Invertek Drives eco OPTIDRIVE Скачать руководство пользователя страница 16

1.3.6.

 

Parameter Group 6 – Advanced Functions 

Par. 

Name 

Minimum 

Maximum 

Default 

Units 

P6-01 

Enable Firmware Upgrade 

Enables the firmware upgrade mode, allowing the User Interface firmware and/or the Power Stage Control firmware to be upgraded. 
Options are: 
0 : Disabled 
1 : Upgrade User Interface and Power Stage Control firmware 
2 : Upgrade User Interface firmware only 
3 : Upgrade Power Stage Control firmware only 

NOTE 

This parameter should not be adjusted by the User. The firmware upgrade process is carried out fully automatically using Optitools 
Studio PC software. 

P6-02 

Automatic Thermal Management Minimum Switching 
Frequency 

10 

Model 

Dependent 

10 

kHz 

This parameter defines the minimum effective switching frequency which the drive will use. 
During operation, the drive measures the power module temperature and will switch automatically to a lower switching frequency if 
the temperature reaches a pre-defined limit. This parameter determines the lowest frequency that can be used. In the event that the 
power module temperature continues to increase, the drive will trip on over temperature. 

P6-03 

Auto Reset Time Delay 

60 

20 

Sets the delay time which will elapse between consecutive drive reset attempts when Auto Reset is enabled in P2-36 

P6-04 

User Relay Output Hysteresis Control 

0.0 

25.0 

0.3 

This parameter works in conjunction with P2-11 and P2-13 = 2 or 3 to set a band around the target speed (P2-11 = 2) or zero speed 
(P2-11 = 3). When the speed is within this band, the drive is considered to be at target speed or Zero speed.  This function is used to 
prevent “chatter” on the relay output if the operating speed coincides with the level at which the digital / relay output changes state.  
e.g. if P2-13 = 3, P1-01 = 50Hz and P6-04 = 5%, the relay contacts close above 2.5Hz 

P6-08 

Maximum Speed Reference Frequency 

20 

kHz 

When the motor speed reference is to be controlled by a frequency input signal (connected to Digital input 3), this parameter is used 
to define the input frequency which corresponds to the maximum motor speed (set in P1-01).  This maximum frequency that can be 
set in this parameter must be in the range 5kHz to 20kHz. 
When set to 0, this function is disabled. 

P6-10 

Enable Function Block Program Operation 

0 : Function Block Program Disabled. 
1 : Function Block Prgram Enabled
. This parameter must be set to 1 to enable any Function Block Program loaded into the drive to 
operate. When set to 0, the Function Block Program will be disabled. 

P6-11 

Speed Holding Time on Enable 

250 

Defines a time period for which the drive will run at Preset Speed 7 (P2-07) when the Enable signal is applied to the drive. The preset 
speed can be any value from minimum to maximum frequency and in either direction. This function can be useful in applications 
requiring controlled start-up behaviour regardless of the normal system operation, and allows the user to program the drive to always 
start at the same frequency, with the same direction of rotation for a specified time period before returning to normal operation. 
This function can be used with pumps to provide a reverse spin on start-up to clear any potential blockages. 

P6-12 

Speed Holding / DC Injection Time on Disable 

250 

When P6-18 = 0, defines a time period for which the drive will run at Preset Speed 8 (P2-08) following removal of the Enable signal, 
before ramping to stop.   

Note 

Setting this parameter > 0 will result in the drive continuing to operate for the set time at the preset speed after the enable signal has 
been removed. It is important to ensure this method of operation is safe prior to using this function. 

P6-18 

DC Injection Braking Current 

0.0 

100.0 

0.0 

Defines the DC current level as a percentage of motor rated current (P1-08) that is applied to the motor when a stop command is 
received and the DC Injection function is activated. 

P6-22 

Cooling Fan Runtime Counter Reset 

0 : No Function 
1 : Reset
. Setting to 1 resets the internal Fan run-time counter to zero (as displayed in Index 1 of P0-35). 

P6-23 

Energy Consumption (kWh) Meter Reset 

0 : No Function 
1 : Reset
 . Setting to 1 resets internal kWh meter to zero (as displayed in Index 1 of P0-26 and Index 1 of P0-27). 

P6-24 

Maintenance Time Interval 

60000 

Hours 

Allows the user to define a maintenance interval period for the application. This defines the total number of run time hours which 
must elapse before the service indicator is displayed. This may be viewed on the drive OLED display, may be programmed to a relay 
output, and also sets a bit in the drive status word.  
When P6-25 is set to 1, the internal service interval counter is set to this value 

P6-25 

Maintenance Time Reset 

When this parameter is set to 1, the internal service interval counter is set to the value defined in P6-24 

P6-26 

Analog Output 1 Scaling 

0.0 

500.0 

100.0 

Defines the scaling factor as a % used for Analog Output 1 

P6-27 

Analog Output 1 Offset 

-500.0 

500.0 

0.0 

Defines the offset as a % used for Analog Output 1 
 

Содержание eco OPTIDRIVE

Страница 1: ...Optidrive Eco Advanced User Guide Revision 1 00 Optidrive Eco Parameter Set Overview 1 AC Variable Speed Drive 0 75kW 250kW 1HP 350HP 200 480 Volt 1 3 Phase Advanced User Guide Revision 1 00...

Страница 2: ...e time of release This user guide must be read in conjunction with the Optidrive Eco User Guide included with each product and in particular all relevant safety information and warnings The informatio...

Страница 3: ...5 Parameter Group 0 Monitoring Parameters Read Only 25 1 6 P6 28 Value Selection 29 2 Diagnostic and Fault Messages 30 3 Immunity Tests 31 3 1 Electrostatic Discharge ESD 31 3 2 Electrical Fast Trans...

Страница 4: ...c Read Write Group 2 P2 01 to P2 40 Extended Parameters Extended Read Write Group 3 P3 01 to P3 18 PID Controller Extended Read Write Group 4 P4 01 to P4 14 Motor Control Extended Read Write Group 5 P...

Страница 5: ...d nameplate voltage of the motor Volts The factory default setting of this parameter is drive model dependent as follows All kW HP models intended for 200 240 volt operation e g ODV 3 x2xxx xxF1x xN F...

Страница 6: ...from the fieldbus option module interface 5 Slave Mode The drive acts as a Slave to a connected Optidrive operating in Master Mode 6 BACnet MSTP Control Control via BACnet bus connected to the RJ45 s...

Страница 7: ...requency reference applied to the drive is within the band the Optidrive output frequency will remain at the upper or lower limit of the band P2 11 Analog Output 1 Terminal 8 Function Select 0 12 8 Di...

Страница 8: ...ve and no fault exists 2 At Target Frequency Speed Logic 1 when the output frequency matches the setpoint frequency Hysterisis is applied defined by P6 04 3 Output Frequency 0 0 Hz Logic 1 when the dr...

Страница 9: ...rror Limit Logic 1 when the PID Error exceeds the adjustable threshold 15 High or Low load detected Logic 1 when the output current falls outside of the load monitoring profile See P8 06 to P8 08 P2 1...

Страница 10: ...e signal level falls below 3mA 4 to 20mA Signal In the event that the signal falls below 3mA the Optidrive will ramp operate at Preset Speed 4 20 to 4mA Signal the Optidrive will trip and show the fau...

Страница 11: ...Speed 4 P2 04 4 Minimum Speed Terminal Start Following a stop and restart the drive will always initially run at the minimum speed P1 02 The drive starting is controlled from the digital inputs based...

Страница 12: ...applied to the Analog Input 1 P3 10 PID Feedback Signal Source Select 0 5 0 0 Analog Input 2 1 Analog Input 1 2 Motor Current The feedback value is scaled such that 100 0 P1 08 3 DC bus voltage The fe...

Страница 13: ...gain value for the speed controller when operating in Vector Speed or Vector Torque motor control modes P4 01 0 or 1 Higher values provide better output frequency regulation and response Too high a va...

Страница 14: ...put 1 status bit 1 indicates digital input 2 status etc 3 Analog Input 2 Signal Level 0 to 1000 0 to 100 0 4 Drive Heatsink Temperature 0 to 100 0 to 100 C 5 User Register 1 6 User Register 2 7 P0 80...

Страница 15: ...s option to be used P9 38 must be set to 1 and the PID User setpoint must not be utilised within any Function Block Code 2 User register 3 The value received by the drive in PDI 3 is transferred to Us...

Страница 16: ...d into the drive to operate When set to 0 the Function Block Program will be disabled P6 11 Speed Holding Time on Enable 0 250 0 s Defines a time period for which the drive will run at Preset Speed 7...

Страница 17: ...A higher value may cause a significant distortion in the motor current which may cause an aggressive rough motor behaviour P7 10 System Inertia Constant 0 600 10 System Load Inertia to Motor Inertia...

Страница 18: ...arameter enables the Load Profile Monitoring Function load current monitoring which can be used to detect belt failure in belt driven fan applications or Dry Pump Pump Blockage or broken impeller in P...

Страница 19: ...mber of assist pumps P8 14 1 or network slave drives P8 14 2 that are available in the Pump Staging application Setting the value to 0 disables Pump Staging P8 16 Pump Duty Switch Over Time 0 1000 0 H...

Страница 20: ...ng on their state Parameters defined as logic sources have the following range of possible settings No Drive LED Display Drive OLED Display Function 0 Off Safe Function permanently disabled or where a...

Страница 21: ...n Forward or Run Reverse commands are applied from external sources e g Fieldbus control signals or a Function Block Program Logic 1 Drive operation is allowed Logic 0 Drive stops using deceleration r...

Страница 22: ...d restart P9 18 Speed Reference Select Bit 0 Logic Source P9 19 Speed Reference Select Bit 1 Logic Source P9 20 Speed Reference Select Bit 2 Logic Source Note The active speed setpoint source can be s...

Страница 23: ...n Module Drive Tripped Relay 5 Cascade Option Module Drive Running 1 Relay Output 1 Function set by User Defined Source P9 42 Clean Trigger Input Edge Trigger 0 25 0 This parameter defines the source...

Страница 24: ...for various internal protection and monitoring functions P0 17 Stator Resistance Rs Ohms Displays the measured motor stator resistance providing an auto tune has been successfully completed P0 19 Casc...

Страница 25: ...ay shows user resettable time reset with P6 22 Second display shows none resettable time This is used for scheduled maintenance information P0 36 DC Bus Voltage Log 256ms Volts Diagnostic log for DC b...

Страница 26: ...alue in use for output relay settings that use hysteresis defined by P6 04 P0 62 Fire Mode Total Acitvation Counter Specifies the total number of times that Fire Mode has been activated on the drive P...

Страница 27: ...ltage Volts Displays the supply voltage measured between L2 and L3 terminals for indication to the user P0 76 L3 L1 Input Voltage Volts Displays the supply voltage measured between L3 and L1 terminals...

Страница 28: ...a 123 Function Block Program Cycle Time R Data 32 User analog output 1 RW Data 124 Function Block Program ID R Data 33 User analog output 2 RW Data Reserved R 34 Reserved RW Data 130 kWh meter user re...

Страница 29: ...s trip P LOSS 14 Input phase loss trip SC F05 54 BACnet comms loss trip h O I 15 Instantaneous over current on drive output SC F06 55 Reserved th Flt 16 Faulty thermistor on heatsink SC F07 56 Reserve...

Страница 30: ...e as defined in EN 61000 4 4 2004 Test points Test Method Level Control Terminals Capacitive clamp 1kV at 5kHz Motor Power Terminals Capacitive clamp 2kV at 5kHz 1 PH Supply Power Terminals Coupling D...

Страница 31: ...Time Four individual deceleration ramps 0 600 seconds 0 01s resolution Frame 2 3 0 6000 seconds 0 1s resolution Frame 4 above 4 1 3 Overload Capacity Overload Capacity 110 of rated current for 60 seco...

Страница 32: ...5 Maximum non condensing 4 3 4 Vibration Levels Bump Test Testing in each of three mutually perpendicular axes in turn Reference standard IEC 60068 2 29 Severity 18g 6ms half sine No of bumps 600 100...

Страница 33: ...Current P1 08 The accumulator value reduces towards zero The time required depends on the actual load current as explained further below Motor Current 100 P1 08 The accumulator value remains static M...

Отзывы: