Inverter Diagram
LITHIONICS BATTERY, CLEARWATER, FL 33765 USA | PH: 727.726.4204 | FAX: 727.797.8046 | WEB: LITHIONICSBATTERY.com
8
A warning label should be installed at the main AC panel to indicate that there is an
inverter in the system.
An RCD (Residual Current Device) type circuit breaker rated to support the expected
load must be included in series with the output, and cable cross-section must be sized
accordingly. This breaker should be as close to the inverter as possible. If this breaker is
not of the RCD (Residual Current Device) type, GFCI receptacles must be used at all AC
outlets.
The inverter is provided with a ground relay that automatically connects the neutral
output to the chassis if no external AC supply is available. In an RV installation, the
inverter chassis must be connected the vehicle chassis ground (via the negative
distribution buss). The chassis grounding conductor must be not less than one size
smaller than the DC positive conductor and have a capacity such that the DC positive
fuse has an amperage rating not greater than 135% of the current rating of this
grounding wire. When using an inverter sub panel, the inverter neutrals must return
to the inverter sub panel and not the main AC panel.