Goodrive300-01A series VFD for air compressor
Function description
-35-
5 Function description
5.1 Function parameter list
"
○
" indicates that the value of the parameter can be modified when the VFD is in stopped or running
state.
"
◎
" indicates that the value of the parameter cannot be modified when the VFD is in running state.
"
●
" indicates that the value of the parameter is the actually detected value which cannot be modified.
(The VFD automatically checks and constrains the modification of parameters, which helps prevent
incorrect modifications.)
P00 group Basic functions
Function
code
Name
Description
Default
Modify
P00.00
Speed control
mode
0: SVC mode 0 (applicable to AM, SM)
1: SVC mode 1(applicable to AM)
2: V/F control
Note:
AM: Asynchronous Motor;
SM: Synchronous Motor;
If vector mode is adopted, it is a must to carry
out motor parameter autotuning on the VFD
first.
0
◎
P00.01
Channel of
running
commands
0: Keypad (LED off)
1: Terminal (LED blinks)
2: Communication (LED on)
0
○
P00.02
Communication
mode of
running
commands
0: Modbus communication
1
–3: Reserved
0
○
P00.03
Max. output
frequency
–400.00Hz
50.00Hz
◎
P00.04
Upper limit of
running
frequency
50.00Hz
○
P00.05
Lower limit of
running
frequency
0.00Hz
frequency)
0.00Hz
○