Ion Technologies WC33

Submersible Sump Pump

OPERATION MANUAL

Dated: 04/09/2018

Document Name: WC33_OM

Page 3 of 8

www.ionproducts.net

Pump runs but delivers only small amount of 

water.

1.  Pump may be air locked. Start and stop several 

times by plugging and unplugging cord. Check 

vent hole in pump case for plugging.

2.  Pump head may be too high. Pump cannot 

deliver water over 24

'

  vertical  lift.  Horizontal 

distance does not affect pumping, except loss 

due to friction through discharge pipe.

3.  Inlet in pump base may be clogged. Remove 

pump and clean out openings.

4.  Impeller or volute openings may be plugged or 

partially plugged. Remove pump and clean out.

5.  Pump impeller may be partially clogged causing 

motor to run slow, resulting in motor overload. 

Clear impeller.

Fuse blows or circuit breaker trips when pump 

starts.

1.  Inlet in pump base may be clogged. Remove 

pump and clean out openings.

2.  Impeller or volute openings may be plugged or 

partially plugged. Remove pump and clean out.

3.  Pump impeller may be partially clogged causing 

motor to run slow, resulting in motor overload. 

Clear impeller.

4. 

Fuse size or circuit breaker is too small.

5. 

Defective  motor  stator;  return  to  authorized 

service center for verification.

Motor runs for short time then stops. Then after 

short period starts again. Indicates tripping 

overload caused by symptom shown.

1.  Inlet in pump base may be clogged. Remove 

pump and clean out openings.

2.  Impeller or volute openings may be plugged or 

partially plugged. Remove pump and clean out.

3.  Pump impeller may be partially clogged causing 

motor to run slow, resulting in motor overload. 

Clear impeller.

4. 

Defective  motor  stator;  return  to  authorized 

service center.

Dimensions

Installation Drawing

Performance

Head - feet

Capacity - US GPM

0

25

15

5

10

20

30

0

25

20

15

10

5

30

35

40

45

10”

3-5/8”

6-1/2”

9”

9-1/2”

9”

1-1/2”

Содержание WC33

Страница 1: ...This system is not intended for use in hazardous locations per NFPA 70 National Electric Code Do not pump flammable liquids Consult factory for optional equipment rated for hazardous location use WARN...

Страница 2: ...the floor and you must unplug the pump or make any adjustments Pump Servicing Note Automatic thermal overload protects the sealed in oil motor Running dry may overheat the motor and activate the over...

Страница 3: ...s 1 Inlet in pump base may be clogged Remove pump and clean out openings 2 Impeller or volute openings may be plugged or partially plugged Remove pump and clean out 3 Pump impeller may be partially cl...

Страница 4: ...6 or 8 5 depending on your switch s range to find the On level Please refer to the Installation Drawing CAUTION Bottom of switch should not be mounted lower than suction inlet of pump When installing...

Страница 5: ...ectrical codes WARNING Electrical outlet must not be located in pump pit For best performance do not use electrical extension cords INSTALLATION DRAWING Lowest pump off level BE SURE TO MOUNT THE ION...

Страница 6: ...the On level is at a point within the basin insuring that the Off level does not fall below the minimum level shown in the Installation Drawing ii If the On level is still too high the switch will ha...

Страница 7: ...OPERATION MANUAL Dated 04 09 2018 Document Name WC33_OM Page 7 of 8 www ionproducts net Ion Digital Level Control Digital Level Control Switch Notes Notes...

Страница 8: ...ect a defect in a product shall extend the Warranty beyond the period set forth above Metropolitan shall not be obligated to remedy any defect where otherwise required pursuant to the Warranty unless...

Отзывы: