![INVT BD100KTR-P Скачать руководство пользователя страница 47](http://html1.mh-extra.com/html/invt/bd100ktr-p/bd100ktr-p_manual_2085726047.webp)
46
Whether the power grid is connected correctly and powered on
Check whether the communication of measuring equipment is normal
9.3.2 Non-Alarm Inducing Failure
Machine working noise is high
Check whether the power is in the normal range; Measure whether the grid-connected
current and voltage waveforms are normal; Check the replacement of cooling fans.
Network communication mode:
Please check whether the IP address, subnet mask and gateway are set correctly.
Check whether the communication line is through and whether it is well connected.
If all the above tests are normal and correct, try to replace the LCD monitoring board.
Serial communication mode:
Check the wiring, check all wiring is good, A/B has no connection.
Communication adapter does not match. Replace communication adapter and try
again.
Check whether the local address and baud rate are consistent with the host computer.
LCD screen cannot be switched on and off
Check the communication connection between LCD screen and DSP board
9.3.3 Alarm Failure List
LCD can display 32 alarms, and the corresponding solutions are shown in Table 9-2 below.
Table 9-2 Alarm Fault Handling Method
Fault Type
Processing Method
Low battery voltage
Disconnect DC load switch and check DC side voltage and battery
configuration
Battery Voltage Low Auxiliary
Power Supply
Disconnect DC load switch and check DC side voltage and battery
configuration
Low battery power
Disconnect DC circuit breaker load switch and check energy storage
battery status
Battery
Back
Connection
Failure
Switch-off DC-side input bus
Busbar Overvoltage Fault
Turn off to check DC side voltage
Bus Short Circuit Fault
Turn off and check DC bus connection
Overvoltage
of
power Check the voltage of grid connection point by shutdown