9.2 Diagnosis and Solution
9.2.1 E0(EEPROM parameter error) error diagnosis and solution
Circuit or software error on indoor PCB
Replace indoor PCB
9.2.2 E1(indoor / outdoor units communication protection) error diagnosis and solution
Disconnect the power supply, after 1 minute,
connect the power supply, turn on the unit with
remote controller
Does the unit work normally?
Check the wiring between
indoor and outdoor unit. Is
the connection of L, N, S and
GND good?
Is the GND connection on
outdoor PCB good?
NO
NO
Reconnect and retest again
Is the LED4 (red) on
outdoor PCB bright and
LED1(yellow) blinking?
Replace outdoor e-box.
Yes
Yes
The power supply for
outdoor PCB is fail. Check
the wiring on outdoor PCB
comparing with wiring plate.
Is the connection good?
No
Correct the connection.
Yes
No
Replace indoor PCB
and repower on. Is
the failure cleared?
9.2.3 E5(Open or short circuit of outdoor temperature sensor) diagnosis and solution.
Is the outdoor temperature
sensor connector and
connection good?
9.2.4 E6(open or short circuit of room or evaporator temperature sensor) diagnosis and solution.
Repair the connector and
reconnect
NO
YES
Replace the sensor and
check if E5 display again?
Replace outdoor e-box
YES
Содержание MSC-24/QD FP
Страница 8: ...6 3 Dimension 3 1 Indoor Unit MSC 24 QD FP MSH 24 QD FP...
Страница 9: ...7 3 2 Outdoor Unit MSC 24 QD FP...
Страница 11: ...9 5 Refrigerant cycle diagram...
Страница 12: ...10 6 Wiring diagram 6 1 Indoor Unit MSC 24 QD FP MSH 24 QD FP...
Страница 13: ...11 6 2 Outdoor Unit MSC 24 QD FP...
Страница 37: ...35...