Invertek Drives OPTIDRIVE E3 Series Скачать руководство пользователя страница 3

3   MOUNT

Mechanical Dimensions

Dimensions 

       

 

 

Weight

Drive  

Size

A

D

E

F

G

Drive  

Size

Weight

mm

in

mm

in

mm

in

mm

in

mm

in

kg

Ib

1

232.0

9.13

189.0

7.44

25.0

0.98

162.0

6.37

161.0

6.34

1

2.5

5.5

2

257.0

10.12

200.0

7.87

28.5

1.12

182.0

7.16

188.0

7.40

2

3.5

7.7

3

310.0

12.20

251.5

9.90

33.4

1.31

238.0

9.37

211.0

8.30

3

7.0

15.4

4

360.0

14.17

300.0

11.8

33.4

1.31

275.0

10.82 240.0

9.44

4

9.5

20.9

Mounting Clearance

Drive Size

X Above & Below

Y Either Side

mm

in

mm

in

All Frame Sizes

200

7.87

10

0.39

NOTE

Typical drive heat losses are approximately 3% of operating load conditions. Above are guidelines only 

and the operating ambient temperature of the drive MUST be maintained at all times.

Mounting Bolts & Tightening Torques

Mounting Bolts

Tightening Torques

Frame Size

Frame Size

Control Terminals

Power Terminals

All Frame Sizes

4 x M4 (#8)

All Frame Sizes

0.8 Nm (7 lb-in)

1.5 Nm (13 lb-in)

Содержание OPTIDRIVE E3 Series

Страница 1: ...Quick Start Guide AC Variable Speed Drive IP66 NEMA 4X 0 37kW 22kW 0 5HP 30HP 1 10V 230V Single Phase input 230V 480V 3 Phase input Switched Non switched...

Страница 2: ...rrent x 10 2 PREPARE Prepare the Mounting Location The Optidrive must be mounted in a vertical position only Installation should be on a suitable flat flame resistant surface Do not mount flammable ma...

Страница 3: ...0 0 1 1 8 33 4 1 31 275 0 10 82 240 0 9 44 4 9 5 20 9 Mounting Clearance Drive Size X Above Below Y Either Side mm in mm in All Frame Sizes 200 7 87 10 0 39 NOTE Typical drive heat losses are approxim...

Страница 4: ...regulations Maximum dimensions are given in the Rating Tables section of this Quick Start Guide Install the Wiring L1 L L3 EMC Gland plate can be removed for installation L2 N U V W 1 2 3 4 5 6 7 8 9...

Страница 5: ...e side of this equipment and shall be rated 480Volt phase to ground 480 Volt phase to phase suitable for over voltage category iii and shall provide protection for a rated impulse withstand voltage pe...

Страница 6: ...ommon 10 RL1 Output Relay Function defined by P 18 See Parameter List 1 1 RL2 Output Relay Connection Example Factory Default Functions No Description DI1 0 1 Open Stop Closed Run DI2 Open Forward Rot...

Страница 7: ...ress the Navigate key for 1 second The display will show the motor power kW If P 10 0 pressing the Navigate key for 1 second will display the motor speed RPM Changing Parameters Press and hold the Nav...

Страница 8: ...7 Motor Rated Voltage Back EMF at rated speed PM BLDC 0 250 500 230 400 V P 08 Motor Rated Current Drive Rating Dependent A P 09 Motor Rated Frequency 10 500 50 60 Hz P 10 Motor Rated Speed 0 30000 0...

Страница 9: ...00 s P 25 Analog Output Function Select 0 11 8 Digital Output Mode Logic 1 24V DC Analog Output Mode 0 Drive Enabled Running 1 Drive Healthy 2 At Target Frequency Speed 3 Drive Tripped 4 Output Freque...

Страница 10: ...0 10 Unidirectional External 0 10Volt reference pot A 0 20 External 0 20mA signal t 4 20 External 4 20mA signal trip on loss r 4 20 External 4 20mA signal t 20 4 External 20 4mA signal trip on loss r...

Страница 11: ...9 2 25 25 8 8 10 5 50 3 4 5 29 2 40 40 8 8 15 3 25 200 240 10 V 3 Phase Input 3 Phase Output 1 0 37 0 5 3 4 6 6 8 8 2 3 1 0 75 1 5 6 10 10 8 8 4 3 1 1 5 2 8 9 16 15 8 8 7 2 1 5 2 8 9 16 15 8 8 7 100 2...

Страница 12: ...heatsink 17 Internal memory fault IO 18 4 20mA Signal Lost 19 Internal memory fault DSP 21 Motor PTC thermistor trip 22 Cooling Fan Fault IP66 only 23 Drive internal temperature too high 26 Output Fau...