Electrical Control Function
152
Electrical Control System
controller, the buzzer will emit a sound and this indicates the follow me function is initiated. But when the
indoor PCB receives signal which sent from remote controller every 3 minutes, the buzzer will not
respond. When the unit is running with follow-me function, the PCB will control the unit according to the
temperature from follow-me signal, and the temperature collection function of room temperature sensor
will be shielded.
2) When the follow-me function is available, the PCB will not respond according to the setting temperature
from follow-me signal every 3 minutes.
3) The PCB will take action to the mode change information from remote controller signal, and the
follow-me function will be turned off. (if the wired remote controller does not initiate follow me function).
4) When the unit is running with follow-me function, if the PCB doesn’t receive any signal from remote
controller for 7 minutes or pressing FOLLOW ME button again, the follow-me function will be turned off
automatically, and the temperature collection function of room temperature sensor will be available, the
PCB will control the unit according to the room temperature detected from its own room temperature
sensor and setting temperature.
5)
When the indoor PCB receives the follow-me signal from wired remote controller, the control is the
same as that from wireless remote controller, but buzzer will not respond. When the PCB receives
turning-off follow-me signal from wired remote controller, the unit will quit follow-me function at once.
The follow-me function controlled by wired remote controller prevails that by wireless remote controller.
1.3.11 Point Check Function(Excluding 12K)
There is a check switch in outdoor PCB.
Press the switch SW1 to check the states of unit when the unit is running.
Press the switch N times it will display the content corresponding to No. N. After getting into the check
function, it will display No. N with 1.5s, meanwhile the low bit decimal of digit display flashing, indicated to
get into the check function display. After 1.5s, it will display the content corresponding to No. N.
the digital display tube will display the follow procedure when push SW1 each time.
N
Display
Remark
00
Normal display
Display running frequency, running state or malfunction code
01
Indoor unit capacity demand code
Actual data*HP*10
If capacity demand code is higher than 99, the digital display
tube will show single digit and tens digit. (For example, the
digital display tube show “5.0”,it means the capacity demand
is 15. the digital display tube show “60”,it means the capacity
demand is 6.0)
02
Amendatory capacity demand code
03
The frequency after the capacity requirement
transfer
04
The frequency after the frequency limit
05
The frequency of sending to 341
06
Indoor unit evaporator outlet temp.(heating T2
,
cooling T2B)
If the temp. is lower than -9 degree, the digital display tube will
show “-9”.If the temp. is higher than 70 degree, the digital
Содержание LCAC
Страница 1: ...SERVICE MANUAL english LCAC AIR CONDITIONING SYSTEMS...
Страница 2: ......
Страница 4: ...ii General Information...
Страница 15: ...Service Space 12 Indoor Units 3 Service Space 1000mm 1000mm 1000mm 1000m m...
Страница 17: ...Air Velocity Distributions Reference Data 14 Indoor Units 36 42K Cooling Heating...
Страница 18: ...Air Velocity Distributions Reference Data Indoor Units 15 50 60K Cooling Heating...
Страница 23: ...Field Wiring 20 Indoor Units 9 Field Wiring...
Страница 24: ...Wiring diagram Indoor Units 21 10 Wiring diagram V4MCI 24 V4MCI 36 V4MCI 42 V4MCI 50 V4MCI 60...
Страница 31: ...Static Pressure 28 Indoor Units 4 Static Pressure V4MDI 12 V4MDI 18...
Страница 32: ...Static Pressure Indoor Units 29 V4MDI 24...
Страница 33: ...Static Pressure 30 Indoor Units V4MDI 36 V4MDI 42 V4MDI 50 V4MDI 60...
Страница 38: ...Wiring Diagram 36 Indoor Units 10 Wiring Diagram V4MDI 12 V4MDI 18 V4MDI 24 V4MDI 42 V4MDI 50 V4MDI 60...
Страница 39: ...Wiring Diagram Indoor Units 37...
Страница 43: ...Service Space 42 Indoor Units 3 Service Space...
Страница 52: ...Wiring Diagram Indoor Units 51 10 Field Wiring...
Страница 53: ...Wiring Diagram 52 Indoor Units 11 Wiring diagram V4MKI 18...
Страница 54: ...Ceiling Floor Type Indoor Units 53 V4MKI 36 V4MKI 24...
Страница 55: ...Wiring Diagram 54 Indoor Units...
Страница 59: ...Service Space 58 Indoor Units 3 Service Space...
Страница 63: ...Wiring Diagram 62 Indoor Units 9 Field Wiring V4MCRI 12 V4MCRI 18...
Страница 64: ...Field Wiring Indoor Units 63 10 Field Wiring V4MCRI 12 V4MCRI 18...
Страница 68: ...Console Type Console Type 67 2 Dimensions 16 Drain pipe 195 Hanging arm Unit mm 700 600 210...
Страница 69: ...Console Type 68 Console Type 3 Service Space...
Страница 74: ...Console Type Console Type 73 9 Field Wiring V4MLI 12 V4MLI 18...
Страница 75: ...Console Type 74 Console Type 10 Field Wiring V4MLI 12 V4MLI 18...
Страница 78: ...Dimensions Floor standing Type 77 2 Dimensions H W D Dimension Model W mm D mm H mm V4MFI 24 500 315 1700...
Страница 79: ...Service Space 78 Floor standing Type 3 Service Space...
Страница 80: ...Wiring Diagrams Floor standing Type 79 4 Wiring Diagrams V4MFI 24...
Страница 85: ...Field Wiring 84 Floor standing Type 9 Field Wiring...
Страница 86: ...Wiring diagram Floor standing Type 85 10 Wiring diagram V4MFI 24...
Страница 89: ...Dimensions 88 Floor standing Type 2 Dimensions Dimension Mode W mm D mm H mm V1MFI 50B V1MFI 66B 610 390 1925...
Страница 90: ...Service Space Floor standing Type 89 3 Service Space...
Страница 96: ...Field Wiring Floor standing Type 95 9 Field Wiring...
Страница 97: ...Field Wiring 96 Floor standing Type 10 Field Wiring V1MFI 50B V1MFI 66B...
Страница 100: ...Dimensions 100 Outdoor Units Model KBtu h Unit mm W D H W1 A B 50 60 952 415 1333 1045 634 404...
Страница 103: ...4 Electric Characteristics U4MRS 12 U4MRS 18 U4MRS 24 U4MRS 36 U4MRT 42 U4MRT 50 U4MRT 60...
Страница 106: ...Wiring diagram 106 Outdoor Units 7 Wiring diagram U4MRS 12 U4MRS 18...
Страница 107: ...Wiring diagram Outdoor Units 107 U4MRS 24 U4MRS 36...
Страница 108: ...Wiring diagram Outdoor Units 109 U4MRT 42 U4MRT 50 U4MRT 60...
Страница 154: ...Troubleshooting Electrical Control System 157 2 1 8 Display board of Floor standing...
Страница 166: ...Troubleshooting Electrical Control System 169 2 4 4 2 E1 malfunction For current loop communication...
Страница 168: ...Troubleshooting Electrical Control System 171 2 4 4 3 J4 malfunction J4...
Страница 171: ...Troubleshooting 174 Electrical Control System 2 4 4 6 F5 malfunction The same as E3 in indoor 2 4 4 7 J5 malfunction J5...
Страница 177: ...Troubleshooting 180 Electrical Control System 2 4 4 13 J0 malfunction J0...
Страница 190: ...Scan here to download the latest version of this manual LCAC AIR CONDITIONING SYSTEMS...