9
1)
Open the terminal block cover located on the rear panel of the UPS, please refer
to the appearance diagram)
2)
For 5/6K(L) UPS, it is recommended to select the UL1015 10AWG(6mm
2
) wire or
other insulated wire which complies with AWG Standard for the UPS input and
output wirings.
3)
For 10K(L)/3 phase 10KS UPS, it is recommended to select the UL1015
8AWG(10mm
2
) wire or other insulated wire which complies with AWG Standard for
the UPS input and output wirings.
4)
For 3 phase 15KS /3 phase 20KL UPS, it is recommended to select the UL1015
6AWG (25mm
2
) wire or other insulated wire which complies with AWG Standard
for the UPS input and output wirings.
Note: Do not use the wall receptacle as the input power source for the UPS, as its
rated current is less than the UPS’s maximum input current. Otherwise the receptacle
may be burned and destroyed.
5)
Connect the input and output wires to the corresponding input and output
terminals according to the following diagram.
6)
Note: you must make sure that the input and output wires and the input and
output terminals are connected tightly
the protective earth ground wire refers to
the wire connection between the equipment which consumes electric equipment
and the ground wire. The wire diameter of protective earth ground wire should be
at least as above mentioned for each model and green wire or green wire with
yellow ribbon wire is used.
7)
After having completed the installation, make sure the wiring is correct.
8)
Please install the leak current protective breaker at the output power distribution
panel of the UPS if necessary.
9)
To connect the load with the UPS, please turn off all the loads first, then perform
the connection and finally turn on the loads one by one. No matter the UPS is
connected to the utility power or not, the output of the UPS may have electricity.