Universal WiFi BAT Installation Guide (rev 1.0) 15
DSC Panel Programming
See Supported Panels section on page 25. All Control Panels
must have a Phone Number in the Panel and an Account Number
in the Panel. As long as your Reporting Codes are in the Panel
and is transmitting in Contact ID it will send signals.
Programming when using TELCO (Recommended)
: General
Concept Programming on DSC (BAT WiFi as Sole
Communicator):
Section
BAT as Sole Communicator
Code Summarization
301
Enter a Receiver Number
310
Enter Account Number
350
Enter ‘03’ to send Contact ID Panel default is ‘04’, SIA
Note: Ensure All Report Codes are in, and signals can be sent.
Programming ONLY when using PC-Link to send Signals
(Not Recommended)
: DSC Programming for Communications -
GSM Emulation:
If GSM is used, it must be in dialer capture mode
Secti
on
BAT as
Sole
Communi-
cator
BAT as
Failover w/
Add'l
Communi-
cation Device
BAT as Dual
Reporting w/
Add'l
Communi-
cation Device
Code
Summarization
015
Disable
Option 7
If GSM, Disable
Option 7
If Phone Line,
Enable Option 7
If GSM, Disable
Option 7
If Phone Line,
Enable Option 7
Option 7 turns on/off
telephone line
supervision.
167
Set ‘060’
Seconds
Set ‘060’
Seconds
Set ‘060’
Seconds
Sets T-Link
acknowledgement
delay to 60 secs.
301
Set 'CAAF'
Set 'CAAF'
Set 'CAAF'
'CAAF' has to be set
for the panel to send
signals to the PC-
Link
302
N/A
N/A
Set 'Central
Station Receiver
#'
Second telephone
number goes here.
303
N/A
Set 'Central
Station Receiver
#'
Set 'Central
Station Receiver
#'
This section is the
telephone backup of
section 301.
350
Set ‘04’ /
‘04’
Set ‘04’ / ’03 for
Contact ID, 04
for SIA
FSK’ **
Set ‘04’ / ’03 for
Contact ID, 04
for SIA
FSK’ **
Format sent as
either contact ID
(03), or SIA FSK
(04). The PC-Link /
BAT can ONLY
receive signals via
SIA FSK (04).