9.5. Advanced Parameters
For Advanced Parameters, basic information only is provided in this guide. The parameter functions are described more fully in
Optitools Studio PC software.
9.5.1. Parameter Group 6 – Advanced Configuration
Par.
Function
Setting Range
Default
Notes
P6-01
Firmware Upgrade Enable
0
Disabled
0
This parameter should not be
adjusted by the user.
1
Update I/O & P/S
2
Update I/O
3
Update P/S
P6-02
Thermal Overload Management
4 – 32kHz (Model Dependent)
4 kHz
Minimum Effective Switching
Frequency.
P6-03
Auto Reset Time Delay
1 – 60 Seconds
20s
P6-04
Relay Output Hysteresis
0.0 – 25.0%
0.3%
P6-08
Max Speed Reference Frequency
0 – 20kHz
0 kHz
P6-10
Function Block Program Enable
0
Disabled
0
1
Enabled
P6-11
Speed Hold Time on Enable
0 – 250s
0s
P6-12
Speed Hold / DC Injection Time on Disable
0 – 250s
0s
P6-18
DC Injection Current
0.0 – 100.0%
0.0%
This function is active only
for Induction Motors (IM)
and Synchronous Reluctance
Motor (SyncRM).
P6-22
Reset Fan Run Time
0
No Reset
0
1
Reset
P6-23
Reset Energy Meters
0
No Reset
0
1
Reset
P6-24
Maintenance Time Interval
0 – 60000 Hours
0 Hours
P6-25
Reset Maintenance Indicator
0
No Reset
0
1
Reset
P6-26
Analog Output 1 Scaling
0.0 – 500.0%
100.0%
P6-27
Analog Output 1 Offset
-500.0 – 500.0%
0.0%
P6-28
P0-80 Display Index
0 - 255
0
P6-29
User Default Parameters
0
No Function
0
1
Save user parameters
2
Clear user parameters
P6-30
Level 3 (Advanced) Access Code
0 – 9999
201
9
Extended P
arameters