background image

Information for UL Compliance

Optidrive E3 is designed to meet the UL requirements. For an up to date list of UL compliant products, please refer to UL listing 

NMMS.E226333. In order to ensure full compliance, the following must be fully observed.

Input Power Supply Requirements

Supply Voltage

200 – 240 RMS Volts for 230 Volt rated units, + /- 10% variation allowed. 240 Volt RMS Maximum.
380 – 480 Volts for 400 Volt rated units, + / - 10% variation allowed, Maximum 500 Volts RMS.

Frequency

50 – 60Hz + / - 5% Variation

Short Circuit 

Capacity

All drives are suitable for use on a circuit capable of delivering not more than 100kA maximum short-

circuit Amperes symmetrical with the specified maximum supply voltage when protected by Class J fuses.

Mechanical Installation Requirements

All Optidrive E3 units are intended for installation within controlled environments which meet the condition limits shown in the 

Environment section of this Quick Start Guide.
The drive can be operated within an ambient temperature range as stated in the Environment section of this Quick Start Guide.
For IP66 (Nema 4X) units, installation in a pollution degree 2 environment is permissible.

Electrical Installation Requirements

Incoming power supply connection must be according to the Install the Wiring section of this Quick Start Guide.
Suitable power and motor cables should be selected according to the data shown in Rating Tables section of this Quick 

Start Guide and the National Electrical Code or other applicable local codes.
Motor Cable

75°C Copper must be used.

Power cable connections and tightening torques are shown in the Mechanical Dimensions section of this Quick Start Guide.
Integral Solid Sate short circuit protection does not provide branch circuit protection. Branch circuit protection must be 

provided in accordance with the national electrical code and any additional local codes. Ratings are shown in the Rating 

Tables section of this Quick Start Guide.
For Canadian installations transient surge suppression must be installed on the line side of this equipment and shall be rated 

480Volt (phase to ground), 480 Volt (phase to phase), suitable for over voltage category iii and shall provide protection for 

a rated impulse withstand voltage peak of 2.5kV.
UL Listed ring terminals / lugs must be used for all bus bar and grounding connections.

General Requirements

Optidrive E3 provides motor overload protection, set at 150% of full load, in accordance with the National Electrical Code (US).
Where a motor thermistor is not fitted, or not utilised, Thermal Overload Memory Retention must be enabled by setting P-60 = 1.
Where a motor thermistor is fitted and connected to the drive, connection must be carried out according to the information 

shown in the Motor Thermistor Connection section of the Quick Start Guide.
UL rated ingress protection (“Type” ) is only met when cables are installed using a UL recognized bushing or fitting for a 

flexible conduit system which meets the required level of protection (“Type”).
For conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC.
Not intended for installation using rigid conduit system.

WARNING:

 The opening of the branch-circuit protective device may be an indication that a fault has been interrupted. To reduce 

the risk of fire or electric shock, current-carrying parts and other components of the controller should be examined and replaced if 

damaged. If burnout of the current element of an overload relay occurs, the complete overload relay must be replaced.

Control Terminal Wiring

 

 

All analog signal cables should be suitably shielded. 

Twisted pair cables are recommended.

 

 

Power and Control Signal cables should be routed 

separately where possible, and must not be routed parallel 

to each other.

 

 

Signal levels of different voltages e.g. 24 Volt DC and 110 

Volt AC, should not be routed in the same cable.

 

 

Maximum control terminal tightening torque is 0.5Nm.

 

 

Control Cable entry conductor size: 0.05 – 2.5mm2 /  

30 – 12 AWG.

Control Terminal Connections

Switched Units:

 May use the built in control switch and 

potentiometer, or external control signals connected to the 

control terminals.

Non-Switched Units:

 Require external control signals to 

be connected to the control terminals.

Содержание OPTIDRIVE E3 Series

Страница 1: ...Quick Start Guide AC Variable Speed Drive IP66 NEMA 4X 0 37kW 22kW 0 5HP 30HP 1 10V 230V Single Phase input 230V 480V 3 Phase input Switched Non switched...

Страница 2: ...rrent x 10 2 PREPARE Prepare the Mounting Location The Optidrive must be mounted in a vertical position only Installation should be on a suitable flat flame resistant surface Do not mount flammable ma...

Страница 3: ...0 0 1 1 8 33 4 1 31 275 0 10 82 240 0 9 44 4 9 5 20 9 Mounting Clearance Drive Size X Above Below Y Either Side mm in mm in All Frame Sizes 200 7 87 10 0 39 NOTE Typical drive heat losses are approxim...

Страница 4: ...regulations Maximum dimensions are given in the Rating Tables section of this Quick Start Guide Install the Wiring L1 L L3 EMC Gland plate can be removed for installation L2 N U V W 1 2 3 4 5 6 7 8 9...

Страница 5: ...e side of this equipment and shall be rated 480Volt phase to ground 480 Volt phase to phase suitable for over voltage category iii and shall provide protection for a rated impulse withstand voltage pe...

Страница 6: ...ommon 10 RL1 Output Relay Function defined by P 18 See Parameter List 1 1 RL2 Output Relay Connection Example Factory Default Functions No Description DI1 0 1 Open Stop Closed Run DI2 Open Forward Rot...

Страница 7: ...ress the Navigate key for 1 second The display will show the motor power kW If P 10 0 pressing the Navigate key for 1 second will display the motor speed RPM Changing Parameters Press and hold the Nav...

Страница 8: ...7 Motor Rated Voltage Back EMF at rated speed PM BLDC 0 250 500 230 400 V P 08 Motor Rated Current Drive Rating Dependent A P 09 Motor Rated Frequency 10 500 50 60 Hz P 10 Motor Rated Speed 0 30000 0...

Страница 9: ...00 s P 25 Analog Output Function Select 0 11 8 Digital Output Mode Logic 1 24V DC Analog Output Mode 0 Drive Enabled Running 1 Drive Healthy 2 At Target Frequency Speed 3 Drive Tripped 4 Output Freque...

Страница 10: ...0 10 Unidirectional External 0 10Volt reference pot A 0 20 External 0 20mA signal t 4 20 External 4 20mA signal trip on loss r 4 20 External 4 20mA signal t 20 4 External 20 4mA signal trip on loss r...

Страница 11: ...9 2 25 25 8 8 10 5 50 3 4 5 29 2 40 40 8 8 15 3 25 200 240 10 V 3 Phase Input 3 Phase Output 1 0 37 0 5 3 4 6 6 8 8 2 3 1 0 75 1 5 6 10 10 8 8 4 3 1 1 5 2 8 9 16 15 8 8 7 2 1 5 2 8 9 16 15 8 8 7 100 2...

Страница 12: ...heatsink 17 Internal memory fault IO 18 4 20mA Signal Lost 19 Internal memory fault DSP 21 Motor PTC thermistor trip 22 Cooling Fan Fault IP66 only 23 Drive internal temperature too high 26 Output Fau...

Отзывы: