10. "Validate the safety functions" on page 54.
6.2 Install and configure LBK System BUS
6.2.1 Install the controller
WARNING! To prevent tampering, make sure the controller is only accessible to authorized
personnel (e.g. key-locked electrical panel).
1. Mount the controller on the DIN rail.
2. Make electrical connections, see "Terminal blocks and connector pin-outs" on page 67 and "Electrical
NOTICE
: if at least one input is connected, the SNS input "V+ (SNS)" and the GND input "V- (SNS)" must
also be connected.
Note
: to correctly connect the digital inputs, see "Voltage and current limits for digital inputs" on page 67.
6.2.2 Define the working frequency of the sensors
1. Connect the controller to the computer via data micro-USB cable or Ethernet cable (see "Ethernet
2. Supply power to the controller.
3. Start the Inxpect Safety application.
4. Click
User
and enter the admin password.
Note
: if not yet set, set a valid password. Memorize the admin password and provide it only to people who are
authorized to change the configuration.
5. Click
Configuration
>
Settings
>
General
.
6. In
Operational frequency
if the system is installed in one of the countries with national restrictions, select
the restricted bandwidth, otherwise select the full bandwidth.
Note
: this setting does not have any effect on system performance or safety.
6.2.3 Define the area to be monitored
WARNING! LBK System BUS is disabled during configuration. Prepare opportune safety measures
in the dangerous area protected by the system before configuring the system.
1. In the Inxpect Safety application, click
Configuration
>
Sensor position
.
2. Add the desired number of sensors in the plane.
3. Define the position and inclination of each sensor.
4. Click
Configuration
>
Sensors Operation
.
5. For each detection field of each sensor define the selected safety working modes, the detection distance,
the field of view and the restart timeout.
6.2.4 Configure the inputs and outputs
1. In the Inxpect Safety application, click
Settings
.
2. Click
Digital Input-Output
and define the input and output functions.
3. If the muting is managed, click
Muting
and assign the sensors to the groups according to the logic of the
digital inputs.
4. Click
APPLY CHANGES
to save the configuration.
6. Installation and use procedures
LBK System BUS | Instruction manual v1.0 SEP 2020 | LBK-System-BUS_instructions_en v1.0 | © 2020 Inxpect SpA
49