Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE
Page 4/16
UMA-CDZ-IP-ACIWM200.001-00
2 - INSTALLATION
2.1 PRODUCT HANDLING
AIR CONDITIONER IP-ACIW series must be handled in upright
position and protected against accidental tipping over.
Air conditioners IP-ACIW series are fitted with female blind threaded insert to screw male
lifting eye bolts.
The air conditioner handling, when unpacked, can be done thanks to lifting eye bolt.
If lifting eye bolts are not included, please provide an adequate M6 male lifting eye bolt
(2)
and screw it inside blind threaded
(1)
insert placed on top of the air conditioner
Check the proper fixing of eye bolts before lift the air conditioner.
2.2 GENERAL CHECKS BEFORE INSTALLATION
Before the installation make sure that the cabinet is disconnected from the
electrical supply.
GENERAL CHECKS
- electrical enclosure must be disconnected form power supply
- electrical data shown on rating label pasted on air conditioner side must be
guaranteed
- Electrical enclosure must be sized according to air conditioner dimensions and
weight.
- Electrical enclosure must have at least IP54 protection degree
- Internal and external components of electrical enclosure don’t have to affect the
proper installation of air conditioner
- The installation site must be free from excessive dirt, aggressive ambient
conditions and moisture.
- The installation site must be free from hot air flows
- The internal side of electrical enclosure must be free from dirt and moisture
- The environment temperature must be within the range specified on label pasted
on air conditioner side
- Inside of electrical enclosure there must not be components that could affect the
proper ventilation
- the enclosure positioning with installed air conditioner must be carefully selected to
ensure good ventilation (clearance between the air conditioner and the near walls
must be at least 500 mm in each side).
- Proper disposing of condensate discharge