INSTALLATION AND ASSEMBLY
iV-Office ventilation device
•
Installation and operating instructions
►
Route the fan BUS, 3-wire (stranded wire) from
the control unit to the wall opening of the ventilation
device.
►
Re-plaster the plaster/masonry slot.
Ensure
that the cable end protrudes approx.
500 mm (min. wall thickness X, section 4.4)
into the interior.
NOTE:
Laying cables whose sheathing
is not resistant to plaster under plaster
leads to short circuits and cable fire!
• Route cables that are not plaster-resistant
in the conduit.
The fan BUS is installed.
►
Mill the plaster/masonry slot between the control
unit and the wall opening.
Make sure
that the plaster/wall slot for the cable to
the control unit is positioned at a 45° angle to the
bottom left of the wall opening.
►
Seal off the wall opening from the inside and outside
until you are ready to install the wall sleeve.
The plaster/wall slot for the cable (fan BUS)
has been created.
NOTE:
The use of too small a cable
cross-section
leads to too great a voltage
drop and/or contact is not guaranteed!
• For the fan BUS, use a cable cross-section
of at
least 0.75 mm²
.
6 – 16 V DC
230 V AC
Wall slot cutter, hammer, chisel, fan BUS (3-wire)
Requirements:
The wall opening is created.