The inverter diagram depicts a typical AC installation. The main panel has an output breaker for the
non-inverter loads. It is used to power the high-power loads that are beyond the inverter’s capacity
such as a water heater or an electric stove. The AC input must be protected with a magnetic circuit
breaker rated at 50A or less, and the cable cross-section must be sized accordingly. Make all
connections using proper crimp-on connectors (do not use twist on connectors).
The inverter has a Power Assist feature and when enabled can add up to 2kVA (2000/120=17A) to
the output during periods of peak power requirement. With a maximum input current of 50A, the
inverter can supply up to 67A (50+17).