Invertek Drives eco OPTIDRIVE Скачать руководство пользователя страница 17

Optidrive Eco Advanced User Guide Revision 1.00 

Opt

idr

ive 

Eco 

Par

am

e

te

Set Ov

er

vi

ew

 

1

 

Par. 

Name 

Minimum 

Maximum 

Default 

Units 

P6-28 

P0-80 Display Value Index 

200 

This parameter defines the index of the internal variable, the value of which will be displayed in P0-80.   
This is usually used in conjunction with the Function Block Program. Refer to section 1.6 for further information. 

P6-29 

Save User Parameters as Default 

0 : No Function 
1 : Save Parameters. 
Setting this parameter to 1 saves the present drive parameter settings to the User Default Parameters Memory.  
Following this, if the User carries out a 3-button default parameter command (UP, DOWN and STOP), the parameter saved at this time 
will be restored. 
2 : Erase Parameters. Setting 2 clears the User Default Parameters Memory.  

P6-30 

Advanced Parameter Access Code Definition 

9999 

201 

Defines the access code which must be entered into P1-14 to allow access to the Advanced Parameters. 

1.3.7.

 

Parameter Group 7 – Motor Data 

 

The following parameters are used internally by the drive to provide optimum possible motor control. Incorrect setting of the 
parameters can result in poor performance and unexpected behaviour of the motor. Adjustments should only be carried out by 
experienced users who fully understand the functions of the parameters. 

Par. 

Name 

Minimum 

Maximum 

Default 

Units 

P7-01 

Motor Stator Resistance (Rs) 

Ohms 

Motor stator resistance value measured during the autotune. 

P7-03 

Motor Stator Inductance (Lsd) 

For induction motors: phase stator inductance value.  
For permanent magnet motors: phase d-axis stator inductance in Henry (H). 

P7-04 

Motor Magnetising Current (Id rms) 

0.0 

For induction motors: magnetizing / no load current. Before Auto-tune, this value is approximated to 60% of motor rated current (P1-
08), assuming a motor power factor of 0.8. 

P7-05 

Motor Leakage Coefficient (Sigma) 

For induction motors: motor leakage inductance coefficient 

P7-06 

Motor Stator Inductance : PM Motors (Lsq) 

For permanent magnet motors: phase d-axis stator inductance in Henry (H).

 

P7-09 

Over Voltage Current Limit 

0.0 

100.0 

5.0 

Effective in vector speed control mode only, and will come into function once the drive DC bus voltage increases above a preset limit. 
This voltage limit is set internally just below the over voltage trip level. This parameter will effectively limit the output torque current 
in order to prevent a large current flowing back to the drive, which may cause an Over-voltage trip. A small value in this parameter will 
limit the motor control torque when the drive DC bus voltage exceeds the preset limit. A higher value may cause a significant 
distortion in the motor current, which may cause an aggressive, rough motor behaviour. 

P7-10 

System Inertia Constant 

600 

10 

System Load Inertia to Motor Inertia Ratio entered as H = (JTot / JMot). This value can normally be left at the default value (10) and is 
used by the drive control algorithms as a feed-forward control variable to provide optimum torque current to accelerate the load. 
Hence accurate setting of the inertia ratio will produce a better system response and dynamic behaviour. 

P7-11 

Pulse Width Minimum Limit 

500 

This parameter is used to limit the minimum output pulse width, which can be used for long motor cable applications. Increasing the 
value of this parameter will reduce the risk of over-current trips, but will also reduce the maximum available output motor voltage. 

P7-12 

Magnetising Period 

5000 

ms 

Defines the delay time between the output stage enabling at 0.0Hz prior to the output frequency beginning to ramp to accelerate the 
motor. This allows time for the motor to correctly magnetise, and avoids possible over current trips that may occur if the output 
frequency begins to ramp before the motor flux has stabilised. 

P7-14 

Low Frequency Torque Boost 

0.0 

100.0 

0.0 

Effective in all motor control modes, except V/F mode (P4-01 = 2), but primarily intended for use with synchronous motors. 
Allows a boost current to be applied at start-up and low frequency (limit defined by P7-15), as a percentage of the motor rated current 
(P1-08). Injecting some additional current into the motor at low speed helps to ensure that the rotor alignment is maintained, 
imrpoving operation of the motor at lower speeds.  
In order to determine the correct setting, run the drive at the lowest frequency required by the application and increase boost levels 
to provide both required torque and smooth operation whilst avoiding excessive current levels which may cause nuisance tripping. 

P7-15 

Torque Boost Frequency Limit 

0.0 

50.0 

0.0 

Frequency range for applied boost current (P7-14) as a % of motor rated frequency (P1-09). This sets the frequency cut-off point above 
which boost current is no longer applied to the motor. 
 

P7-18 

Over Modulation Enable 

0: Disabled 
1 : Enabled.
 When enabled, over modulation provides a small increase in the available output voltage from the drive, which can assist 
in applications where the supply voltage is too low to provide the required motor voltage, resulting in an increased motor current. 

P7-19 

BLDC Light Load Optimisation 

0: Disabled 
1 : Enabled.
 When enabled and the drive is set in BLDC Mode (P4-01 = 4), the drive will reduce the output voltage during loght load 
operation in order to improve motor efficiency and performance.  This setting has no effect when the motor is significantly loaded. 

 
 

 

Содержание eco OPTIDRIVE

Страница 1: ...Optidrive Eco Advanced User Guide Revision 1 00 Optidrive Eco Parameter Set Overview 1 AC Variable Speed Drive 0 75kW 250kW 1HP 350HP 200 480 Volt 1 3 Phase Advanced User Guide Revision 1 00...

Страница 2: ...e time of release This user guide must be read in conjunction with the Optidrive Eco User Guide included with each product and in particular all relevant safety information and warnings The informatio...

Страница 3: ...5 Parameter Group 0 Monitoring Parameters Read Only 25 1 6 P6 28 Value Selection 29 2 Diagnostic and Fault Messages 30 3 Immunity Tests 31 3 1 Electrostatic Discharge ESD 31 3 2 Electrical Fast Trans...

Страница 4: ...c Read Write Group 2 P2 01 to P2 40 Extended Parameters Extended Read Write Group 3 P3 01 to P3 18 PID Controller Extended Read Write Group 4 P4 01 to P4 14 Motor Control Extended Read Write Group 5 P...

Страница 5: ...d nameplate voltage of the motor Volts The factory default setting of this parameter is drive model dependent as follows All kW HP models intended for 200 240 volt operation e g ODV 3 x2xxx xxF1x xN F...

Страница 6: ...from the fieldbus option module interface 5 Slave Mode The drive acts as a Slave to a connected Optidrive operating in Master Mode 6 BACnet MSTP Control Control via BACnet bus connected to the RJ45 s...

Страница 7: ...requency reference applied to the drive is within the band the Optidrive output frequency will remain at the upper or lower limit of the band P2 11 Analog Output 1 Terminal 8 Function Select 0 12 8 Di...

Страница 8: ...ve and no fault exists 2 At Target Frequency Speed Logic 1 when the output frequency matches the setpoint frequency Hysterisis is applied defined by P6 04 3 Output Frequency 0 0 Hz Logic 1 when the dr...

Страница 9: ...rror Limit Logic 1 when the PID Error exceeds the adjustable threshold 15 High or Low load detected Logic 1 when the output current falls outside of the load monitoring profile See P8 06 to P8 08 P2 1...

Страница 10: ...e signal level falls below 3mA 4 to 20mA Signal In the event that the signal falls below 3mA the Optidrive will ramp operate at Preset Speed 4 20 to 4mA Signal the Optidrive will trip and show the fau...

Страница 11: ...Speed 4 P2 04 4 Minimum Speed Terminal Start Following a stop and restart the drive will always initially run at the minimum speed P1 02 The drive starting is controlled from the digital inputs based...

Страница 12: ...applied to the Analog Input 1 P3 10 PID Feedback Signal Source Select 0 5 0 0 Analog Input 2 1 Analog Input 1 2 Motor Current The feedback value is scaled such that 100 0 P1 08 3 DC bus voltage The fe...

Страница 13: ...gain value for the speed controller when operating in Vector Speed or Vector Torque motor control modes P4 01 0 or 1 Higher values provide better output frequency regulation and response Too high a va...

Страница 14: ...put 1 status bit 1 indicates digital input 2 status etc 3 Analog Input 2 Signal Level 0 to 1000 0 to 100 0 4 Drive Heatsink Temperature 0 to 100 0 to 100 C 5 User Register 1 6 User Register 2 7 P0 80...

Страница 15: ...s option to be used P9 38 must be set to 1 and the PID User setpoint must not be utilised within any Function Block Code 2 User register 3 The value received by the drive in PDI 3 is transferred to Us...

Страница 16: ...d into the drive to operate When set to 0 the Function Block Program will be disabled P6 11 Speed Holding Time on Enable 0 250 0 s Defines a time period for which the drive will run at Preset Speed 7...

Страница 17: ...A higher value may cause a significant distortion in the motor current which may cause an aggressive rough motor behaviour P7 10 System Inertia Constant 0 600 10 System Load Inertia to Motor Inertia...

Страница 18: ...arameter enables the Load Profile Monitoring Function load current monitoring which can be used to detect belt failure in belt driven fan applications or Dry Pump Pump Blockage or broken impeller in P...

Страница 19: ...mber of assist pumps P8 14 1 or network slave drives P8 14 2 that are available in the Pump Staging application Setting the value to 0 disables Pump Staging P8 16 Pump Duty Switch Over Time 0 1000 0 H...

Страница 20: ...ng on their state Parameters defined as logic sources have the following range of possible settings No Drive LED Display Drive OLED Display Function 0 Off Safe Function permanently disabled or where a...

Страница 21: ...n Forward or Run Reverse commands are applied from external sources e g Fieldbus control signals or a Function Block Program Logic 1 Drive operation is allowed Logic 0 Drive stops using deceleration r...

Страница 22: ...d restart P9 18 Speed Reference Select Bit 0 Logic Source P9 19 Speed Reference Select Bit 1 Logic Source P9 20 Speed Reference Select Bit 2 Logic Source Note The active speed setpoint source can be s...

Страница 23: ...n Module Drive Tripped Relay 5 Cascade Option Module Drive Running 1 Relay Output 1 Function set by User Defined Source P9 42 Clean Trigger Input Edge Trigger 0 25 0 This parameter defines the source...

Страница 24: ...for various internal protection and monitoring functions P0 17 Stator Resistance Rs Ohms Displays the measured motor stator resistance providing an auto tune has been successfully completed P0 19 Casc...

Страница 25: ...ay shows user resettable time reset with P6 22 Second display shows none resettable time This is used for scheduled maintenance information P0 36 DC Bus Voltage Log 256ms Volts Diagnostic log for DC b...

Страница 26: ...alue in use for output relay settings that use hysteresis defined by P6 04 P0 62 Fire Mode Total Acitvation Counter Specifies the total number of times that Fire Mode has been activated on the drive P...

Страница 27: ...ltage Volts Displays the supply voltage measured between L2 and L3 terminals for indication to the user P0 76 L3 L1 Input Voltage Volts Displays the supply voltage measured between L3 and L1 terminals...

Страница 28: ...a 123 Function Block Program Cycle Time R Data 32 User analog output 1 RW Data 124 Function Block Program ID R Data 33 User analog output 2 RW Data Reserved R 34 Reserved RW Data 130 kWh meter user re...

Страница 29: ...s trip P LOSS 14 Input phase loss trip SC F05 54 BACnet comms loss trip h O I 15 Instantaneous over current on drive output SC F06 55 Reserved th Flt 16 Faulty thermistor on heatsink SC F07 56 Reserve...

Страница 30: ...e as defined in EN 61000 4 4 2004 Test points Test Method Level Control Terminals Capacitive clamp 1kV at 5kHz Motor Power Terminals Capacitive clamp 2kV at 5kHz 1 PH Supply Power Terminals Coupling D...

Страница 31: ...Time Four individual deceleration ramps 0 600 seconds 0 01s resolution Frame 2 3 0 6000 seconds 0 1s resolution Frame 4 above 4 1 3 Overload Capacity Overload Capacity 110 of rated current for 60 seco...

Страница 32: ...5 Maximum non condensing 4 3 4 Vibration Levels Bump Test Testing in each of three mutually perpendicular axes in turn Reference standard IEC 60068 2 29 Severity 18g 6ms half sine No of bumps 600 100...

Страница 33: ...Current P1 08 The accumulator value reduces towards zero The time required depends on the actual load current as explained further below Motor Current 100 P1 08 The accumulator value remains static M...

Отзывы: