2.7.2. Different level installation
If the remote unit is installed higher with respect to the
appliance (fig.13), a siphon must be installed at every
branch or return (a), every 1.8 metres of difference in level
along the return pipe and at every delivery (b).
If the remote unit is installed lower compared to the appli-
ance, no siphon is required (fig.12).
Fig. 12
Fig. 13
Different level
installation
2.7.3. Refrigerator-remote units connection
The diameters of the appliance power supply pipes are
sized for installation distances up to 15 metres (
see
Table 7
).
For greater distances, contact IRINOX Spa.
CP ONE has a basin for collecting the condensate.
The basin can be extracted from the bottom part of the
cabinet holder.
L’isolamento della linea di aspirazione e del gas
caldo dovrà essere fatto con isolante del tipo a cellule
chiuse di buona qualità, dello spessore minimo di 19
mm.
Table 7
Flow line
Ø mm
Intake line
Ø mm
Hot gas line
Ø mm
Pipes maximum length: 15 m
6
12
10
19 mm
2.9. WATER COOLING UNITS CONNECTION
•
•
• During testing (mains water), with the machine at a
standstill and water network ready, check that the
condenser drain pipe does not allow water to escape.
If this is not the case, regulate the pressure valve until
the leak stops (Fig.17).
It is recommended to supply a gate valve and an
inspectionable filter in the water flow line. The
condenser water flow and drain pipes are indicated by
relevant plates. Both connections are 3/8”F and threa-
ded.
See
Table 3
for maximum water consumption
Fig. 17
FEATURES OF THE LINE FOR
WATER-COOLED CONDENSING UNITS
Maximum pressure of the inlet water
Minimum pressure of the inlet water
Maximum temperature of the inlet water in order to
guarantee normal functioning of the appliance
1600 KPa
50 KPa
25°C
(well water)
2.8. CONDENSATE DRAIN
Intake pipe