Function
code
Name
Description
Default
Modify
P01.09
Starting frequency
of DC braking for
stop
0.00
–P00.03 (max. output frequency)
0.00Hz
○
P01.10
Wait time before DC
braking for stop
0.00
–50.00s
0.00s
○
P01.11
DC braking current
for stop
0.0
–150.0%
0.0%
○
P01.12
DC braking time for
stop
0.00
–50.00s
0.00s
○
P01.13
FWD/REV running
deadzone time
0.0
–3600.0s
0.0s
○
P01.14
FWD/REV running
switching mode
0: Switch at zero frequency
1: Switch at the starting frequency
2: Switch after the speed reaches the stop
speed with a delay
0
◎
P01.15
Stop speed
0.00
–100.00Hz
5.00Hz
◎
P01.16
Stop speed
detection mode
0: Detect as per the set speed value (judge
the ramps frequency)
1: Detect as per the speed feedback value
(valid for vector control only)
1
◎
P01.17
Feedback speed
detection time
0.00
–100.00s (valid only when P01.16=1)
0.50s
◎
P01.18
Terminal-based
running command
protection at
power-on
0: The terminal running command is invalid
at power-on
1: The terminal running command is valid at
power-on
0
○
P01.19
Action selected
when running
frequency less than
frequency lower
limit (valid when
frequency lower
limit greater than 0)
0: Run at the frequency lower limit
1: Stop
2: Sleep
0
◎
P01.20
Wake-up-from-sleep
delay
0.0
–3600.0s (valid when P01.14=2)
0.0s
○
P01.21
Power-off restart
selection
0: Disable
1: Enable
0
○