Page 9

9.2

Data Printout

If readings were stored using the STORE key on the hand unit, these can be printed or
transferred to a computer. After printout, the data memory is cleared. See section 16.5
page 15 for ISL supplied printer settings and information.

9.3

Clear Data Memory

Use this function prior to beginning a new set of measurements to remove invalid data
from memory.

Exit

Press to return to normal screen display.

9.4

Open Supervisor Level

Please enter access code: You need password entry, this is factory set at 000.

Enter 000 (or new code) then keypad press

9.5

Set Alarm Level

Enter the alarm level for the leak rate you wish to alarm at. This level alerts the "ALARM"
LED in the handgun.

Only the alarm level corresponding to the chosen mode ml/sec or ppm can be entered.

Valid alarm levels are for (leak rates) 0.5 E-6 / 5 E-7 ml/s to 20 E-6 / 200 E-7 ml/s, and 5
to 1000 ppm (concentration). Values beyond these limits are rejected.

9.6

Operator ID mode

It may be useful to be able to identify the operator from the data printout, there are two
stages to ensure this:

10.0

Do not force operator ID

Selected this if no data printouts are to be made.

10.1

Force Operator ID by name

Select this only If data printout is to carry an operator’s name.

If selected, the operators name entry screen is opened after power on. The operator may
now enter his name or short code. If nothing is entered, i.e. the entry is terminated with
the edit line empty, the instrument will operate normally, but data printout is not possible.

Содержание GAS-CHECK SF6

Страница 1: ...INSTRUCTION MANUAL GAS CHECK SF6 AN INSTRUMENT FOR THE LOCATION AND MEASUREMENT OF LEAKS IN SF6 FILLED ELECTRICAL SWITCHGEAR User Manual iss 01 Software Version V1 39BB...

Страница 2: ...ion 6 7 3 Low flow error 7 7 4 Flare stall 7 7 3 Low battery voltage 7 7 5 Switching OFF 7 8 0 Switching OFF in case of fault 7 8 1 User setup 8 8 2 Set volume Contrast 8 9 0 Open Operator Level 8 9 1...

Страница 3: ...p after fuse has been removed 15 16 3 Pre set passwords on delivery 15 16 4 Settings on despatch 16 16 5 Citizen printer 16 16 6 Spares and consummables 16 3 0 GENERAL This manual is addressed to thos...

Страница 4: ...contain a microchip programmed with specific sensor information At Switch ON the console automatically reads sensor information Smart Sensors are not radioactive and contain nothing harmful Life is ap...

Страница 5: ...may confidently measure This is OFF whenever the instrument is in standby or programming mode error condition or the actual reading is above 20 of the alarm level Red 2 NOT READY This light is on whe...

Страница 6: ...used at any time During the short zero time the lights change from RED to GREEN Do not leak test during this time During normal use it is recommended to press the CIRCLE key occasionally to zero the d...

Страница 7: ...for you press Exit Should this not be the case please refer to paragraphs Possible Fault Conditions During Operation and Switching Off in Case of Fault in this manual 7 1 MEASURING OPERATION The GAS C...

Страница 8: ...entration of SF6 many times above the measuring range 2 High vacuum in the probe caused by a partially blocked or aged sensor The instrument will attempt to compensate for these until a level is reach...

Страница 9: ...the present value of a parameter will already be entered You may then confirm or delete and re enter 8 2 Set volume Contrast Using the three slider type controls on this screen select contrast for be...

Страница 10: ...vel alerts the ALARM LED in the handgun Only the alarm level corresponding to the chosen mode ml sec or ppm can be entered Valid alarm levels are for leak rates 0 5 E 6 5 E 7 ml s to 20 E 6 200 E 7 ml...

Страница 11: ...be assigned for 6 different operators please refer to Changing Passwords section 10 4 10 3 Access codes 10 4 CHANGING PASSWORDS Use one of the eight buttons to select the password you wish to change t...

Страница 12: ...Air is measured first which takes 4 seconds A time bar is displayed along with an audible bleep The display then instructs the operator to put the probe to the reference leak When this is done the fi...

Страница 13: ...when the STORE key is pressed Pressing either the STORE or CLEAR buttons resets this 12 3 Display units The touch screen display and alarm level entries as well as reference leak values will operate...

Страница 14: ...e following will occur The touch screen screen contrast sensor and sample flow regulation are switched off Vacuum is released Lifetime of all major components is saved If POWER DOWN is selected the in...

Страница 15: ...r operation The main function of the filter is to block out short wave noise Filter Count represents the number of measuring cycles over which the signal must be continuously above or below the averag...

Страница 16: ...ew sensor and sets these values in the console memory this may take 10 50 seconds 15 2 Changing the Probe To change the sensor You Must Power Down Never unplug the probe while the red lights on the co...

Страница 17: ...er set up ALL 4 SWITCHES MUST BE IN THE OFF POSITION Switch the printer ON using the side mounted slide switch The POWER and SEL green lights should be lit Press SEL to turn OFF the light and use LF t...

Отзывы: