Goodrive600 series high-performance multifunction VFD
Basic operation guidelines
-83-
Function
code
Name
Description
Default
P00.08
Reference object of B
frequency command
0: Max. output frequency
1: A frequency command
0
P00.09
Combination mode of setting
source
0: A
1: B
2: (A+B)
3: (A- B)
4: Max(A, B)
5: Min. (A, B)
0
P05.01
–
P05.04
Multifunction digital input
terminal (S1
–S4) function
selection
10: Increase frequency setting (UP)
11: Decrease frequency setting (DOWN)
12: Clear the frequency increase/decrease
setting
13: Switch between A setting and B setting
14: Switch between combination setting and
A setting
15: Switch between combination setting and
B setting
/
P08.44
UP/DOWN terminal control
setting
0x000
–0x221
Ones place: Frequency setting selection
0: The setting made through UP/DOWN is
valid.
1: The setting made through UP/DOWN is
invalid.
Ones place: Frequency control selection
0: Valid only when P00.06=0 or P00.07=0
1: Valid for all frequency setting methods
2: Invalid for multi-step speed running when
multi-step speed running has the priority
Hundreds place: Action selection for stop
0: Setting is valid.
1: Valid during running, cleared after stop
2: Valid during running, cleared after a stop
command is received
0x000
P08.45
Frequency increment change
rate of the UP terminal
0.01
–50.00 Hz/s
0.50 Hz/s
P08.46
Frequency reduce rate of the
DOWN terminal
0.01
–50.00 Hz/s
0.50 Hz/s
P17.00
Set frequency
0.00Hz
–P00.03 (Max. output frequency)
0.00Hz
P17.02
Ramp reference frequency
0.00Hz
–P00.03 (Max. output frequency)
0.00Hz
P17.14
Digital adjustment value
0.00Hz
–P00.03
0.00Hz
5.6.9 Analog input
The inverter unit carries two analog input terminals, in which AI1 is 0(2)
–10V/0(4)–20mA and whether AI1 uses voltage
input or current input can be set by P05.50, and AI2 is -10
–10V. Each input can be filtered separately, and the
corresponding reference curve can be set by adjusting the reference corresponds to the max. value and min. value.