rtc appears on the display The indicator goes off Description Phase 1 With the cabinet holder in Stand by select the operating mode See par...

Страница 17: ...Ur2 average humidity Ur3 high humidity Press P1 to confirm the data entered and exit the menu If no key is pressed after a pre set time one automatically exits the menu and the entered data is saved O...

Страница 18: ...temperature unit of measurement is F The instrument is in standby Steady Flashing Change temperature set point Compressor run requested but pending safety time end Defrosting in progress but pending c...

Страница 19: ...ing the machine on empty until the operating temperature is set In order to have good machine performance and not have deterioration of food we recommend you Make sure that a sufficient space is left...

Страница 20: ...intenance operation disconnect the machine from the electrical power supply by turning the main switch off and remo ving the plug do not pull the power supply cable to disconnect the machine from the...

Страница 21: ...visual signal system which signals the presence of an alarm press a key to silence the sound alarm Meaning Minimum temperature HACCP alarm Maximum temperature HACCP alarm Open door HACCP alarm No vol...

Страница 22: ...e connection to the electrical line No coolant gas Technician intervention No power supply Check the connection to the electrical line Faulty fan Intervention of a technician to replace the fan No ele...

Страница 23: ...aintenance operations accurately reas semble the covers and tighten the locking screws Fig 28 Fig 29 For correct and efficient functioning of the cabinet holder the air condenser must be kept clean in...

Страница 24: ...OX headquarter via Madonna di Loreto 6 B 31020 Corbanese di Tarzo TV Italy production site via Caduti nei lager 1 Z I Prealpi Trevigiane loc Scomigo 31015 Conegliano TV Italy P 39 0438 2020 F 39 0438...

Отзывы: