SHENZHEN INVT ELECTRIC CO., LTD. CHV160 Operation Manual
56
corresponding setting
P5.19
AI1 input filtering time
0.00s
10.00s
0.00
10.00
0.10s
Above function codes define the relationship between analog input voltage and the setting
value that analog input is corresponding to. When the analog input voltage exceeds the range
of the set maximum or minimum input, the beyond portion should be calculated with maximum
input or minimum input.
When analog input is amperage input, 0mA-20mA is corresponding to 0V-10V.
For different applications, the corresponding nominal value of analog setting 100.0% is
different. For details, please refer to each application description.
Following figures shows several settings. Note: AI1 lower limit must be less or equal to AI1
upper limit.
Figure 6-12 Relationship between analog input and setting value
AI1 input filtering time determines analog input sensitiveness. Increasing this parameter, in
order to prevent malfunction caused by interference to the analog, can strengthen the
anti-interference ability, but reduce the analog input sensitiveness.
Function
Code
Name
Description
setting range
Default
Value
P5.20
AI2 lower limit
0.00V
10.00V
0.00
10.00
0.00V
P5.21
AI2 lower limit
corresponding setting
-100.0%
100.0% -100.0
100.0
0.0%
P5.22
AI2 upper limit
0.00V
10.00V
0.00
10.00
10.00V
P5.23
AI2 upper limit
corresponding setting
-100.0%
100.0% -100.0
100.0 100.0%
P5.24
AI2 input filtering time
0.00s
10.00s
0.00
10.00
0.10s
P5.25
AI3 lower limit
-10.00V
10.00V -10.00
10.00
0.00V
P5.26
AI3 lower limit
corresponding setting
-100.0%
100.0% -100.0
100.0
0.0%
P5.27
AI3 upper limit
-10.00V
10.00V -10.00
10.00 10.00V
P5.28
AI3 upper limit
corresponding setting
-100.0%
100.0% -100.0
100.0 100.0%
P5.29
AI3 input filtering time
0.00s
10.00s
0.00
10.00
0.10s
P5.30
AI4 lower limit
0.00V
10.00V
0.00
10.00
0.00V
P5.31
AI4 lower limit
corresponding setting
-100.0%
100.0% -100.0
100.0
0.0%
P5.32
AI4 upper limit
0.00V
10.00V
0.00
10.00
10.00V