36
Parameter 1 & Interface Display
Parameter 2 Description
Bypass Frequency Range Setting
Display: 8
Display: HS
Parameter 2: Acceptable high
frequency point and acceptable low
frequency point for Bypass mode.
Press the Up or Down key to adjust the
values
HLS:
Bypass high frequency point
For 50Hz output frequency models:
51-55Hz:
Setting the frequency high
loss point from 51Hz to 55Hz (Default:
53.0Hz)
For 60Hz output frequency models
61-65Hz:
Setting the frequency high
loss point from 61Hz to 65Hz (Default:
63.0Hz)
LLS:
Bypass low Frequency Point
For 50Hz output frequency models:
45-49Hz:
Setting the frequency low
loss point from 45Hz to 49Hz (Default:
47.0Hz)
For 60Hz output frequency models:
55-59Hz:
Setting the frequency low
loss point from 55Hz to 59Hz (Default:
57.0Hz)
Enable / Disable Programmable Outlets
Display: 9
Parameter 2: Enable or Disable
programmable outlets
ENA:
Enable Programmable outlets
DIS:
Disable Programmable Outlets
(Default)