6.10 Communication protocol description
Byte
1
2
3
4
5
6
7
8
9
10
11
Name
SOF CMD CH Data 1 Data 2
Data 3 Data 4 Data 5 Data 6 Data 7 CRC
Return
Command
Set output
15
1
0-7 Mode
[1-3]*
ON/OFF
[0,1]
TON
LSB*
TON
MSB*
TOFF
LSB*
TOFF
MSB*
Restart
state**
CRC
ON or NO
Read
channel
parameters
15
2
0-7
x
x
x
x
x
x
x
CRC
Set counter
15
10
0-7
[0:7]
[8:15]
[16:23] [24:31]
CRC
Read
counter
15
11
0-7
[0:7]
[8:15]
[16:23] [24:31]
CRC
WWW
control
15
99
x
1
-status
0x55 –
off
all
other -
on
x
x
x
x
x
x
CRC
ON or NO
Read
channels
15
100
x
x
x
x
x
x
x
x
CRC
CH7-CH0 Chx – 2
bytes; 1
output
state 2 coil
state
Read
channel
name
15
101
0-7
x
x
x
x
x
x
x
CRC
String
Read
device
name
15
200
x
x
x
x
x
x
x
x
CRC
String
*only Lantick and PE-2-1
** only Lantick
*** - Reading parameters returns:
SOF
CMD
Ch
Data 1
Data 2
Data 3
Data 4
Data 5
Data 6
Data 7
CRC
15
2
0-7
Mode[1-3],
100-input
ON/OFF[0,1]
TON
LSB
TON
MSB
TOFF
LSB
TOFF
MSB
Restart state
CRC
Description
Value
State
ON/OFF
0
off
1
on
MODE
1
static
2
toggle
3
1-pulse
CRC
Byte sum
Содержание NANO TEMP