   |   Optidrive Eco User Guide   |   

Version 3.05

www.invertekdrives.com

Par.

Parameter Name

Units

P0-36

DC Bus Voltage Log (256ms)

-

Diagnostic log for DC bus voltage. Values logged every 256mS with 8 samples total. Logging suspended on drive trip.

P0-37

DC Bus Voltage Ripple Log (20ms)

-

Diagnostic log for DC bus voltage ripple. Values logged every 20mS with 8 samples total. Logging suspended on drive trip.

P0-38

Heatsink Temperature Log (30s)

-

Diagnostic log for heatsink temperature. Values logged every 30S with 8 samples total. Logging suspended on drive trip.

P0-39

Internal Temperature Log (30s)

-

Diagnostic log for drive ambient temperature. Values logged every 30S with 8 samples total. Logging suspended on drive trip.

P0-40

Motor Current Log (256ms)

-

Diagnostic log for Motor Current. Values logged every 256mS with 8 samples total. Logging suspended on drive trip.

NOTE 

The above parameters (P0-36 to P0-40) are used to store the history of various measured levels within the drive at various regular time 

intervals prior to a trip. The values are frozen when a fault occurs and can be used for diagnostic purposes.

P0-41

Over Current Fault Counter

-

P0-42

Over Voltage Fault Counter

-

P0-43

Under Voltage Fault Counter

-

P0-44

Heatsink Over Temperature Fault Counter

-

P0-45

Reserved

-

P0-46

Ambient Over Temperature Fault Counter

-

NOTE 

These parameters (P0-41 to P0-46) contain a record of how many times certain critical faults have occurred during a drives operating 

lifetime. This provides useful diagnostic data.

P0-47

I/O Comms Fault Counter

-

Displays the number of communication errors detected by the I/O processor in messages received from the power stage processor 

since the last power up.

P0-48

DSP Comms Fault Counter

-

Displays the number of communication errors detected by the Power Stage processor in messages received from the I/O processor 

since the last power up.

P0-49

Modbus RTU / BACnet MSTP Fault Counter

-

This parameter is incremented every time an error occurs on the Modbus RTU communication link. This information can be used for 

diagnostic purposes.

9

Extended P

arameters

Содержание Eco Optidrive ODV-3-220043-1F12-SN

Страница 1: ...nput General Information and Ratings Introduction Mechanical Installation Electrical Installation LED Keypad and Display Operation Commissioning Parameters Extended Parameters Serial Communications Co...

Страница 2: ...5 2 Selecting the Language on the OLED Display 32 5 3 Additional Display Messages 32 5 4 Changing Parameters 33 5 5 Parameter Factory Reset User Reset 34 5 6 Resetting the Drive Following a Trip 34 5...

Страница 3: ...corporated complies with the EMC legislation of the country of use Within the European Union equipment into which this product is incorporated must comply with the EMC Directive 2004 108 EC When using...

Страница 4: ...control cables whilst power is applied to the drive or to the external control circuits Danger Indicates a potentially hazardous situation other than electrical which if not avoided could result in da...

Страница 5: ...621 100 3F12 MN 6A 30 40 1 10 No ODV 3 621500 3F12 MN 6A 37 50 150 No ODV 3 621800 3F12 MN 6B 45 60 180 No ODV 3 622020 3F12 MN 6B 55 75 202 No 380 480 Volt 3 Phase Input Model Code Frame kW HP Amps...

Страница 6: ...3F1X TN ODV 3 220070 3F1D TN 2A 1 5 2 7 Yes ODV 3 220105 3F1X TN ODV 3 220105 3F1D TN 2A 2 2 3 10 5 Yes ODV 3 320180 3F1X TN ODV 3 320180 3F1D TN 3 4 5 18 Yes ODV 3 320240 3F1X TN ODV 3 320240 3F1D T...

Страница 7: ...5 37 50 72 Yes ODV 3 540900 3F1N TN 5 45 60 90 Yes ODV 3 641 100 3F1N TN 6 55 75 1 10 No ODV 3 641500 3F1N TN 6 75 100 150 No ODV 3 641800 3F1N TN 6 90 150 180 No ODV 3 742020 3F1N TN 7 1 10 175 202 N...

Страница 8: ...short this means that the low harmonic drives do not require an input choke and should not have one installed drives outside of the above frame sizes and supply voltage number of phases are of standa...

Страница 9: ...installation For an up to date list of UL compliant products please refer to UL listing NMMS E226333 The drive can be operated within an ambient temperature range as stated in section 10 1 Environmen...

Страница 10: ...89 18 1 39 9 6A 614 24 17 286 1 1 25 320 12 59 578 22 75 200 7 87 200 7 87 32 70 5 6B 726 28 58 330 13 320 12 59 680 26 77 225 8 85 225 8 85 43 94 8 Mounting Bolts Tightening Torques Frame Size Metric...

Страница 11: ...15 20 28 175 6 89 520 20 47 8 0 31 8 50 0 34 15 0 60 23 50 7 6 865 34 06 330 12 99 330 12 99 830 32 68 200 7 87 840 33 07 10 0 39 1 1 0 44 22 0 86 55 121 2 7 1280 50 39 330 12 99 360 14 17 1245 49 02...

Страница 12: ...in kg Ib 2 257 10 12 188 7 40 239 9 41 200 7 87 178 7 01 220 8 66 29 1 12 4 2 0 17 8 5 0 33 4 8 10 6 3 310 12 20 21 1 8 29 266 10 47 252 9 90 200 7 87 277 10 89 33 1 31 4 2 0 17 8 5 0 33 7 7 16 8 Mou...

Страница 13: ...gases or liquids conductive contaminants such as condensation carbon dust and metallic particles and sprays or splashing water from all directions High moisture salt or chemical content environments s...

Страница 14: ...use a suitable flat blade screwdriver to pull the release tab downwards and lift the bottom of the drive away from the rail first 3 8 Guidelines for Mounting IP55 Units Before mounting the drive ensur...

Страница 15: ...m mounting clearances as shown in the table below must be observed The mounting site and chosen mountings should be sufficient to support the weight of the drives Using the drive as a template or the...

Страница 16: ...table operating environment this should include Ambient temperature is at or below that set out in the section 1 1 1 Environmental with any relevant derating applied Heat sink fans where fitted freely...

Страница 17: ...and 2 x 28 3mm 1 PG13 5 and 2 PG21 1 x M20 and 2 x M25 Size 3 IP66 1 x 20 5mm and 2 x 28 3mm 1 PG13 5 and 2 PG21 1 x M20 and 2 x M25 UL rated ingress protection Type is only met when cables are instal...

Страница 18: ...able for rigid conduit system connection This manual is intended as a guide for proper installation Invertek Drives Ltd cannot assume responsibility for the compliance or the non compliance to any cod...

Страница 19: ...nnected to a suitable ground location to maintain touch potentials within safe limits In addition the motor ground must be connected to one of the ground terminals on the drive 4 2 4 Ground Fault Moni...

Страница 20: ...ding EMC cable gland shielded to motor chassis 4 3 2 Recommended Cable Types by EMC Category Rated Supply Voltage Number of Input Phases Frame Size Effective Switching Frequency Maximum Motor Cable Le...

Страница 21: ...ted at the motor end using an EMC type gland allowing connection to the motor body through the largest possible surface area Where drives are mounted in a steel control panel enclosure the cable scree...

Страница 22: ...t current at the Optidrive Power terminals as defined in IEC60439 1 is 100kA 4 5 Optional Input Chokes The majority of the Optidrive Eco product range is based on a low harmonic solution using film ca...

Страница 23: ...signed with low impedance to HF signals are recommended as a minimum Installation within a suitable steel or copper tube is generally also acceptable The cable screen should be terminated at the motor...

Страница 24: ...g of the drive makes no difference to the available duration of the overload condition NOTE The 45kW 400V Eco model ODV 3 540900 3 overload capability follows that shown in the variable torque table i...

Страница 25: ...DC 10Volt DC Output On board 10V DC Supply 10 mA 6 AI 1 DI 4 Analog Input 1 Digital Input 4 Speed Reference 1 0 10V 4 10 3 24 7 0V COM 0 Volt Common 0V Common for AI AO DI DO 8 AO 1 Analog Output 1 M...

Страница 26: ...8 1 Parameter Group 2 Extended Parameters on page 45 The function of the analog input e g for speed reference or PID feedback for example is defined by parameters P1 12 and P1 13 The function of thes...

Страница 27: ...lies with the definition of Safe torque off as defined by IEC 61800 5 2 2007 The STO Function also corresponds to an uncontrolled stop in accordance with category 0 Emergency Off of IEC 60204 1 This m...

Страница 28: ...on Sto F 29 A fault has been detected within either of the internal channels of the STO circuit Refer to your Invertek Sales Partner 4 11 5 STO Function response time The total response time is the ti...

Страница 29: ...source 1 7 Safety relay Protective Capped Trunking or equivalent to prevent STO Cable short circuit to an external Voltage source Safety relay Protected shielded cables Wires should be protected again...

Страница 30: ...thod selected in P1 13 o De energise the STO inputs Drive will display InHibit o Give a start command as per the start source method selected in P1 13 and check that the drive still displays Inhibit a...

Страница 31: ...isplay Main Displayed Parameter Shows which of the selectable parameters is currently being shown on the main display e g Motor Speed Motor Current etc Operating Information Provides a real time displ...

Страница 32: ...abled Drive is enabled running display shows the output frequency Hz Press the Navigate key to select alternative displays Press the Navigate key for 1 second The display will show the motor current A...

Страница 33: ...ers LED Display TFT and OLED Display ECO 01 ECO 01 ECO 01 ECO 01 ECO 01 Stop P1 01 P1 08 30 0A P1 08 Stop 15kW 400V 3Ph 50 0Hz 30 0A P1 08 30 0 3 0 30 0A 15kW 400V 3Ph Press and hold the Navigate key...

Страница 34: ...Stop All parameters are reset to Factory defaults 5 6 Resetting the Drive Following a Trip Optidrive ECO has many protection features designed to protect both the drive and motor from accidental dama...

Страница 35: ...ble parameter group will be selected 5 8 3 Setting a Parameter to the Minimum Value 0 Whilst editing a parameter value press the Up and Down keys simultaneously The parameter will be set to the lowest...

Страница 36: ...r through a boiler it may be necessary to set a speed to ensure the boiler does not run dry during operation 6 1 3 Acceleration and Deceleration Ramp Times Optidrive Eco units are factory set with acc...

Страница 37: ...mum Default Units P1 01 Maximum Frequency Speed Limit P1 02 500 0 50 0 60 0 Hz Rpm Maximum output frequency or motor speed limit Hz or Rpm If P1 10 0 the value entered displayed is in Rpm NOTE The max...

Страница 38: ...current This parameter is also effective when using alternative motor types P4 01 3 4 or 5 In this case the boost current level is defined as 4 x P1 1 1 x P1 08 P1 12 Primary Command Source 0 6 0 0 Te...

Страница 39: ...eset 2 8 O Stop C Run Enable O Fire Mode 1 C Normal Operation 1 O Remote Ctrl C Local Ctrl Analog In 1 O Preset 1 C Preset 2 9 3 Keypad Speed Reference O Stop C Run Enable O Normal Operation C Preset...

Страница 40: ...When disabled Preset speed 8 can be selected as per preset speeds 1 4 P2 09 Skip Frequency Centre Point P1 02 P1 01 0 0 Hz Rpm Defines the centre point of the skip frequency band The width of the skip...

Страница 41: ...en the motor current exceeds the adjustable limit 6 Motor torque limit Logic when the motor torque exceeds the adjustable limit 7 Analog input 2 limit Logic when the signal applied to the Analog Input...

Страница 42: ...0 100 0 Setting the upper limited value for P2 1 1 and P2 15 please refer to P2 1 1 or P2 15 P2 17 Relay 1 AO1 Lower Limit 0 P2 16 0 0 Setting the lower limited value for P2 1 1 and P2 15 please refer...

Страница 43: ...unction using the OptiTools Studio Suite PC software In addition if P2 25 0 P1 02 0 P2 10 0 and P2 09 P1 02 this ramp time is applied to both acceleration and deceleration when operating below minimum...

Страница 44: ...ly start if Digital Input 1 is closed to Following a trip the drive will make up to 5 attempts to restart at 20 second intervals The drive must be powered down to reset the counter The numbers of rest...

Страница 45: ...P3 03 is set to 0 by default which disables the differential time constant Care must be taken when adjusting this value outside of its default value P3 04 PID Operating Mode 0 1 0 0 Direct operation...

Страница 46: ...drive will monitor the PID feedback level for the time entered in P3 16 If the PID feedback level does not exceed the threshold entered in P3 17 before the time in P3 16 expires then the drive will tr...

Страница 47: ...ulator When P4 12 is enabled the value is retained during power off P4 13 Output Phase Sequence 0 1 0 0 U V W 1 U W V Direction of motor rotation when operating in a forward direction will be reversed...

Страница 48: ...Select 0 7 0 When using an optional Fieldbus interface this parameter configures the parameter source for the 3rd process data word transferred from the drive to the network master during cyclic commu...

Страница 49: ...0 0 25 0 0 3 P6 08 Max Speed Reference Frequency 0 20kHz 0 kHz P6 10 Function Block Program Enable 0 Disabled 0 1 Enabled P6 11 Speed Hold Time on Enable 0 250s 0s P6 12 Speed Hold DC Injection Time...

Страница 50: ...ckage P8 02 Pump Stir Activation Time 1 6000 10 Seconds Set the time period that the stir function will be active once triggered excludes time for deceleration to stop P8 03 Pump Clean Function Select...

Страница 51: ...0 1 0 When Fire mode is assigned to a digital input on the drive then the logic configuration for the input is set by P8 09 to allow normally open or normally closed activation Default behaviour is f...

Страница 52: ...0 P8 17 30 0 Hz Rpm This parameter defines the speed at which an Assist Pump is stopped when using the Pump Cascade or Optiflow feature When the drive output decreases below this threshold one of the...

Страница 53: ...e P9 19 Speed Reference Select Input 1 P9 20 Speed Reference Select Input 2 P9 21 Preset Speed Select Input 0 P9 22 Preset Speed Select Input 1 P9 23 Preset Speed Select Input 2 P9 28 Motorised Pot Up...

Страница 54: ...plays the output level of the PID controller P0 11 Motor Voltage Volts Displays the instantaneous output voltage from the drive to the motor P0 12 Output Torque Nm Displays the instantaneous output to...

Страница 55: ...29 Drive Type Displays the type details of the drive Three entry display First display Frame size and input voltage level Second display Power rating Third display Output phase count P0 30 Drive Seri...

Страница 56: ...easured levels within the drive at various regular time intervals prior to a trip The values are frozen when a fault occurs and can be used for diagnostic purposes P0 41 Over Current Fault Counter P0...

Страница 57: ...ls and inter drive communication The Modbus interface allows connection to a Modbus RTU network as described in section 10 2 Modbus RTU Communications 10 1 1 RS 485 Communications Electrical Connectio...

Страница 58: ...order to reset any active faults or trips on the drive This bit must be reset to zero once the fault has been cleared Bit 3 Coast stop request Set to 1 to issue a coast stop command 2 Command Speed R...

Страница 59: ...e read from the drive and written to depending on the operating mode of the drive some parameters cannot be changed whilst the drive is enabled for example When accessing a drive parameter via Modbus...

Страница 60: ...s Ramp Control This parameter determines whether the acceleration and deceleration time of the drive is controlled by the drive internal parameters P1 03 Acceleration Time P1 04 Deceleration Time or c...

Страница 61: ...of digital input 2 ON OFF BV14 Digital Input 3 R Status of digital input 3 ON OFF BV15 Digital Input 4 R Status of digital input 4 ON OFF BV16 Digital Input 5 R Status of digital input 5 ON OFF BV17 D...

Страница 62: ...ercent AV15 Speed Reference C Speed reference value object Hertz AV16 User Ramp Time W User ramp value Seconds AV17 User PID Reference W PID controller user reference Percent AV18 User PID Feedback W...

Страница 63: ...ftware Revision Protocol Version Protocol Revision Protocol Services Supported Protocol Object Type Supported Object List Max APDU Length Accepted Segmentation Supported APDU Timeout Number of APDU Re...

Страница 64: ...d Object Types Supported An object type is supported if it may be present in the device For each standard Object Type supported provide the following data 1 Whether objects of this type are dynamicall...

Страница 65: ...Does the BBMD support network address translation Yes No Network Security Options Non secure Device is capable of operating without BACnet Network Security Secure Device is capable of using BACnet Ne...

Страница 66: ...x 500 600 Volts 10 3 50 60 Hz 11 3 Phase Imbalance All three phase Optidrive Eco units have phase imbalance monitoring The maximum permissible voltage imbalance between any two phases is 3 for full lo...

Страница 67: ...M 100 330 11 4 3 380 480 Volts 3 Phase Input Models Frame Size Output Current Capacity Typical Power Rating Nominal Input Current Fuse or MCB Type B Maximum Cable Size Maximum Motor Cable Length A kW...

Страница 68: ...Please see section 4 9 Control Terminal Wiring for further information The PWM output switching from any inverter when used with a long motor cable length can cause an increase in the voltage at the...

Страница 69: ...to phase suitable for over voltage category iii and shall provide protection for a rated impulse withstand voltage peak of 2 5kV Where X is the supply voltage UL Listed ring terminals lugs must be us...

Страница 70: ...ated on the front face of the unit as shown EMC L1 L2 L3 Frame Size 5 Frame Size 5 units have EMC Filter disconnection points only located on the front face of the unit as shown Frame Size 6a 6b Frame...

Страница 71: ...4kHz 8kHz 10kHz 12kHz 14kHz 16kHz 18kHz 20kHz 24kHz 32kHz IP66 2 N A N A 0 0 0 0 0 0 N A N A 3 N A N A 0 0 0 6 N A N A N A N A IP55 4 N A N A 0 0 12 23 33 41 N A N A 5 N A N A 0 0 1 1 23 36 42 N A N...

Страница 72: ...red at 256ms intervals prior to a trip in parameter P0 36 This fault is generally caused by excessive regenerative energy being transferred from the load back to the drive When a high inertia or over...

Страница 73: ...5 Parameter Factory Reset User Reset 21 Motor PTC over heat Motor PTC Over Temperature The connected motor PTC device has caused the drive to trip analog input 2 configured for PTC device 22 Cooling F...

Страница 74: ...to the power rating of the connected drive 45 Incorrect Supply Phase Sequence L1 L2 L3 Phase sequence is incorrect Applies to Frame Size 8 drives only indicates that the incoming power supply phase s...

Страница 75: ...Version 3 05 Optidrive Eco User Guide 75 www invertekdrives com...

Страница 76: ...82 HEMAN IN_V3 05U 82 HEMAN IN_V3 05 Invertek Drives Ltd Offa s Dyke Business Park Welshpool Powys SY21 8JF United Kingdom Tel 44 0 1938 556868 Fax 44 0 1938 556869 www invertekdrives com...

Страница 77: ...The Invertek Eco range is available to purchase online at https invertek inverterdrive com...

Отзывы: