In the manufacture of channel anchors, it is necessary to design the positioning hole with
the base at the bottom of the inverter. The bottom section of each model is shown in the
following figures (mm). Cooling air can enter from the front and bottom, and cables from
the bottom. In front of the inverter, there are DC and AC inlet and outlet holes.
5.6 Design And Installation Of Air Ducts
5.5.1 Forced Air Cooling System
This series energy storage inverters use forced air cooling for heat dissipation, and need to
maintain adequate air intake.
5.5.2 Ventilation Environment
In order to meet the ventilation requirements of this series inverters, the installation
environment should meet the following requirements:
Inverter should avoid installing in the situation of poor ventilation condition and low
air flow. It can get more ventilation by increasing construction measures such as air
supply grille or fan.
Sufficient air intake should be provided at the intake port.
Air quality must be guaranteed. If the content of suspended solids such as sand and
dust in the air is too high, the air quality can meet the requirements through
construction measures (such as installing filters at the air supply grille of the building).
5.5.3 Air Duct Setting
In order to ensure pressure balance, an additional fan can be added at the outlet of the
outlet pipe to exhaust the air. The size of ventilation duct should be designed by
professionals according to the size of air output. When designing and installing, it is nece
ssary to prevent the phenomenon of backfilling air in the inverter cabinets.
Fig. 5-5 Base mounting and fixing
External duct rain
shield
≥1000mm
Cover
plate
Embedded 10# Channel Steel
Cabinet Base Fixed with Channel
Steel
Internal Ventilation
Hose