GD310-UL series VFD
Basic operation instruction
-153-
Function
code
Name
Description
Default
value
P05.25 Switch-off delay of S6 terminal 0.000
–50.000s
0.000s
P05.26 Switch-on delay of S7 terminal 0.000
–50.000s
0.000s
P05.27 Switch-off delay of S7 terminal 0.000
–50.000s
0.000s
P05.28 Switch-on delay of S8 terminal 0.000
–50.000s
0.000s
P05.29 Switch-off delay of S8 terminal 0.000
–50.000s
0.000s
P05.30 Switch-on delay of HDI terminal 0.000
–50.000s
0.000s
P05.31 Switch-off delay of HDI terminal 0.000
–50.000s
0.000s
P07.39
Input terminals state at present
fault
0
P17.12
Digital input terminals state
0
7.12 Digital output
Goodrive310-UL series VFDs have 2 relay output terminals and 1 Y output terminal and 1 high speed
pulse output terminal in the standard configuration. All functions of the digital input terminals are
programmable by the function codes. Open collector pole input can be selected into high speed pulse
input terminal or common switch input terminal by function code.
0
1
2
3
4
5
.
.
.
.
29
30
P06.01
P06.03
P06.04
P06.02
T delay
T delay
T delay
T delay
0
1
P06.05
(default as 0)
(default as 0)
(default as 1)
(default as 5)
P06.00
0
1
0
1
0
1
Delay
0
1
-1
-1
-1
-1
P17.13
P07.40
Fault?
Fault
Run
Y
BIT0
HDO
BIT1
ROI
BIT2
RO2
BIT3
P06.05, P17.13, P07.40
P06.00
P06.07
P06.09
P06.11
P06.13
Y
RO2
ROI
HDO
Digital switch off delay time
Digital output
T delay
T delay
T delay
T delay
Delay
P06.06
P06.08
P06.10
P06.12
Digital switch on delay time
The table below describes the option of the four function parameters and selecting the repeated
output terminal function is allowed.
Set
value
Function
Instructions
0
Invalid
The output terminal has no function.
1
Running
Output ON signal when the VFD is running and there is frequency
output.
2
Forward running
Output ON signal when the VFD is running forward and there is
frequency output.
3
Reverse running
Output ON signal when the VFD is running reverse and there is
frequency output.