Main Diagram
LITHIONICS BATTERY, CLEARWATER, FL 33765 USA | PH: 727.726.4204 | FAX: 727.797.8046 | WEB: LITHIONICSBATTERY.com
The inverter is controlled by the Digital Multi Control Panel. The front mounted switch is used to turn the system on, off, or
to charger only operation. The shore current limit is set by the control knob. Turning the knob to the right or left sets the
desired value. The current limit is shown on the 7-segment display.
The Lithionics IonGage monitors battery voltage, current, power, amp-hours consumed and state of charge.
The Victron Smart Solar MPPT charger is connected to the MRBF fuse block via a 40A fuse and an isolation switch. The PV
solar array is connected to the MPPT charger via a circuit breaker. The specified circuit breaker is only rated at 48VDC; if
your PV solar array has an open circuit voltage that is higher, then another circuit breaker with a higher voltage rating must
be substituted. The fuse and wire sizes are based on the Victron Smart Solar MPPT 100/30 charge controller. If a larger
controller is used then the fuse and wire sizes should be increased as required.
The Sterling Battery to Battery charger is connected to the MRBF fuse block via a 50A fuse (80A for the BB1260
charger).There is also a fuse at the starter battery, this fuse must be installed as close to the battery as possible.