Toogle mode
1-Pulse mode
Power On State
– output status after power supply switching on and in Safety mode
Time On
– time of output switching on in Toggle and 1-Pulse modes.
Time Off
– time of outpput switching off in Toggle mode.
5.2 Output control - Out State Test
This field is used to test outpput. In possition OUT1 it switches on or off the output.
5.3 Reading card number - Card Serial Number
Field shows the last read transponder code.
5.4 RS485 – Configuration of transmission RS485
The field is used to configure the device communication.
MODE
(setting 9 bit transmission):
None
Odd
Even
Mark – bit ‘1’ (the same mode as the double stop)
Space – bit ‘0’
BaudRate
– field to select baud rate
Device Address
– address of the device that will be in the MODBUS network
TimeOut
– time (given in 100 ms) after which, in case of the absence of transmission, the device
goes into failure (Safety mode) and the Timeout flag will be set.
Safety mode enable
– activation of outputs control in case of the absence of communication.
t
on