OS-NET Programming Guide
OS-NET Programming Guide R0
11
AMBIENT LUX
AMBIENT LUX represents various thresholds of ambient light level set for OS-NET sensor and controller to execute the
control. The higher the lux value is, the brighter the ambient light level. DISABLE means to disable the ambient light
sensor which will allow sensor/controller to execute the control regardless of the ambient light level. CURRENT means
setting the current ambient light level as threshold.
DELAY
DELAY represents the time (in minutes) that OS-NET sensor/controller will turn off or dim the light down after the area is
vacated.
TIME OFF
TIME OFF represents the time that OS-NET sensor/controller will keep the light at low dim level after the DELAY time
elapsed. TIME OFF setting is applicable only if the OSLATO mode is set.
HIGH DIM
HIGH DIM setting is to set the output level (in %) of connected lighting during occupancy, or when ambient light level is
lower than the threshold if daylight sensing control is set. For StepDIM control, 8 levels ranging from 50% to 100% can
be selected. If SmartDIM is set, the sensor/controller will continuously dim the lighting output to maintain the overall
area lighting level within the preset range.
LOW DIM/SmartDIM
LOW DIM setting is to set the output level (in %) of connected lighting during vacancy. The OS-NET sensor/controller will
regulate the lighting output at the set level. Setting the LOW DIM at 0 means light off during vacancy. The LOW DIM
setting will become a SmartDIM setting bar if the sensor/controller is set with SmartDIM control, and the LOW DIM level
will be 50% of the SmartDIM setting.
RAMP UP
RAMP UP represents the speed of lighting output will be increased when sensor detects the presence of occupant. 3
options (INSTANT/SOFT/SLOW) are available for selection.
FADE DOWN
FADE DOWN represents the speed of lighting output will be decreased by the sensor/controller. 3 options
(INSTANT/SOFT/SLOW) are available for selection.
VM-TB
VM-TB is to set the time period BEFORE Virtual Midnight. This setting is available only if DSVM control is set.
VM-TA
VM-TA is to set the time period AFTER Virtual Midnight. This setting is available only if DSVM control is set.
SENSITIVITY
SENSITIVITY is for setting the occupancy sensing sensitivity of OS-NET sensor. For typical indoor/outdoor, low bay
applications, LOW sensitivity can be set to eliminate false-on triggering. For high bay applications, NORMAL or HIGH
sensitivity can be set to improve occupancy sensing capability. This setting is only available for OS-NET sensor.
BURN-IN
BURN-IN setting is to conduct a test with all lightings continuously on for a period of time set (in hours) or manual