background image

Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE

 

Page 2/16

 

UMA-CDZ-IP-ACIWM200.001-00

 

WARNING 

 

Safety of AIR CONDITIONER is warranted only by proper use of 

these instruction which must be kept. 

 

Installation must be done by qualified personnel only after 

enclosure power supply disconnecting. 

 

Before any operation, switch off the power supply. 

 

The appliance is classified as not accessible to the general public 

 

The air conditioner is not to be used by persons (including children) with reduced 

physical, sensory or mental capabilities, or lack of experience and knowledge, 

unless they have been given supervision or instruction. 

 

Children being supervised not to play with the air conditioner. 

 

The air conditioner must be installed in accordance with national wiring 

regulations (IEC 60335-2-40:2018) 

 

Upstream of the electrical connection, an efficient disconnection system must be 

provided in compliance with the AS / NSZ 3000 standard 

 

Internal and external components of electrical enclosure don’t have to affect the 

proper installation of air conditioner. 

 

Inside of electrical enclosure there must not be components that could affect the 

proper ventilation. 

 

Provide a proper fixing of the electrical enclosure to the floor to prevent 

accidental tipping due to the supplementary weight of installed AIR 

CONDITIONER. 

 

Installation position of AIR CONDITIONER must be selected to ensure good 

ventilation. Take care that any internal/external components of enclosure don’t 

obstruct air passage. (see section 2.2 GENERAL CHECKS BEFORE 

INSTALLATION) 

 

The heat loss of the components installed inside of the electrical enclosure must 

be lower than useful cooling power of the AIR CONDITIONER. 

 

AIR  CONDITIONER  IP-ACIW  series  must  be  handled  in  upright  position  and 

protected against accidental tipping over. 

 

Do not modify the AIR CONDITIONER structure if it is not specified in these 

instruction or associated instructions. 

 

During transportation of enclosures with installed air conditioner a proper 

bracket must be used to support the cooling unit weight. 

 

Install only original spare parts and accessories.  

 

Protection against access to live parts must be warranty by installer.  

 

The  supply  connector  of  the  AIR  CONDITIONER  must  only  be  connected  and 

disconnected when electrical enclosure is electrically disconnected.

 

 

Follow all technical data shown in this manual

  

 

 

 

 

 

 

 

Содержание IP-ACIWM200.001

Страница 1: ...001 00 USER S MANUAL PART 2 AIR CONDITIONER FOR ELECTRICAL ENCLOSURE INDOOR APPLICATION IP ACIWM200 001 Document UMA CDZ IP ACIWM200 001 00 Date Name Description Original user s manual for air conditi...

Страница 2: ...enclosure there must not be components that could affect the proper ventilation Provide a proper fixing of the electrical enclosure to the floor to prevent accidental tipping due to the supplementary...

Страница 3: ...00 001 FEATURES Unit Power supply V ph Hz 230 1 50 60 Cooling capacity EN14511 A35 A35 W 2000 2100 A35 A50 W 1200 1250 Absorbed electric power EN14511 A35 A35 W 1060 1100 A35 A50 W 1240 1300 Rated cur...

Страница 4: ...ed form power supply electrical data shown on rating label pasted on air conditioner side must be guaranteed Electrical enclosure must be sized according to air conditioner dimensions and weight Elect...

Страница 5: ...CONDITIONER FOR ELECTRICAL ENCLOSURE Page 5 16 UMA CDZ IP ACIWM200 001 00 2 3 FITTING 1 Make the fixing hole on the enclosure as is shown in the drilling template Deburr all sharp edges to avoid acci...

Страница 6: ...unscrewing included in mounting kit 5 Connect the condensate drain pipe like is shown in picture below Put some glue on aluminium pipe before to insert it Air conditioner produces condensate because...

Страница 7: ...Push the spring with a screwdriver and then insert the wire 2 Check the proper wire insertion 3 Connect the unit with the power supply Electrical data shown on rating label pasted on air conditioner...

Страница 8: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 8 16 UMA CDZ IP ACIWM200 001 00 3 1 WIRING DIAGRAM 3 1 1 IP ACIWM200 001...

Страница 9: ...lue hysteresis and the minimum interval of two successive switch on of the compressor parameter C2 is elapsed Compressor and condenser fan turn OFF when internal enclosure temperature decreases below...

Страница 10: ...00 display cabinet sensor 01 display evaporator sensor 0 U2 Switch between Fahrenheit and Celsius 3 00 Fahrenheit 01 Celsius 01 U3 Select defrost or light relay function 00 defrost out 01 light output...

Страница 11: ...o enter the current menu and set its parameters Use or to adjust parameter values then press Set again to return to menu selection status 5 Under any parameter setting status press or press no button...

Страница 12: ...o show shown if parameter U1 1 rH when temperature A6 and alarm delay time run out controller will display rH rL when temperature A5 and alarm delay time run out controller will display rL 5 SPARE PAR...

Страница 13: ...cooling circuit has been modified about type and quantity of refrigerant or composition 2 the unit operates in acid or corrosive ambient 3 the unit has been modified without IP ENCLOSURES consent This...

Страница 14: ...UE LOW VOLTAGE DIRECTIVE 26 February 2014 2014 30 UE EMC DIRECTIVE 26 February 2014 2011 65 UE ROHS DIRECTIVE 8 June 2011 STANDARDS APPLIED TO MEET THE PRINCIPAL ELEMENTS OF THE DIRECTIVE EN 60335 2...

Страница 15: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 15 16 UMA CDZ IP ACIWM200 001 00 SAA CERTIFICATE...

Страница 16: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 16 16 UMA CDZ IP ACIWM200 001 00 NOTES...

Отзывы: