Goodrive300-01A series VFD for air compressor
Function description
-79-
Function
code
Name
Description
Default
Modify
P18.10
Setting
temperature
compressor runs stably, the fan speed is
controlled by thermostatic PID (
=0),
PID calculation is carried out via
the machine head temperature to realize
thermostatic control.
Setting range: -20
–150
75
℃
○
P18.11
Lower-limit
frequency at
load-carrying
running
frequency)
During regulating, if the pressure exceeds
the set working pressure but lower than the
unloading pressure, the allowed min.
working frequency is P18.11.
40.00Hz
○
P18.12
No-load running
frequency
load-carrying running)
The output working frequency allowed during
no-load of air compressor.
38.00 Hz
○
P18.13
No-load delay
When sleep function is valid, after unloading,
the VFD runs at no-load frequency in the
, and then enters sleep
state.
When air consumption quantity is small,
users can enable sleep function; if sleep
function is valid, it is necessary to lower
to make the device enter sleep
state quicker.
Setting range: 0
–3600s
300s
○
P18.14
Stopping delay
After the stopping command becomes valid,
the VFD will first run at no-load frequency in
the time set by
, and then stops.
Setting range: 0
–3600s
0s
○
P18.15
Loading delay
Loading operation is available only after the
motor runs at no-load frequency in the time
set by
Setting range: 0
–3600s
10s
○
P18.16
Restarting delay
After the system stops, it is necessary to wait
restart.
30s
○